ComfortVu™ BACnet Thermostat Plus Model TBPL-H (Line voltage)Carrier Proprietary and Confidential
CARRIER CORPORATION ©2020
Installation and Operation Guide
All rights reserved
62
Technician Settings P196 to P200
P196 – Dead zone between humidification and dehumidification
Range: 0...100 %RH
Default: 0 %RH
P197 – Humidity setpoint
Range: 20...100 %RH
Default: 45 %RH
P198 – Not in use
P200 – Restore defaults
Press the ▲button. The display changes from “00” to “01”.
Press the [On/Off] button to restore default settings.
The thermostat turns Off.
Press the [On/Off] button or wait 60 seconds to return to normal display.