6.23.3 Adjusting the Recorder Stylus
Proper stylus force upon the chart paper is important.
Factory adjustment is 113 to 127 grams (4 to 4.5 oz). To
measure the force, use a spring type gage, and attach it
under the stylus as close as possible to the pen tip (item
4). Exert pull on the gage perpendicular to the chart
surface. The measured force should be noted just as the
pen tip leaves the surface.
NOTE
The two coil springs near the base of the stylus
are NOT involved in establishing chart contact
force. They serve only to hold the stylus in its
retracted position.
Correct adjustment is made by carefully bending the
portion of the stylus arm between the bend near the pen
tip, and the first bend towards the stylus arm base. If the
force is too low, the stylus trace will be light and difficult
to read. If the force is too great, wrinkling, or tearing of
the paper chart may occur.
6.23.4 Rezeroing the Recording Thermometer
For Electronic Partlow Recorder CTD part number
12-00464-xx
Where xx= an odd number (example: 12-00464-03 )
NOTE
Use chart CTD part number 09-00128-00 (F)
part number 09-00128-01 (C).
a. Press the “Calibration” button (item 7, Figure 6--24)
on the bottom of the recorder. The pen tip will drive
fully down scale, then move upscale to the chart ring
at -29C (-20F), and stop.
b. If the tip of the pen (item 4) is on the -29C (-20F) chart
ring the recorder is in calibration, proceed to step c. If
the tip of the pen is NOT on the -29C (-20F) chart ring,
the operator must loosen the two screws on the
bottom of the stylus arm to adjust the pen tip manually
to the -29C (-20F) chart ring. Tighten the screws
when adjustment is complete.
c. Press the calibration button and the pen will position
itself to the correct temperature reading.
For Electronic Partlow Recorder CTD part number
12-00464-xx
Where xx= an even number (example: 12-00464-08)
NOTE
Use chart CTD part number 09-00128-00 (F)
part number 09-00128-01 (C).
a. Press the “Calibration” button (item 7, Figure 6--24)
on the bottom of the recorder. The pen tip will drive
fully down scale, then move upscale to the chart ring
at 0C (32F), and stop.