Table 4–5 Controller Function Codes
CODE
TITLE
DESCRIPTION
NOTE
Note: If the function is not applicable, the display will read "-----"
Display Only Functions
Cd01
Suction Modulation
Valve Opening (%)
Displays the SMV percent open. The right display reads 100% when the valve
is fully open and 0% when the valve is fully closed. The valve will usually be at
21% on start up of the unit except in very high ambient temperatures.
Cd02 Quench Valve
Displays state of the solenoid quench valve, open or closed.
Cd03 Not Applicable
Not used.
Cd04
Cd05
Cd06
Line Current,
Phase A
Line Current,
Phase B
Line Current,
Phase C
The current sensor measures current on two legs. The third unmeasured leg is
calculated based on a current algorithm. The current measured is used for con-
trol and diagnostic purposes.
For control processing, the highest of the Phase A and B current values is used
for current limiting purposes. For diagnostic processing, the current draws are
used to monitor component energization.
Whenever a heater or a motor is turned ON or OFF, the current draw increase/
reduction for that activity is measured. The current draw is then tested to deter
mine if it falls within the expected range of values for the component.
Failure of this test will result in a pre-trip failure or a control alarm indication.
Cd07 Main Power Voltage
The main supply voltage is displayed.
Cd08 Main Power Frequency
The value of the main power frequency is displayed in Hertz. The frequency dis-
played will be halved if either fuse F1 or F2 is bad (alarm code AL21).
Cd09 Ambient Temperature
The ambient sensor reading is displayed.
Cd10
Compressor Suction
Temperature
Compressor suction temperature sensor reading is displayed.
Cd11
Compressor Discharge
Temperature
Compressor discharge temperature sensor reading is displayed.
Cd12
Compressor Suction
Pressure
Compressor suction pressure transducer reading is displayed.
Cd13 Condenser Pressure
Condenser pressure transducer reading is displayed.
Cd14
Compressor
Discharge Pressure
Compressor discharge pressure transducer reading is displayed.
Cd15
Unloader Valve
(On-Off)
Not used in this application
Cd16
Compressor Motor Hour
Meter / Switch On Time
Records total hours of compressor run time. Total hours are recorded in incre-
ments of 10 hours (i.e., 3000 hours is displayed as 300). Press 'Enter' to display
Start Switch 'ON' time.
Cd17 Relative Humidity (%)
Humidity sensor reading is displayed. This code displays the relative humidity,
as a percent value.
Cd18 Software Revision #
The software revision number is displayed.