PRE--COOLING SCHEDULES
Pre--cool offset interaction with other schedules and events
Mode
Pre--cool applies only when the thermostat is in cooling or auto mode and
cooling is in demand.
Hold
When the device is in HOLD, the pre--cool offset is subtracted from the
HOLD cooling setpoint.
DRLC Event
The Pre--cool function shall NOT apply during any DRLC event. This
would defeat the purpose of running an event to save energy.
Price Event
The Pre--cool function shall be cancelled at the time a Price event begins
unless the event has a zero degree offset. This will prevent any overlap if
the user selects a longer pre--cool option that might overlap with a price
event. The pricing offset will be applied to the normal scheduled offset and
not the pre--cool offset, which in effect, cancels the pre--cooling.
Smart Recovery
If the Pre--cool period occurs during a Smart Recovery period, the pre--cool
offset should be applied to the Smart Recovery setpoints.
Program Schedule Changes
If the Program schedule is changed by the user during a Pre--cool period,
the Pre--cool offset should be applied to the new scheduled setpoint.
Vacation
The Pre--cool function shall NOT apply during vacation mode setting.