59CU5A: Installation, Start-up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
7
ELECTROSTATIC DISCHARGE (ESD)
PRECAUTIONS PROCEDURE
1. Disconnect all power to the furnace. Multiple disconnects may be
required. DO NOT TOUCH THE CONTROL OR ANY WIRE
CONNECTED TO THE CONTROL PRIOR TO DISCHARGING
YOUR BODY’S ELECTROSTATIC CHARGE TO GROUND.
2. Firmly touch the clean, unpainted, metal surface of the furnace
chassis which is close to the control. Tools held in a person’s hand
during grounding will be satisfactorily discharged.
3. After touching the chassis, you may proceed to service the control
or connecting wires as long as you do nothing to recharge your
body with static electricity (for example; DO NOT move or shuffle
your feet, do not touch ungrounded objects, etc.).
4. If you touch ungrounded objects (and recharge your body with
static electricity), firmly touch a clean, unpainted metal surface of
the furnace again before touching control or wires.
5. Use this procedure for installed and uninstalled (ungrounded)
furnaces.
6. Before removing a new control from its container, discharge your
body’s electrostatic charge to ground to protect the control from
damage. If the control is to be installed in a furnace, follow items 1
through 4 before bringing the control or yourself in contact with the
furnace. Put all used and new controls into containers before
touching ungrounded objects.
7. An ESD service kit (available from commercial sources) may also
be used to prevent ESD damage.
ACCESSORIES
See Product DataSpecification Sheet for a list of accessories for this
product.
LOCATION
IMPORTANT:
IMPORTANT: Clearances for Condensate Trap
Before locating furnace, refer to condensate trap installation instructions
section for required clearances for trap installation.
A200083
Fig. 6 – Trap Clearance in Horizontal Application
NOTE:
Local codes may require a drain pan and condensate tray when a
condensing furnace is installed over a finished ceiling.
A200084
Fig. 7 – Trap Clearance in Upflow Application
General
These furnaces are shipped with materials to assist in proper furnace
installation. These materials are shipped in the main blower
compartment.
Loose parts bag contents, see
.
This furnace must:
• be installed so the electrical components are protected from water.
• not be installed directly on any combustible material other than wood
flooring (refer to SAFETY CONSIDERATIONS).
• be located close to the chimney or vent and attached to an air
distribution system. Refer to Air Ducts section.
• be provided ample space for servicing and cleaning. Always comply
with minimum fire protection clearances, see
CAUTION
!
FURNACE RELIABILITY HAZARD
Failure to follow this caution may result in unit component damage.
Electrostatic discharge can affect electronic components. Take
precautions during furnace installation and servicing to protect the
furnace electronic control. Precautions will prevent electrostatic
discharges from personnel and hand tools which are held during the
procedure. These precautions will help to avoid exposing the control to
electrostatic discharge by putting the furnace, the control, and the
person at the same electrostatic potential.
CAUTION
!
PERSONAL RELIABILITY HAZARD
Failure to follow this caution may result in unit component damage.
Furnace may not be used for heating buildings under construction.
ADDITIONAL 1” CLEARANCE BELOW TRAP
RECOMMENDED FOR SERVICE
6-3/8”
Rubber elbow
or field supplied
PVC tee
Casing to elbow
or PVC tee = 3”
Casing with offset
adapter = 4-3/4”