background image

11

W R G

Y

W

R

G

C

Y

UNIT TERMINAL CONNECTOR

THERMOSTAT

TERMINALS

FOUR 
WIRES

TWO WIRES

heating only

FURNACE

24-VOLT

TERMINAL BLOCK

TWO WIRES

COOLING SYSTEM

N

O

  C  

 N

C

   I   O

C

 OL   Y   R    G   B

W

R

G

Y

W

R

Y

R

G

Y

C

THERMOSTAT

TERMINAL

4 WIRES

2 WIRES

heating only

wiring
 nuts

FURNACE

24-VOLT

TERMINAL BLOCK

2 WIRES

COOLING SYSTEM

NO

NC

C

UNIT TERMINAL CONNECTOR

N

O

  C   

N

C

   I   OC 

O

L   Y   R    G   B

Standard furnace interlock wiring

Alternate furnace interlock wiring

A11215

Fig. 27 - Interlock Wiring

ELECTRIC CONNECTION TO THE

FURNACE

IMPORTANT

: Never connect a 120- volt AC circuit to the

terminals of the furnace interlock (standard wiring). Only use the
low voltage class 2 circuit of the furnace blower control.

For a furnace connected to a cooling system

On some older thermostats, energizing the “R” and “G” terminals
at the furnace has the effect of energizing “Y” at the thermostat and

thereby turning on the cooling system. If you identify this type of
thermostat, you must use the ALTERNATE FURNACE

INTERLOCK WIRING.

OPERATING THE HRV WITH THE

EVOLUTION AND INFINITY CONTROL

The ventilator has four settings in heating mode and three settings

in cooling mode.

Heating:

AUTO - the ventilator selects the speed based on indoor humidity
and outdoor temperature. It may cycle on/off every 30 minutes

depending on humidity and outside temperature.
LOW - low speed all of the time.
HIGH - high speed all of the time.
DEHUM - will only turn on if humidity is 3% over setpoint. The
speed is determined by indoor humidity and outdoor temperature.

Cooling:

AUTO - the ventilator selects the speed based on indoor humidity

and outdoor temperature. It may cycle on/off every 30 minutes
depending on humidity and outside temperature.
LOW - low speed all of the time.
HIGH - high speed all of the time.
If the fan speed is set to Auto and the ventilator wants to run, the
fan speed will run at High continuous speed. Otherwise, the fan

will stay at the chosen continuous fan speed.

Wiring

Remove top cover assembly from wall control and pass thermostat
wire through hole located on back of control before attaching to

wall. Connect Y, R, G, and B (yellow, red, green and black)
between wall control and HRV circuit board. Following color code

(see Fig. 28 and Fig. 29). Replace top cover assembly.

NOTE

: HRV wall control and circuit board operate on 12vdc.

 YELLOW

Y

R

G B

 RED

 GREEN

 BLACK

A98383

Fig. 28 - Typical Wall Control

% D´HUMIDITE RELATIVE HUMIDITY

´

% HUM. RELATIVE HUM.

55%
45%
35%
30%

EXT. TEMP. EXT.

MODE

MAINTENANCE

AIR EXCHANGE

ECHANGE D´AIR

´

20

25

30

40

50

60

70

80

  10C/50F
    0C/32F
–10C/14F
–20C/–4F

CONTROL

CONNECTOR

WALL  CONTROL

YELLOW

RED

GREEN

BLACK

A98410

Fig. 29 - Control Connections

Summary of Contents for HRVXXLHB

Page 1: ...taller service agency or your distributor or branch for information or assistance The qualified installer or agency must use factory authorized kits or accessories when modifying this product Refer to...

Page 2: ...orced air heating See Fig 2 Moist stale air is exhausted from the high humidity areas in the home such as bathrooms kitchen and laundry room Fresh air is supplied to the cold air return or the supply...

Page 3: ...Remove parts bag from inside unit File claim with shipping company if shipment is damaged or incomplete Select Location The HRV should be located in a conditioned space and in close proximity to a fu...

Page 4: ...es two exhaust registers one for the kitchen one for the bathroom I will connect these registers to a main duct which will connect to the unit high speed performance value of 140 cfm What size of duct...

Page 5: ...N DUCTWORK S Install registers in bedrooms dining room living room and basement S Install registers either in the ceiling or high on the walls with air flow directed towards the ceiling The cooler air...

Page 6: ...HRV CAUTION There are two methods for connecting the unit to the furnace ducts See Fig 12 and 13 B A METAL DUCT MINIMUM 18 0 5 M A B NOT LESS THAN 10 3 1 M A12292 Fig 12 Method 1 Return Supply MINIMUM...

Page 7: ...ect the rigid ducts to the ports IMPORTANT Do not use screws to connect rigid ducts to the ports Make sure that both balancing dampers are left in a fully open position before connecting the ducts to...

Page 8: ...ntrol will override the optional main control Refer to table below to see how to operate the unit using its integrated control PRESS ON PUSH BUTTON LED COLOR RESULTS Once Amber Unit is on Low Speed Tw...

Page 9: ...ight dimming circuits electrical motors dwelling building power or lighting wiring or power distribution panel Use the terminal connector included in the installation kit to perform the electrical con...

Page 10: ...losed to outside Off Low Air exchange with outside Open to outside Low Intermittent 40 min off 20 min exchange low speed Air exchange with outside Open to outside 20 min Closed 40 min Low Off High Air...

Page 11: ...idity and outdoor temperature It may cycle on off every 30 minutes depending on humidity and outside temperature LOW low speed all of the time HIGH high speed all of the time DEHUM will only turn on i...

Page 12: ...ng the unit in you are assured that the unit is not in a defrost cycle 2 Place the magnehelic gauge on a level surface and adjust it to zero A11217 Fig 30 Magnehelic Gauge A12307 Fig 31 Open Balancing...

Page 13: ...14 3 J14 1 J14 2 Furnace blower interlock optional see notes 3 5 J14 4 J14 5 J14 6 J14 7 J14 8 J14 9 J14 10 Override switch optional see notes 3 4 Field wiring remote control see notes 3 4 ICP BK Y R...

Page 14: ...intense use This will ensure maximum efficiency of the plastic partitions within the core Allow heat recovery core to soak for 3 hours in a solution of warm water and mild soap Rinse under stream of...

Page 15: ...S The wires may be broken S Inspect every wire and replace any that are damaged S The wire in the wall OR the wall S Remove the wall control and test it right beside the unit using another control may...

Page 16: ...3 68 20 12 09 124 51 4 026 180 82 1 577 44 42 209 9 14 10 42 47 70 21 11 63 126 52 3 896 181 83 1 533 43 41 198 9 16 9 40 57 72 22 11 20 128 53 3 771 183 84 1 492 40 40 188 5 18 8 38 77 73 23 10 78 12...

Reviews: