69
User Interface Display
Explanation
DHW Settings
D H W
S E T T I N G S
▲
D H W
m a x .
p r i o r i t y
t i m e
3 0 m i n
Allowed Range: 1 to 60 Minutes
Default Setting: 30 Minutes
Maximum time boiler operates in DHW mode limited by DHW
Maximum Priority Time Setting.
Priority timer starts when both CH and DHW demand is
present. Boiler will switch from DHW back to CH operation after
Maximum Priority Time has elapsed.
CH demand then has priority until Maximum Priority Time has
elapsed.
Process repeats until either CH or DHW demand satisfi ed.
System Test
S Y S T E M T E S T
S e t
t e s t
p o w e r
O f f
System test can be activated via installer menu for testing
system at fi xed power rates.
Boiler can be started without CH or DHW demand being
present. System Test has priority over any system demand
while test mode activated.
System test mode automatically ends after 30 minutes boiler
resumes normal operation.
The following modes are available:
• Disabled
• Low power - Burner starts. After ignition period has
fi nished the burner stays at low power
• Ignition power - Burner starts. Stays at ignition power
• High power - Burner starts. After ignition period has
fi nished burner stays at high power.
Note:
• Before running system test modes, check if hydronic
system capable of dissipating heat.
• Both heat exchanger and CH pumps are activated during
system test only.
• During System Test Mode, boiler will run at fi xed power
rates until supply water temperature is 93°C/195°F
• All other safety functions remain active while in System
Test Mode.
S Y S T E M T E S T
B o i l e r
P u m p
O f f
C H \ S y s t e m
P u m p
O f f
D H W
P u m p
O f f
APPENDIX A - CONTROL MODULE
Summary of Contents for BWMAAN000050
Page 46: ...46 13 TROUBLE SHOOTING ...
Page 48: ...48 13 TROUBLE SHOOTING ...
Page 53: ...53 14 WIRING DIAGRAM 14 1 Connection Diagram ...
Page 54: ...54 14 WIRING DIAGRAM 14 2 Schematic Diagram of Ladder Form ...
Page 60: ...60 APPENDIX A CONTROL MODULE ...
Page 61: ...61 APPENDIX A CONTROL MODULE ...
Page 64: ...64 APPENDIX A CONTROL MODULE ...
Page 70: ...70 NOTES ...
Page 71: ...71 Date Service Performed Company Name Tech Initials Company Address Phone ...
Page 72: ...CAC BDP 7310 West Morris St Indianapolis IN 48231 ...