F97CMN and G97CMN: Installation, Start-up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
23
See Notes following table.
(SW1-5 and SW4-3 set to OFF, except as indicated. See notes 1 and 2.)
Unit Size: 1002122
Clg/CF Switch settings
External Static Pressure (ESP)
Clg Switches
SW2-3 SW2-2 SW2-1
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
Clg Default:
OFF
OFF
OFF
1820
1825
1840
1845
1840
1835
1825
1805
1780
1770
CF Switches
SW3-3 SW3-2 SW3-1
Low-Clg Default:
OFF
OFF
OFF
750
740
745
730
715
See note 4
Cooling Airflow
(SW2)
Low-Cooling
Airflow (SW3)
OFF
OFF
ON
750
740
745
730
715
See note 4
OFF
ON
OFF
900
900
915
910
905
See note 4
OFF
ON
ON
1070
1075
1095
1095
1090
1085
1095
1080
1065
1070
ON
OFF
OFF
1280
1285
1305
1305
1310
1305
1295
1300
1290
1285
ON
OFF
ON
1440
1445
1465
1465
1470
1485
1480
1485
1475
1460
ON
ON
OFF
1820
1825
1840
1845
1840
1835
1825
1805
1780
1770
ON
ON
ON
2135
2140
2140
2135
2140
2130
2115
2100
2070
2015
Maximum Clg Airflow
2
2160
2165
2175
2170
2160
2150
2135
2120
2065
2020
CF Switches
SW3-3 SW3-2 SW3-1
Cont. Fan Default:
OFF
OFF
OFF
750
740
745
730
715
See note 4
Continuous Fan
Airflow (SW3)
OFF
OFF
ON
750
740
745
730
715
See note 4
OFF
ON
OFF
900
900
915
910
905
See note 4
OFF
ON
ON
1070
1075
1095
1095
1090
1085
1095
1080
1065
1070
ON
OFF
OFF
1280
1285
1305
1305
1310
1305
1295
1300
1290
1285
ON
OFF
ON
1440
1445
1465
1465
1470
1485
1480
1485
1475
1460
ON
ON
OFF
1440
1445
1465
1465
1470
1485
1480
1485
1475
1460
ON
ON
ON
1440
1445
1465
1465
1470
1485
1480
1485
1475
1460
Heating (SW1)
Maximum Heat Airflow
3
1570
1575
1595
1595
1600
1605
1600
1600
1590
1575
Intermediate Heat Airflow
3
950
955
965
975
970
See note 4
Minimum Heat Airflow
3
755
745
750
735
720
See note 4
Unit Size: 1202422
Clg/CF Switch settings
External Static Pressure (ESP)
Clg Switches
SW2-3 SW2-2 SW2-1
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
Clg Default:
OFF
OFF
OFF
1850
1855
1860
1855
1850
1830
1805
1775
1750
1730
CF Switches
SW3-3 SW3-2 SW3-1
Low-Clg Default:
OFF
OFF
OFF
930
925
915
900
885
See note 4
Cooling Airflow
(SW2)
Low-Cooling
Airflow (SW3)
OFF
OFF
ON
765
745
740
705
680
See note 4
OFF
ON
OFF
930
925
915
900
885
See note 4
OFF
ON
ON
1095
1100
1110
1105
1085
See note 4
ON
OFF
OFF
1265
1255
1265
1280
1275
1285
1270
1260
1250
1230
ON
OFF
ON
1465
1455
1470
1465
1465
1470
1455
1450
1435
1415
ON
ON
OFF
1850
1855
1860
1855
1850
1830
1805
1775
1750
1730
ON
ON
ON
2200
2200
2200
2190
2185
2170
2145
2085
1990
1890
Maximum Clg Airflow
2
2200
2200
2200
2190
2185
2170
2145
2085
1990
1890
CF Switches
SW3-3 SW3-2 SW3-1
Cont. Fan Default:
OFF
OFF
OFF
930
925
915
900
885
See note 4
Continuous Fan
Airflow (SW3)
OFF
OFF
ON
765
745
740
705
680
See note 4
OFF
ON
OFF
930
925
915
900
885
See note 4
OFF
ON
ON
1095
1100
1110
1105
1085
See note 4
ON
OFF
OFF
1265
1255
1265
1280
1275
1285
1270
1260
1250
1230
ON
OFF
ON
1465
1455
1470
1465
1465
1470
1455
1450
1435
1415
ON
ON
OFF
1465
1455
1470
1465
1465
1470
1455
1450
1435
1415
ON
ON
ON
1465
1455
1470
1465
1465
1470
1455
1450
1435
1415
Heating (SW1)
Maximum Heat Airflow
3
1815
1820
1825
1820
1815
1795
1775
1745
1720
1700
Intermediate Heat Airflow
3
1095
1100
1110
1105
1085
See note 4
Minimum Heat Airflow
3
905
900
890
875
855
See note 4
Table 7 – Cooling
4
and Heating Air Delivery - CFM (Bottom Return
5
With Filter) (Continued)