Alarm codes (cont.)
Code Description

Possible cause

Action taken

Reset type

10008 Circuit A High Suction Superheat                                 Pressure transducer 

defective, temp. sensor 

defective,  EXV blocked 

or lack of refrigerant

Circuit A shuts down

Manual

10009 Circuit B High Suction Superheat                                 As above

Circuit B shuts down

Manual

10011 Circuit A Low Suction Superheat                                  As above

Circuit A shuts down

Manual

10012 Circuit B Low Suction Superheat                                  As above

Circuit B shuts down

Manual

10015 Condenser Flow Switch Failure                                   

Abnormal conditions 

on condenser side

Unit shuts down

Automatic (7 alarms within 24 

hours); otherwise, Manual

10016 Compressor A1 Not Started or Pressure Increase 

not Established  

Compressor breaker or 

fuse fault, compressor 

switch open

Compressor A1 shuts down Manual

10017 Compressor A2 Not Started or Pressure Increase 

not Established  

As above

Compressor A2 shuts down Manual

10018 Compressor A3 Not Started or Pressure Increase 

not Established  

As above

Compressor A3 shuts down Manual

10020 Compressor B1 Not Started or Pressure Increase 

not Established  

As above

Compressor B1 shuts down Manual

10021 Compressor B2 Not Started or Pressure Increase 

not Established  

As above

Compressor B2 shuts down Manual

10028 Customer Interlock Failure                                      

Customer interlock 

input set on

Unit shuts down

Automatic (if the unit was 

stopped); otherwise, Manual

10029 Loss of communication with System Manager                        Communication error

Unit returns to the 

standalone mode

Automatic, if communication 

with System Manager is 

restored

10030 Master/Slave communication Failure                               Bus installation fault

Master/Slave control is 

stopped / Unit returns to 

the stand-alone mode

Automatic, if communication is 

restored

10031 Unit is in CCN emergency stop                                   

Network emergency 

stop command

Unit shuts down

Automatic, if emergency stop 

is deactivated

10032 Cooler pump 1 default                                           

Flow switch or water 

pump fault

Unit is restarted with 

another pump running; If 

no pump is available, the 

unit shuts down

Manual

10033 Cooler pump 2 default                                           

Flow switch or water 

pump fault

As above

Manual

10037 Circuit  A  Repeated  High  Discharge  Gas  Overrides                  Repetitive capacity 

decreases

None OR circuit A shuts 

down

Automatic (no discharge gas 

overrides within 30 min) or 

Manual

10038 Circuit  B  Repeated  High  Discharge  Gas  Overrides                  As above

None OR circuit B shuts 

down

As above

10040 Circuit A Repeated low suction temperature 

overrides            

As above

Circuit A shuts down

Manual

10041 Circuit B Repeated low suction temperature 

overrides            

As above

Circuit B shuts down

Manual

10043 Low entering water temperature in heating                       

Low entering fluid temp. 

in Heating mode

None

Automatic, if water temperature 

returns to normal or heating 

mode is stopped

10051

Cooler flow switch failure                                      

Flow switch fault

Unit shuts down

Manual

10063 Circuit A High pressure switch Failure                           High pressure switch is 

open, compressor fault

Circuit A shuts down

Manual

10064 Circuit B High pressure switch Failure                           As above

Circuit B shuts down

Manual

10073 Condenser pump 1 default                                        

Water pump fault

Unit is restarted with 

another pump running; If 

no pump is available, the 

unit shuts down

Manual

10074 Condenser pump 2 default                                        

As above

Unit is restarted with 

another pump running; If 

no pump is available, the 

unit shuts down

Manual

10097 Cooler Water Exchanger Temperature Sensors 

Swapped              

Inlet and outlet temp. 

reversed

Unit shuts down

Manual

10098 Condenser Water Exchanger Temperature Sensors 

Swapped           

As above

Unit shuts down

Manual

Summary of Contents for AquaSnap 30WG Series

Page 1: ...CONTROLS MANUAL Operation instructions Original document Touch Pilot Junior Control 30WG 30WGA 61WG...

Page 2: ...ns 10 5 SETTING UP TOUCH PILOT JUNIOR CONTROL 11 5 1 Reading the Welcome screen 11 5 2 Exploring the Synoptic screen 11 5 3 Starting Stopping the unit 11 5 4 Setting the schedule 12 5 5 Display settin...

Page 3: ...t any time without notice 8 10 Additional space heating control 28 8 11 Built in DHW and space heating control HDC 29 8 12 Condensing pressure control optional 30 8 13 Master Slave control 30 9 DIAGNO...

Page 4: ...instructions prior to proceeding with any work Pay attention to all safety warnings The information provided herein is solely for the purpose of allowing customers to operate and service the equipment...

Page 5: ...trical cables and conduits terminal box covers and motor frames with great care 2 CONTROLLER OVERVIEW 2 1 Control system 30WG 30WGA 61WGunitscomewiththeTouchPilotJunior control that serves as a user i...

Page 6: ...f the green LED is not flashing this indicates a LEN bus wiring problem 3 4 Pressure transducers The control implements three types of pressure transducers where two pressure transducers high pressure...

Page 7: ...ustomer safety loops Condenser 3 way valve SIOB cir A 80 80 Used to control the water flow on the condenser side Boiler SIOB cir A 69 70 Used to command a boiler Running SIOB cir A 37 38 Used to signa...

Page 8: ...me screen will be displayed 4 2 Connections Connections are located on the bottom side of the controller The controller comes with two RS485 ports where the first port is used to connect to CCN Carrie...

