ComfortVu™ BACnet Thermostat Plus Model TBPL-H (Line voltage)Carrier Proprietary and Confidential
CARRIER CORPORATION ©2020
Installation and Operation Guide
All rights reserved
34
Wiring and DIP switch configurations 26 to 29 – FC systems - 2-pipe
Outputs
Config. 26:
2-Pipe, 1/2/3 Speeds
fan
(1)
, Cool/Heat valve,
Humidifier,
Dehum/Reheat for
Dehumidification
Config. 27:
2-Pipe, 1/2/3 Speeds
fan
(1)
, Cool/Heat valve,
Humidifier, Reheat for
Dehumidification
Config. 28:
2-Pipe, Fan VFS,
Humidifier Reheat for
Dehumidification
Config. 29:
2-Pipe, 1/2/3
speeds fan
(1)
, Cool/Heat
PID, Humidifier, Reheat
for Dehumidification
11
Fan high
Fan high
X
Fan high
12
Fan medium
(or Economizer
(5)
)
Fan medium
(or Economizer
(5)
)
Economizer
(5)
(option – SW2.6 ON)
Fan medium
(or Economizer
(5)
)
13
Fan low
Fan low
X
Fan low
14
Heat element
(2)
(2nd stage heat)
Heat element
(2)
(2nd stage heat)
Heat element
(2)
(2nd stage heat)
Heat element
(2)
(2nd stage heat)
15
Cool/Heat valve
(3)
(1st stage heat)
Cool/Heat valve
(3)
(1st stage heat)
Cool/Heat valve
(3)
(1st stage heat)
X
16
X
X
X
X
AO1
Humidifier
Humidifier
Humidifier
Cool/Heat valve PID
(3)
(1st stage heat)
AO2
Dehumidifier
(4)
(option - See SW2.3)
X
Fan VFS
Humidifier
SW1
SW2
(1)
SW1.1, SW1.2 – Fan speeds:
1 speed (Low):
2 speeds(Low and High):
3 speeds(Low, Medium, and High):
SW1.1 = ON, SW1.2 = OFF
SW1.1 = OFF, SW1.2 = ON
SW1.1 = OFF, SW1.2 = OFF
(2)
SW1.4 – 2nd heating stage:
ON = Enable, OFF = Disable
(3)
SW1.5 – Chilled beam option:
ON = Enable chilled beam (fan will not run with 1st stage cooling)
(4)
SW2.3 – Dehumidification:
ON = Use dehumidifier
OFF = Use reheat for dehumidification
(5)
SW2.6 – Terminal 12 operation:
ON = Economizer
OFF = Fan Medium (3 speeds) / Terminal not in use (1/2 speeds/VFS)
Important: Economizer will not work in 3 fan speeds configuration.
See drawing in
Wiring terminals and DIP switches
(page 23) for DIP switch locations.
Fan on/off: 110-230 Vac, 2.5A max.
Fan VFS, PID valves, Hum., Dehum.: 0-10 Vdc, 0.5 mA Not isolated
Control – Heat elements, Cool/Heat valves, Economizer: 110-230 Vac, 0.3A max.
Summary of Contents for ComfortVu Plus TBPL-H
Page 70: ......
Page 71: ...CARRIER CORPORATION 2020 Catalog No 11 808 706 01 4 7 2020 ...