22
Pump Configuration Menu – PUMPCONF (continued)
No. Point name
Status
Default
Unit
Displayed text*
Description
5
2 = Two Pumps Auto
2 = Two Pumps Auto (units with two pumps)
6
3 = Pump#1 Manual
3 = Pump#1 Manual
7
4 = Pump#2 Manual
4 = Pump#2 Manual
8
clpmpdel
24 to 3000
48
hour
Pump Auto Rotation Delay
Pump auto rotation delay (units with two
pumps = auto control)
9
clpmpper
no / yes
no
-
Cool Pump Anti-Sticking
Evaporator pump anti-sticking protection
10
clpmpsby
no / yes
no
-
Cool Pump Stopped in Sby
Not applicable (please ignore this parameter)
11
clpmploc
no / yes
no
-
Flow Checked if Pump Off
Water flow is checked when the pump is off
12
CONDENSER PUMP
CONDENSER PUMP
13
cdpmpseq
0 to 4
0
-
Condenser Pumps Sequence
Condenser pump sequence
14
0 = No Pump
0 = No Pump
15
1 = One Pump Only
1 = One Pump Only
16
2 = Two Pumps Auto
2 = Two Pumps Auto (units with two pumps)
17
3 = Pump#1 Manual
3 = Pump#1 Manual
18
4 = Pump#2 Manual
4 = Pump#2 Manual
19
cdpmpdel
24 to 3000
48
hour
Pump Auto Rotation Delay
Pump Auto Rotation Delay (units with two
pumps = auto control)
20
cdpmpper
no / yes
no
-
Cond Pump Anti-Sticking
Condenser pump anti-sticking protection
21
cdpmpsby
no / yes
no
-
Cond Pump Stopped in Sby
Not applicable (please ignore this parameter)
22
cdpmploc
no / yes
no
-
Flow Checked if Pump Off
Water flow is checked when the pump is off
23
ol_pump
no / yes
no
-
Open loop pump Control
Open loop pump control
*Depends on the selected language (English by default).
Heat/Cool Config Menu – HCCONFIG
No. Point name
Status
Default
Unit
Displayed text*
Description
1
cr_sel
0 to 3
0
-
Cooling Reset Select
Cooling reset selection
2
hr_sel
0 to 3
0
-
Heating Reset Select
Heating reset selection
3
0=none, 1=OAT,
0 = None, 1 = OAT,
4
2=delta T, 3=4-20mA
2 = Delta T, 3 = 4-20 mA control
5
boil_on
no / yes
no
Boiler Manual Command
Boiler manual command:
No = boiler control based on OAT control logic
(see boil_th below)
Yes = boiler control enabled if OAT sensor is
NOT present or the sensor fails
6
boil_th
-15 to 15
-10
°C
Boiler OAT Threshold
Boiler OAT threshold
7
ehs_th
-4.90 to 21.42
5.2
°C
Elec Stage OAT Threshold
Electric heating stage, OAT threshold
8
both_sel
no / yes
no
-
HSM Both Command Select
HSM both command selection
9
ehs_back
no / yes
no
-
1 Elec Stage for Backup
One electric heating stage used for back-up
10
ehs_pull
0 to 60
0
min
Electrical pulldown time
Electrical pull-down time
*Depends on the selected language (English by default).
HDC Configuration Menu – HDC_CONF
No. Point name
Status
Default
Unit
Displayed text*
Description
1
adpmpper
no / yes
no
-
Add. Pump Anti-Sticking
Additional pump anti-sticking protection
2
summ_oat
15.0 to 30.0
20.0
°C
Summer OAT threshold
This threshold defines when Summer mode
can be started
3
summ_on
0 to 12
5
hour
Summer OAT start delay
Summer mode is activated if OAT is above
OAT Threshold [sum_oat] for at least the
sum_on delay
4
summ_off
0 to 12
5
hour
Summer OAT stop delay
Summer mode is reset when OAT goes below
OAT Threshold [sum_oat] minus 2K for at least
the sum_off delay