F97CMN and G97CMN: Installation, Start-up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
26
Verify that the voltage, frequency, and phase correspond to that specified
on unit rating plate. Also, check to be sure that service provided by
utility is sufficient to handle load imposed by this equipment. Refer to
rating plate or
for equipment electrical specifications.
U.S.A. Installations
: Make all electrical connections in accordance with
the current edition of the National Electrical Code (NEC) NFPA 70 and
any local codes or ordinances that might apply.
Canada Installations
: Make all electrical connections in accordance
with the current edition of the Canadian Electrical Code CSA C22.1 and
any local codes or ordinances that might apply.
A11401
Fig. 31 – Typical Field Wiring Diagram
Table 9 – Electrical Data
A190279
Fig. 32 – Field-Supplied External Electrical Box on Furnace Casing
J-Box Installation
W/W1
W2
COM
Y/Y2
R
G
MODULATING
FURNACE
SIZE
VOLTS-
HERTZ-
PHASE
OPERATING VOLTAGE
RANGE
*
*. Permissible limits of the voltage range at which the unit operates satisfactorily.
MAX UNIT
AMPS
UNIT
AMPACITY
†
†. Unit ampacity = 125 percent of largest operating component’s full load amps plus 100 percent of all other potential operating components’ (EAC, humidifier, etc.) full load
amps.
MINIMUM
WIRE SIZE
AWG
MAXIMUM
WIRE LENGTH
FT (M)
‡
‡. Length shown is as measured one way along wire path between furnace and service panel for maximum 2 percent voltage drop
MAXIMUM FUSE
OR CKT BKR
AMPS
**
**. Time-delay type is recommended
Maximum
Minimum
0601714
115-60-1
127
104
9.0
12.0
14
30 (9.4)
15
0602120
115-60-1
127
104
14.1
18.4
12
31 (9.5)
20
0801714
115-60-1
127
104
9.0
12.0
14
30 (9.4)
15
0802120
115-60-1
127
104
14.1
18.4
12
31 (9.5)
20
1002122
115-60-1
127
104
14.1
18.4
12
31 (9.5)
20
1202422
115-60-1
127
104
14.1
18.4
12
31 (9.5)
20
WARNING
!
ELECTRICAL SHOCK AND FIRE HAZARD
Failure to follow this warning could result in personal injury, death, or
property damage.
The cabinet MUST have an uninterrupted or unbroken ground
according to NEC NFPA 70 or local codes to minimize personal injury
if an electrical fault should occur. In Canada, refer to Canadian
Electrical Code CSA C22.1. This may consist of electrical wire,
conduit approved for electrical ground or a listed, grounded power cord
(where permitted by local code) when installed in accordance with
existing electrical codes. Refer to the power cord manufacturer’s
ratings for proper wire gauge. Do not use gas piping as an electrical
ground.
CAUTION
!
FURNACE MAY NOT OPERATE HAZARD
Failure to follow this caution may result in intermittent furnace
operation.
Furnace control must be grounded for proper operation or else control
will lock out. Control must remain grounded through green/yellow wire
routed to gas valve and manifold bracket screw.
WARNING
!
FIRE HAZARD
Failure to follow this warning could result in personal injury, death, or
property damage.
Do not connect aluminum wire between disconnect switch and furnace.
WARNING
!
FIRE OR ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury, death, or
property damage.
High voltage field connections must be located in J-Box with furnace,
or in field supplied external disconnect mounted to furnace.
If field-supplied manual disconnect switch is to be mounted on furnace
casing side, select a location where a drill or fastener cannot damage
electrical or gas components.
COPPER
WIRE ONLY
ELECTRIC
DISCONNECT
SWITCH
ALUMINUM
WIRE