T-354
3–8
3.3
ELECTRICAL DATA
Table 3–2 Electrical Data
a. Circuit Breaker
CB-1 Trips at
29 amps
CB-2 (50 amp) Trips at
62.5 amps
CB-2 (70 amp) Trips at
87.5 amps
b. Compressor
Motor
Full Load Amps (FLA)
17.6 amps @ 460 VAC
(with current limiting set at 21 amps)
c. Condenser
Fan Motor
380 VAC, Single Phase,
50 Hz
460 VAC, Single Phase,
60 hz
Full Load Amps
1.3 amps
1.6 amps
Horsepower
0.43 hp
0.75 hp
Rotations Per Minute
1425 rpm
1725 rpm
Voltage and Frequency
360 - 460 VAC +/- 2.5 hz
400 - 500 VAC +/- 2.5 hz
Bearing Lubrication
Factory lubricated, additional grease not required.
Rotation
Counter-clockwise when viewed from shaft end.
d. Evaporator
Coil Heaters
Number of Heaters
6
Rating
750 watts +5/ -10% each @ 230 VAC
Resistance (cold)
66.8 to 77.2 ohms @ 20
C (68
F)
Type
Sheath
e. Evaporator
Fan Motor(s)
380 VAC/50 hz
460 VAC/60 hz
Full Load Amps
High Speed
1.6
2.1
Full Load Amps
Low Speed
0.6
0.6
Nominal Horsepower
High Speed
0.58
1.0
Nominal Horsepower
Low Speed
0.07
0.12
Rotations Per Minute
High Speed
2850 rpm
3450 rpm
Rotations Per Minute
Low Speed
1425 rpm
1750 rpm
Voltage and Frequency
360 - 460 VAC +/-
1.25 hz
400 - 500 VAC +/-
1.5 hz
Voltage & Frequency using
power autotransformer
180 - 230 VAC +/-
1.25 hz
200 - 250 VAC
+/-
1.5 hz
Bearing Lubrication
Factory lubricated, additional grease not required
Rotation EF#1
CW when viewed from shaft end
Rotation EF#2
CCW when viewed from shaft end
f. Fuses
Control Circuit
7.5 amps (F3A, F3B)
Controller/DataCORDER
5 amps (F1 & F2)
Emergency Defrost
5 amps (FED)
Drain Line Heater
5 amps (FDH)
Humidity Power
Transformer
5 amps (FH)
g. Compressor Crankcase Heater
180 watts @ 460 VAC