39
13 - TROUBLE SHOOTING
Check
for
120
V
ac
Inside
High
Voltage
T
erminal
B
ox.
Is
120
V
ac
available?
External
Power
S
witch
O
N?
YES
NO
Turn
ON
power
to
B
oiler.
Is
Power
L
ight
Lit?
YES
YES
NO
NO
Does
User
Interface
Display
work?
Check
Circuit
Breaker
or
Emergency
Disconnect
Switch
and
120
Vac
W
iring
to
Boiler.
Fix
or
Repair
External
W
iring.
Check
1
20
Vac
o
n
M
olex
Connector
o
n
top
of
Lower
J
acket
is
120
V
ac
available?
Replace
W
ire
Harness.
NO
YES
Replace
Power
Light
YES
NO
Remove
User
Interface
from
base.
Using
Digital
V
oltmeter
check
for
25
to
30
Vdc.
Is
voltage
present?
Locate
fuse
holder
o
n
front
of
control
a
nd
pull
to
c
heck
fuse.
Spare
fuse
located
on
controller.
Make
sure
all
wire
harness
p
lugs
are
p
roperly
pushed
in.
R
elease
plug
lock
with
finger,
remove
a
nd
reconnect
a
ll
7
p
lugs
.
C
heck
wiring
from
User
Interface
to
Low
Voltage
Terminal
Strip
including
checking
continuity
of
the
wires.
Does
User
Interface
Display
w
ork?
NO
YES
YES
NO
Replace
Control
Module
Replace
User
Interface
GO TO NEXT PAGE
Remove
Top
J
acket.
Is
User
Interface
Lit?
NO
YES
Summary of Contents for BWMAAN000050
Page 46: ...46 13 TROUBLE SHOOTING ...
Page 48: ...48 13 TROUBLE SHOOTING ...
Page 53: ...53 14 WIRING DIAGRAM 14 1 Connection Diagram ...
Page 54: ...54 14 WIRING DIAGRAM 14 2 Schematic Diagram of Ladder Form ...
Page 60: ...60 APPENDIX A CONTROL MODULE ...
Page 61: ...61 APPENDIX A CONTROL MODULE ...
Page 64: ...64 APPENDIX A CONTROL MODULE ...
Page 70: ...70 NOTES ...
Page 71: ...71 Date Service Performed Company Name Tech Initials Company Address Phone ...
Page 72: ...CAC BDP 7310 West Morris St Indianapolis IN 48231 ...