36
Step 5 — Install Machine Supports
INSTALL STANDARD ISOLATION
Figures 40-43 show the position of support plates and shear flex
pads, which together form the standard machine support system.
Service clearance under the chiller can be enhanced if the grout is
not extended along the entire length of the heat exchangers.
Fig. 40 — 23XRV30-57 Machine Footprint
Fig. 41 — 23XRV Frame Size A Machine Footprint
IMPORTANT: Chiller housekeeping pad, anchor bolts and
attachment points to be designed by others in accordance
with all applicable national and local codes.
*
*
23XRV
HEAT EXCHANGER SIZE
DIMENSIONS (ft-in.)
A
B
C
D
E
F
G
30-32
12-10-3/4
5-5-1/4
0
0-3-5/8
1-3-1/4
0-9
0-1/2
35-37
14- 7-1/4
5-5-1/4
0
0-3-5/8
1-3-1/4
0-9
0-1/2
40-42, 4D
12-10-3/4
6-0
0-1-1/2
0-3-5/8
1-3-1/4
0-9
0-1/2
45-47, 4E
14- 7-1/4
6-0
0-1-1/2
0-3-5/8
1-3-1/4
0-9
0-1/2
50-52
12-10-3/4
6-5-1/2
0-1/2
0-3-5/8
1-3-1/4
0-9
0-1/2
55-57
14- 7-1/4
6-5-1/2
0-1/2
0-3-5/8
1-3-1/4
0-9
0-1/2
a23-1534
*See Fig. 43 or 44.
OUTSIDE EDGE OF
1'-3 7/8"
[403mm]
CONDENSER TUBESHEET.
OUTSIDE EDGE OF
(TYPICAL BOTH ENDS)
EVAPORATOR TUBESHEET.
(TYPICAL BOTH ENDS)
[997mm]
3'-3 1/4"
Y*
[387mm]
TYPICAL
1'-3 1/4"
13'-0 1/2"
[3975mm]
SUPPORT PLATE
X*
[3766mm]
12'-4 1/4"
[105mm]
X
TYPICAL
[13mm]
0'-0 1/2"
[213mm]
0'-8 3/8"
0'-4 1/8"
0'-9"
Y
TYPICAL
[229mm]
0'-3"
[76mm]
ACCESSORY SOLEPLATE
TYPICAL
0'-3 1/2"
[89mm]
[610mm]
2'-0"
[38mm]
0'-1 1/2"
TYPICAL
CL
EVAPORATOR & COMPRESSOR
REAR
FRONT
SUCTION END
DISCHARGE END
CL
CONDENSER
a23-1685
*See Fig. 43 or 44.
Summary of Contents for AquaEdge 23XRV
Page 53: ...53 Fig 58 23XRV Controls Schematic ...
Page 54: ...54 Fig 58 23XRV Controls Schematic cont FROM 2000767952 SHEET 3 ...
Page 55: ...55 Fig 58 23XRV Controls Schematic cont ...
Page 56: ...56 Fig 59 23XRV Controls Schematic Rockwell Standard Tier VFD Shown ...
Page 57: ...57 Fig 60 23XRV LF2 VFD Wiring Diagram ...
Page 65: ...65 Fig 70 23XRV Insulation Area Units with P Compressor ...