59CU5A: Installation, Start-up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
24
In the state of Massachusetts:
For recommended gas pipe sizing, see
. Risers must be used to
connect to furnace and to meter. Support all gas piping with appropriate
straps, hangers, etc. Use a minimum of one hanger every 6 ft. (2 M).
Joint compound (pipe dope) should be applied sparingly and only to
male threads of joints.
An accessible manual equipment shutoff valve MUST be installed
external to furnace casing and within 6 ft. (2 M) of furnace.
Install a sediment trap externally in the riser leading to furnace, see
. Connect a capped nipple into lower end of tee. Capped nipple
should extend below level of furnace gas controls. Place a ground
joint
union between furnace gas control valve and exterior manual
equipment
gas shutoff valve.
A 1/8-in. (3 mm) NPT
plugged tapping, accessible for test gauge
connection, MUST be
installed immediately upstream of gas supply
connection to
furnace and downstream of manual equipment shutoff
valve.
Piping should be pressure and leak tested in accordance with the current
edition of the
NFGC in the United States, local, and
national plumbing
and gas codes before the furnace has been
connected. After all
connections have been made, purge lines and
check for leakage at
furnace prior to operating furnace.
NOTE:
The furnace gas control valve inlet pressure tap connection
is
suitable to use as test gauge connection providing test
pressure DOES
NOT exceed maximum 0.5 psig (14-in. w.c.) stated
on gas control valve,
see
If pressure exceeds 0.5 psig (14-in. w.c.), gas supply pipe must be
disconnected from furnace and capped before and during supply
pipe
pressure test. If test pressure is equal to or less than 0.5 psig
(14-in. w.c.),
turn off electric shutoff switch located on furnace gas control valve and
accessible manual equipment shutoff valve before and during supply
pipe pressure test. After all connections have been made, purge lines and
check for leakage at furnace prior to operating furnace.
The gas supply pressure shall be within the maximum and minimum
inlet supply pressures marked on the rating plate with the furnace
burners ON and OFF.
Gas entry can be from left or right side, or top panel, see
and
Gas Pipe Grommet
For direct vent (2-pipe) applications, the knockout for the gas pipe must
be sealed to prevent air leakage. Remove the knockout, install the
grommet in the knockout, then insert the gas pipe. The grommet is
included in the loose parts bag, see
.
Table 12 – Maximum Capacity of Pipe
* Cubic ft of gas per hr for gas pressures of 0.5 psig (14-in. w.c.) or less and a pressure drop of
0.5-in. w.c. (based on a 0.60 specific gravity gas). Ref: (
) and 6.2 of NFPA54/ANSI
Z223.1 (current edition).
A190265
Fig. 35 – Gas Entry
A170125
Fig. 36 – Alternate Gas and Electric Entry
NOTE: Top plate may be field drilled for alternate gas and 115 VAC
electric entry
NOTICE
!
1. Gas supply connections MUST be performed by a licensed plumber
or gas fitter.
2. When flexible connectors are used, the maximum length shall not
exceed 36 in. (915 mm).
3. When lever handle type manual equipment shutoff valves are used,
they shall be T-handle valves.
4. The use of copper tubing for gas piping is NOT approved by the
state of Massachusetts.
WARNING
!
FIRE OR EXPLOSION HAZARD
A failure to follow this warning could result in personal injury, death,
and/or property damage.
If local codes allow the use of a flexible gas appliance connector,
always use a new listed connector. Do not use a connector which has
previously served another gas appliance. Black iron pipe shall be
installed at the furnace gas control valve and extend a minimum of 2-in.
(51 mm) outside the furnace.
CAUTION
!
FURNACE DAMAGE HAZARD
Failure to follow this caution may result in furnace damage.
Connect gas pipe to furnace using a backup wrench to avoid damaging
gas controls and burner misalignment.
NOMINAL
IRON PIPE
SIZE
IN. (MM)
LENGTH OF PIPE - FT (M)
10 (3.0) 20 (6.0)
30 (9.1) 40 (12.1) 50 (15.2)
1/2 (13)
175
120
97
82
73
3/4 (19)
360
250
200
170
151
1 (
25)
680
465
375
320
285
1-1/4 (32)
1400
950
770
660
580
1-1/2 (39)
2100
1460
1180
990
900
LEFT SIDE GAS ENTRY.
GAS PIPE GROMMET
REQUIRED FOR DIRECT
VENT APPLICATONS
GAS PIPE GROMMET REQUIRED
FOR DIRECT VENT APPLICATIONS
1 1/2 inch for Gas
7/8 inch for 115 VAC Electric