Page 9: ...er password User password required Legend Genunit Config Schedule HDC Configuration Date Time Pump Configuration Holiday Reset Config Control Identification Heat Cool Config Broadcast User Configurati...

Page 10: ...rt no action taken on the unit Steady icon Alarm s active on the unit see section 9 5 OTHER SCREENS Login screen Parameters screen s Login Confirm advanced access login Save changes Logout Reset the u...

Page 11: ...d 5 SETTING UP TOUCH PILOT JUNIOR CONTROL 5 1 Reading the Welcome screen The Welcome screen is the first screen shown after starting the user interface It displays the application name as well as the...

Page 12: ...is set the selected period will be presented in the form of the green band on the timeline 7 Press the Save button to save your changes or the Cancel button to exit the screen without making modificat...

Page 13: ...r level security ensures that only authorised users are allowed to modify critical unit parameters Only logged in users are allowed to access the Configuration menu It is strongly recommended to chang...

Page 14: ...ion is from a PC using a web browser with Java IMPORTANT UsefirewallsandVPNforsecureconnection 6 2 Opening the web interface To access theTouch Pilot Junior control enter the IP address of the unit in...

Page 15: ...ditional features some tables may contain parameters that cannot be configured for a given unit General Parameters Menu GENUNIT No Point name Status Unit Displayed text Description 1 CTRL_TYP 0 to 2 L...

Page 16: ...emperature circuit A 4 SST_B C Saturated Suction Tp B Saturated suction temperature circuit B 5 SUCT_A C Gas Suction Temp A Compressor suction temperature circuit A 6 SUCT_B C Gas Suction Temp B Compr...

Page 17: ...pen close Remote Setpoint Switch2 Remote Setpoint Switch 2 6 LIM_SW1 open close Limit Switch 1 Status Demand limit switch 1 7 LIM_SW2 open close Limit Switch 2 Status Not applicable please ignore this...

Page 18: ...oint Evaporator water delta temp setpoint 12 CL_WdpSp kPa Cool Water DP Setpoint Evaporator water delta pressure setpoint 13 CL_DvPos 0 to 100 Cool Pump drive position Evaporator pump drive position 1...

Page 19: ...ber of starts compressor A1 7 hr_cp_a2 hour Compressor A2 Hours Operating hours compressor A2 8 st_cp_a2 Compressor A2 Starts Number of starts compressor A2 9 hr_cp_a3 hour Compressor A3 Hours Operati...

Page 20: ...Displayed text Description 1 m_delay no yes Delay Active Start up delay in effect 2 m_2ndspt no yes Second Setpoint Active Second setpoint in use The setpoint used during unoccupied periods 3 m_reset...

Page 21: ...a given unit Genunit Config Menu GENCONF No Point name Status Default Unit Displayed text Description 1 lead_cir 0 to 2 0 Cir Priority Sequence Circuit priority 2 0 Auto 1 A Lead 2 B Lead 0 Automatic...

Page 22: ...the selected language English by default Heat Cool Config Menu HCCONFIG No Point name Status Default Unit Displayed text Description 1 cr_sel 0 to 3 0 Cooling Reset Select Cooling reset selection 2 hr...

Page 23: ...fu 30 1 to 52 2 40 5 C OAT Full Reset Value OAT max reset value 12 dt_hr_no 0 to 14 1 0 C Delta T No Reset Value Delta T no reset value 13 dt_hr_fu 0 to 14 1 0 C Delta T Full Reset Value Delta T max r...

Page 24: ...onth Day of the month 2 month 1 to 12 Month of year Month 3 year 20nn Year Year 4 dow Monday Sunday Day of Week Day of the week Time HH MM 5 hour 0 to 24 hour Hour Hour 6 minute 0 to 59 min Minute Min...

Page 25: ...operate in Cooling mode only The unit operation is based on the following parameters Unit On Off status This parameter indicates whether the unit is shut down not authorised to start or in operation...

Page 26: ...mpdel for cooler OR 4 Set PumpAuto Rotation Delay cdpmpdel for condenser Pump Auto Rotation Delay clpmpdel cdpmpdel 24 to 3000 h 48 h 8 4 3 Pump speed control If the pump with variable flow option has...

Page 27: ...g setpoint reset which can be applied if the condensing setpoint control depends on outdoor air temperature reading reset source OAT Cooling mode 30WG 30WGA 61WG Cooling control point reset is used to...

Page 28: ...et boiler manual command 1 Navigate to the Configuration menu 2 Select Heat Cool Config HCCONFIG 3 Set Boiler Manual Command boil_on Boiler Manual Command boil_on No OAT sensor logic is applied Yes Bo...

Page 29: ...ntinue to operate as described earlier The electric heater stages operate only in the heating mode but not during domestic hot water production 8 11 4 Heating or domestic hot water mode A three way va...

Page 30: ...ch Pilot Junior continuously optimises system operation to obtain the best system efficiency by controlling the number of fans required for any thermal load and outside temperature conditions 8 12 3 C...

Page 31: ...2 Select Current Alarms 3 The list of active alarms will be displayed 9 3 Resetting alarms The alarm can be reset either automatically by the control or manually through the touch panel display or th...

Page 32: ...12002 Circuit B Discharge Pressure Transducer Failure As above Circuit B shuts down As above 12004 Circuit A Suction Pressure Transducer Failure As above Circuit A shuts down Automatic up to 3 alarms...

Page 33: ...stand alone mode Automatic if communication is restored 10031 Unit is in CCN emergency stop Network emergency stop command Unit shuts down Automatic if emergency stop is deactivated 10032 Cooler pump...