35
Table 14 — Minimum Outdoor-Air Operating Temperature — English
LEGEND
NOTES:
1. Based on 80 F condensing temperature at 100% and 75%
capacity and a 75 F condensing temperature at 50% and 25%
capacity.
2. Unit sizes 035 to 130 are based on dual circuit operation. Dual
circuit low ambient option should be based on circuit with low-
est TD.
3. Operation below minimum ambient temperatures listed will
require Motormaster
®
control.
UNIT 09DP
TD
MINIMUM AMBIENT (F) WITHOUT MOTORMASTER CONTROL
100% Capacity
75% Capacity
50% Capacity
25% Capacity
018
30
58
62
62
64
25
63
66
65
66
20
67
70
68
68
020
30
44
51
54
59
25
51
58
58
62
20
58
63
64
66
030
30
27
38
45
54
25
37
47
51
58
20
47
55
58
63
035
30
41
48
50
58
25
47
53
55
60
20
53
59
60
63
040
30
32
41
45
55
25
39
47
50
57
20
46
53
56
61
050
30
20
35
45
52
25
25
42
50
56
20
31
50
56
60
060
30
20
30
45
50
25
25
37
50
54
20
31
47
56
58
065
30
19
32
41
51
25
30
42
47
56
20
42
51
55
62
075
30
24
36
43
53
25
35
45
50
57
20
45
54
57
63
085
30
16
29
39
50
25
28
40
46
55
20
39
49
54
61
095
30
15
26
37
49
25
25
38
44
54
20
37
48
53
61
115
30
15
24
35
48
25
22
36
43
54
20
35
46
52
60
130
30
15
25
36
49
25
23
36
43
54
20
36
47
52
60
TD
—
Temperature Difference (F)