Table 1 – CAPVP Cased Coil Information

MODEL

SIZE (TON)

FLUSH FIT TO

FURNACE WIDTH

COIL CONNECTION TUBE SIZE (IN.)

Liquid

Suction

CAPVP1917ALA

1.5

17-1/2" / 445 mm

3/8

3/4

CAPVP2517ALA

2.0

17-1/2" / 445 mm

3/8

3/4

CAPVP3717ALA

3.0

17-1/2" / 445 mm

3/8

3/4

CAPVP3721ALA

3.0

21" / 533 mm

3/8

7/8

CAPVP4321ALA

3.5

21" / 533 mm

3/8

7/8

CAPVP6124ALA

5.0

24-1/2" / 622 mm

3/8

7/8

INTRODUCTION

Use this instruction manual to install CAPVP indoor coil on

multipoise furnaces. (See Fig. 1.) The CAPVP coil is enclosed in a

casing.

Do n lo

rnace

Installation

plo

rnace

Installation

Retrn

S pply

Ret rn

S pply

Eapo rator

Coil

A13060

Fig. 1 

 

Typical Installation Upflow/Downflow Cased Coils

*  CAUTION: DO NOT MOUNT COIL LOWER THAN

    3˝ (76mm) MINIMUM OR FURN

ACE FAILURE MAY RESULT

Wide Coil

Narrow Coil

Narrow Furnace

Wide Furnace

Field Fabricated

Adapter(s)

3˝ (76mm)

A13061

Fig. 2 

 

Adapter(s) Installation When Coil Overhangs or Un-

derhangs Furnace

INSTALLATION

Inspect Equipment

File claim with shipper if equipment is damaged or incomplete.

Select Installation

NOTE

:  Consult the furnace installation instructions for any

special requirements when installing the coil to the furnace.

Upflow CAPVP Coil Installation.

The cased coil is designed to fit furnaces of the same width.

1. Set coil in place on upflow furnace discharge air opening.

2. Ensure coil is level for proper condensate drainage. Do not

tip coil toward condensate drain. Coil casing need not be

fastened or screwed to furnace.

3. When installing wider coil on narrow furnace, create field

fabricated adapter. (See Fig. 2.)

4. When installing narrow coil on wide furnace, create field

fabricated adapter. (See Fig. 2.)

NOTE

:  On upflow installations where the indoor coil is placed in

an unconditioned space, a 6” (152 mm) wide piece of insulation
should be applied and wrapped around the outside of coil casing
and supply duct contact point.
See Table 1 for dimensions. Note instructions for placement of coil

casing on furnace.

Downflow CAPVP Coil Installation.

IMPORTANT

: Installing “A” coils rotated 90

_

 from the front of

the furnace in downflow applications can cause water blow off or
coil freeze up. This is due to the concentration of air on one coil
slab or lack of air on the opposite coil slab. If the airflow is high
due to ductwork or other causes, and there is a chance for water
blow off, it is recommended that a 3” (76 mm) field

supplied

adapter be placed between the coil and the furnace to allow the air
to distribute evenly to both coil slabs. (See Fig. 3.)

3” (76mm)

A13062

Fig. 3 

 

Downflow Installation With Coil Rotated 90

_

1. Set cased coil on supply duct opening.
2. Place field fabricated 3” (76 mm) adapter on coil casing.

Adapter should be tapered to fit coil/furnace combination

when one of them is larger than the other.

3. Set furnace on adapter.

NOTE

:  In downflow installation with a 4

way multipoise

furnace, break off perforated duct flanges on furnace. See furnace
installation instructions.

CONNECT REFRIGERANT PIPING

Use accessory tubing package or field

supplied tubing of

refrigerant grade, see Product Data information for ordering.

  CAPVP  

Summary of Contents for CAPVP1917ALA

Page 1: ... WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage NOTE is used to highlight suggestions which will result in enhanced installation reliability or operation ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death Before...

Page 2: ... screwed to furnace 3 When installing wider coil on narrow furnace create field fabricatedadapter See Fig 2 4 When installing narrow coil on wide furnace create field fabricatedadapter See Fig 2 NOTE On upflow installations where the indoor coil is placed in an unconditioned space a 6 152 mm wide piece of insulation should be applied and wrapped around the outside of coil casing and supply duct co...

Page 3: ...evice while brazing valves must be wrapped with a heat sinking material such as a wet cloth CAUTION PERSONAL INJURY HAZARD Failure to follow this warning could result in personal injury Wear eye protection Coil is factory charged with 15 psi nitrogen The coil is under pressure and TXV screen is in place behind liquid line plug DO NOT removed liquid line plug first always remove the suction line pl...

Page 4: ...d primary drain NOTE In applications where return air humidity levels stay at 70 or above for a prolonged period of time condensation can form on the bottom of pan and drip Condensate Line Trap Sewer Line Air Gap Above Liquid Level A10216 Fig 5 Condensate Drain to Waste Line WASTE LINE CONNECTION If the condensate line is to be connected to a waste sewer line an open trap must be installed ahead o...

Reviews: