F97CMN and G97CMN: Installation, Start-up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
21
Table 7 – Cooling
4
and Heating Air Delivery - CFM (Bottom Return
5
With Filter)
(SW1-5 and SW4-3 set to OFF, except as indicated. See notes 1 and 2.)
Unit Size: 0601714
Clg/CF Switch settings
External Static Pressure (ESP)
Clg Switches
SW2-3 SW2-2 SW2-1
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
Clg Default:
OFF
OFF
OFF
1060
1070
1080
1080
1075
1065
1050
1035
1025
1010
CF Switches
SW3-3 SW3-2 SW3-1
Low-Clg Default:
OFF
OFF
OFF
545
530
520
525
510
See note 4
Cooling Airflow
(SW2)
Low-Cooling
Airflow (SW3)
OFF
OFF
ON
545
530
520
525
510
See note 4
OFF
ON
OFF
710
710
710
695
690
See note 4
OFF
ON
ON
875
880
890
895
895
890
885
880
870
855
ON
OFF
OFF
1060
1070
1080
1080
1075
1065
1050
1035
1025
1010
ON
OFF
ON
1235
1240
1250
1255
1255
1250
1230
1190
1155
1115
ON
ON
OFF
1235
1240
1250
1255
1255
1250
1230
1190
1155
1115
ON
ON
ON
1235
1240
1250
1255
1255
1250
1230
1190
1155
1115
Maximum Clg Airflow
2
1425
1425
1405
1370
1335
1300
1260
1225
1190
1155
CF Switches
SW3-3 SW3-2 SW3-1
Cont. Fan Default:
OFF
OFF
OFF
545
530
520
525
510
See note 4
Continuous Fan
Airflow (SW3)
OFF
OFF
ON
545
530
520
525
510
See note 4
OFF
ON
OFF
710
710
710
695
690
See note 4
OFF
ON
ON
875
880
890
895
895
890
885
880
870
855
ON
OFF
OFF
1060
1070
1080
1080
1075
1065
1050
1035
1025
1010
ON
OFF
ON
1060
1070
1080
1080
1075
1065
1050
1035
1025
1010
ON
ON
OFF
1060
1070
1080
1080
1075
1065
1050
1035
1025
1010
ON
ON
ON
1060
1070
1080
1080
1075
1065
1050
1035
1025
1010
Heating (SW1)
Maximum Heat Airflow
3
1075
1085
1095
1095
1090
1080
1065
1050
1035
1020
Intermediate Heat Airflow
3
535
515
505
515
495
See note 4
Minimum Heat Airflow
3
420
410
415
400
380
See note 4
Unit Size: 0602120
Clg/CF Switch settings
External Static Pressure (ESP)
Clg Switches
SW2-3 SW2-2 SW2-1
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
Clg Default:
OFF
OFF
OFF
1735
1735
1725
1715
1700
1685
1665
1650
1625
1605
CF Switches
SW3-3 SW3-2 SW3-1
Low-Clg Default:
OFF
OFF
OFF
540
525
525
520
540
See note 4
Cooling Airflow
(SW2)
Low-Cooling
Airflow (SW3)
OFF
OFF
ON
540
525
525
520
540
See note 4
OFF
ON
OFF
680
725
725
720
720
See note 4
OFF
ON
ON
925
915
910
895
900
890
875
865
860
855
ON
OFF
OFF
1070
1075
1080
1070
1080
1075
1055
1045
1030
1020
ON
OFF
ON
1215
1245
1235
1220
1220
1210
1200
1195
1185
1175
ON
ON
OFF
1380
1385
1395
1390
1395
1390
1380
1365
1355
1340
ON
ON
ON
1735
1735
1725
1715
1700
1685
1665
1650
1625
1605
Maximum Clg Airflow
2
1955
1950
1940
1925
1905
1885
1855
1815
1745
1685
CF Switches
SW3-3 SW3-2 SW3-1
Cont. Fan Default:
OFF
OFF
OFF
540
525
525
520
540
See note 4
Continuous Fan
Airflow (SW3)
OFF
OFF
ON
540
525
525
520
540
See note 4
OFF
ON
OFF
680
725
725
720
720
See note 4
OFF
ON
ON
925
915
910
895
900
890
875
865
860
855
ON
OFF
OFF
925
915
910
895
900
890
875
865
860
855
ON
OFF
ON
925
915
910
895
900
890
875
865
860
855
ON
ON
OFF
925
915
910
895
900
890
875
865
860
855
ON
ON
ON
925
915
910
895
900
890
875
865
860
855
Heating (SW1)
Maximum Heat Airflow
3
1080
1085
1095
1090
1095
1085
1070
1055
1045
1030
Intermediate Heat Airflow
3
685
725
730
725
730
See note 4
Minimum Heat Airflow
3
560
555
555
550
565
See note 4