Check Thermostat Operation — 

To check thermo-

stat operation, perform the following procedure:

1. Press the Mode button repeatedly until the Heat icon

appears on the display. The thermostat is now in Heating

mode.

2. Press the Fan button. The Fan Auto icon will appear on

the display screen. Press the UP ARROW button until the

heating set point is 10 F (6 C) higher than the current

room temperature. Heating and fan should be energized.

3. Press the Mode button repeatedly until the Cool icon

appears on the display. The thermostat is now in Cooling

mode.

4. Press the DOWN ARROW button until the cooling set

point is 10 F lower than the current room temperature.

Cooling and fan should be energized.

5. Press the Mode button repeatedly until the Off icon

appears. Press the Fan button until the display reads Fan

On. The fan should energize.

6. If heating, cooling, or fan operation do not work, check

wiring and consult Table 4.

Final Checklist

1. Put away tools and instruments. Clean up debris and

packaging.

2. Review Owner’s Guide with occupant or owner.
3. Leave the manuals with owner.

OPERATION

The Mode button selects the operating mode of the thermo-

stat. If OFF is selected, the thermostat will not enter Heating or

Cooling mode. If HEAT is selected, the thermostat will only

enter Heating mode (if the room temperature is below the heat-

ing set point). If COOL is selected, the thermostat will only

enter Cooling mode (if the room temperature is above the cool-

ing set point). If AUTO is selected, the thermostat will enter

Heating or Cooling mode based on the room temperature and

the heating and cooling set points. If PROGRAM ON is select-

ed, the stored schedule is enabled and the thermostat will

follow the Occupied and Unoccupied schedules stored in its

memory.

Auto-Changeover — 

When the thermostat mode is set

to AUTO, the thermostat will provide automatic changeover

from Heating to Cooling mode and Cooling to Heating mode

when required. The thermostat will automatically switch to

maintain the desired temperature setting. The thermostat does

not need to be manually changed from heating to cooling or

cooling to heating operation.

Two-Stage Operation — 

The second stage of heat or

cool is turned on when the first stage has been on for a mini-

mum of 2 minutes and the temperature differential from the set

point is equal to or greater than the set point plus the deadband

plus 2 degrees.

Clock Backup — 

In the event of a power loss, the ther-

mostat will keep time for a minimum of 48 hours without

external power or batteries.

Fan Operation — 

If Fan On is selected, the fan will run

continuously during occupied schedule (except when Mode is

switched to OFF). The fan will be off during unoccupied

schedule except during heating or cooling operation.

If Fan On is not selected, the fan will only operate during

heating or cooling operation.

Emergency Heat — 

Emergency heat is available for

heat pump applications. To turn on emergency heat, press and

hold the Fan button. While holding the Fan button, press the

UP button for 2 seconds. An ‘‘EH’’ will be displayed. During

emergency heat, the fan will operate and the second stage of

heat will be energized (locking out the first stage compressor).

To exit emergency heat, press and hold the Fan button. While

holding the Fan button, press the UP button for 2 seconds. Dur-

ing emergency heat, only OFF and HEAT modes are available.

Holiday Mode — 

When the thermostat is in Holiday

mode, the thermostat will operate under Unoccupied set points.

To configure and activate the Holiday mode, press the Holiday

button. The ‘‘HOL’’ icon will be displayed along with the re-

maining days of Holiday mode operation. Press the UP or

DOWN ARROWS to select the number of days that the holi-

day schedule will be in effect. A value of 0 disables Holiday

mode. The duration can be set from 1 to 99 days. The thermo-

stat will enter Holiday mode on midnight of the next day after

the mode has been activated. Holiday mode will remain in ef-

fect until midnight of the last configured day.

If the Holiday mode is in effect, the number of days remain-

ing will blink on and off and the ‘‘Unoccupied’’ icon will be

displayed. The Override button will be active during Holiday

mode.

To turn off the Holiday mode before the remaining config-

ured days have passed, press the Holiday button to enter the

Configuration mode. Press the DOWN ARROW to set the

number of days to zero. Holiday mode will be disabled.

Keypad Lock — 

To prevent unauthorized use of the ther-

mostat, the front panel buttons can be disabled. To disable or

lock the keypad, press and hold the Mode button. While hold-

ing down the Mode button, press the UP and DOWN ARROW

buttons simultaneously. The ‘‘Locked’’ icon will appear on the

display.

The thermostat is unlocked by performing the same proce-

dure. Press and hold the Mode button. While holding down the

Mode button, press the UP and DOWN ARROW buttons si-

multaneously. The ‘‘Locked’’ icon will be removed from the

display.

Summary of Contents for AQUAZONE 50QE900

Page 1: ...r property damage GENERAL The 7 day commercial programmable thermostats is a wall mounted low voltage thermostat which maintains room temperature by controlling the operation of an HVAC heating cooling and ventilation system Separate heating and cooling set points and auto changeover capability allow occupied and unoccupied programming for energy savings This thermostat allows up to 4 time tempera...

Page 2: ...re length and routing to allow proper closure of the thermostat Strip each wire at the end no more than 1 4 in to prevent adjacent wires from shorting together Match and connect wires to terminals on the thermostat See Fig 2 5 and Table 1 9 Push excess wiring into wall Seal hole in wall to prevent drafts 10 Re attach thermostat cover to back plate by aligning the top two prongs of the back plate i...

Page 3: ...ser to reset the Service Filter counter to zero and remove the SERVICE FILTER icon if displayed on the thermostat screen Press the OVERRIDE button while in Setup Step 3 and the counter is reset to zero Press the arrow buttons to ad just the number of hours the blower will run before the SER VICE FILTER icon is displayed The range is 0 to 1950 hours Set the variable to 0 to disable this function Th...

Page 4: ...arity for the heat pump The vari able can be set to either B or O Set the reversing valve polarity to the correct value depending on the application The default is O Program Thermostat Schedules Before pro gramming the thermostat plan the thermostat daily schedule The schedule is divided into 7 days Monday through Sunday Each day has from 2 to 4 time periods Occupied 1 Occupied 2 Occupied 3 Unoccu...

Page 5: ... been entered press the Program button to exit Programming mode NOTE The thermostat will continue to follow the schedule until a new one is entered If only one occupied schedule is selected the Occupied 2 and 3 schedules are skipped If the start time is set later in the day than the stop time the program will run from midnight of that day to the stop time and then from the start time to mid night ...

Page 6: ...the deadband plus 2 degrees Clock Backup In the event of a power loss the ther mostat will keep time for a minimum of 48 hours without external power or batteries Fan Operation If Fan On is selected the fan will run continuously during occupied schedule except when Mode is switched to OFF The fan will be off during unoccupied schedule except during heating or cooling operation If Fan On is not sel...

Page 7: ...ower operation timer to 0 hours Cooling Will Not Energize Select COOL mode Decrease cooling set point to 10 degrees below room temperature Check for 24 vac at Y1 terminal If present ther mostat is operating correctly and problem is with wiring or equipment If 24 vac is not present replace the thermostat Check for Compres sor Cycle per Hour Limit Cooling may be locked out Heating Will Not Energize ...

Page 8: ...ntinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53500037 01 Printed in U S A Form 50QE 7SI Pg 8 7 07 Replaces 50QE 2SI Book 1 4 Tab 5a 5a Copyright 2007 Carrier Corporation ...

Reviews: