31
9 -
DIAGNOSTICS
Touch Pilot Junior control system has many fault tracing aid
functions, protecting the unit against risks that could result
in the failure of the unit.
9.1 - Control diagnostics
The user interface enables the quick display of the unit status:
The
blinking bell
icon indicates that there is an alarm,
but the
unit is still running
.
The
highlighted bell
icon indicates that the
unit is
shut down
due to a detected fault.
The local interface – TOUCH PILOT JUNIOR – gives the
user quick access to monitor all unit operating conditions.
If an operating fault is detected, the alarm is triggered.
All information regarding the existing alarms (current and
past alarms) can be found in the Alarm menu.
Viewing alarm information
Alarm menu
Date
Hour
Code
Description
Current Alarms
(basic access)
•
•
•
Alarm History
(basic access)
•
•
•
Reset Alarms
(user access)
•
9.2 - Displaying current alarms
The Current alarms menu may display up to 10 current alarms.
To access the list of currently active alarms
1. Press the
Alarm
button in the upper-right part of the screen.
2. Select
Current Alarms
.
3. The list of active alarms will be displayed.
9.3 - Resetting alarms
The alarm can be reset either automatically by the control
or manually through the touch panel display or the web
interface (in the Reset Alarms menu). See also section 9.5.
• The Reset alarms menu displays up to 5 alarm codes
which are currently active on the unit.
• Alarms can be reset without stopping the machine.
• Only logged-in users can reset the alarms on the unit.
To reset the alarm manually
1. Press the
Alarm
button in the upper-right part of the screen.
2. Select
Reset Alarms
.
3. Set “Alarm Reset” to Yes.
IMPORTANT:
Not all alarms can be reset by the user. Some
alarms are reset automatically when operating conditions
return to normal.
CAUTION:
In the event of a power supply interrupt, the
unit restarts automatically without the need for an external
command. However, any faults active when the supply is
interrupted are saved and may in certain cases prevent a
circuit or a unit from restarting.
9.4 -
E-mail notifications
The.control.provides.the.option.to.define.one.or.two.recipients.
who.receive.e-mail.notifications.each.time.the.new.alarm.occurs.
or all existing alarms have been reset.
IMPORTANT:
E-mail notifications can be configured only
by Carrier service.