Table 1 – CAPVP Cased Coil Information
MODEL
SIZE (TON)
FLUSH FIT TO
FURNACE WIDTH
COIL CONNECTION TUBE SIZE (IN.)
Liquid
Suction
CAPVP1917ALA
1.5
17-1/2" / 445 mm
3/8
3/4
CAPVP2517ALA
2.0
17-1/2" / 445 mm
3/8
3/4
CAPVP3717ALA
3.0
17-1/2" / 445 mm
3/8
3/4
CAPVP3721ALA
3.0
21" / 533 mm
3/8
7/8
CAPVP4321ALA
3.5
21" / 533 mm
3/8
7/8
CAPVP6124ALA
5.0
24-1/2" / 622 mm
3/8
7/8
INTRODUCTION
Use this instruction manual to install CAPVP indoor coil on
multipoise furnaces. (See Fig. 1.) The CAPVP coil is enclosed in a
casing.
Do n lo
rnace
Installation
plo
rnace
Installation
Retrn
S pply
Ret rn
S pply
Eapo rator
Coil
A13060
Fig. 1
−
Typical Installation Upflow/Downflow Cased Coils
* CAUTION: DO NOT MOUNT COIL LOWER THAN
3˝ (76mm) MINIMUM OR FURN
ACE FAILURE MAY RESULT
Wide Coil
Narrow Coil
Narrow Furnace
Wide Furnace
Field Fabricated
Adapter(s)
3˝ (76mm)
A13061
Fig. 2
−
Adapter(s) Installation When Coil Overhangs or Un-
derhangs Furnace
INSTALLATION
Inspect Equipment
File claim with shipper if equipment is damaged or incomplete.
Select Installation
NOTE
: Consult the furnace installation instructions for any
special requirements when installing the coil to the furnace.
Upflow CAPVP Coil Installation.
The cased coil is designed to fit furnaces of the same width.
1. Set coil in place on upflow furnace discharge air opening.
2. Ensure coil is level for proper condensate drainage. Do not
tip coil toward condensate drain. Coil casing need not be
fastened or screwed to furnace.
3. When installing wider coil on narrow furnace, create field
fabricated adapter. (See Fig. 2.)
4. When installing narrow coil on wide furnace, create field
fabricated adapter. (See Fig. 2.)
NOTE
: On upflow installations where the indoor coil is placed in
an unconditioned space, a 6” (152 mm) wide piece of insulation
should be applied and wrapped around the outside of coil casing
and supply duct contact point.
See Table 1 for dimensions. Note instructions for placement of coil
casing on furnace.
Downflow CAPVP Coil Installation.
IMPORTANT
: Installing “A” coils rotated 90
_
from the front of
the furnace in downflow applications can cause water blow off or
coil freeze up. This is due to the concentration of air on one coil
slab or lack of air on the opposite coil slab. If the airflow is high
due to ductwork or other causes, and there is a chance for water
blow off, it is recommended that a 3” (76 mm) field
−
supplied
adapter be placed between the coil and the furnace to allow the air
to distribute evenly to both coil slabs. (See Fig. 3.)
3” (76mm)
A13062
Fig. 3
−
Downflow Installation With Coil Rotated 90
_
1. Set cased coil on supply duct opening.
2. Place field fabricated 3” (76 mm) adapter on coil casing.
Adapter should be tapered to fit coil/furnace combination
when one of them is larger than the other.
3. Set furnace on adapter.
NOTE
: In downflow installation with a 4
−
way multipoise
furnace, break off perforated duct flanges on furnace. See furnace
installation instructions.
CONNECT REFRIGERANT PIPING
Use accessory tubing package or field
−
supplied tubing of
refrigerant grade, see Product Data information for ordering.
CAPVP