background image

TROUBLESHOOTING

If necessary, review the Flotronic Plus Control System,

Control Sequence, and Controls Operation sections
found in this book. Tables 5 and 6 show how to use the
keyboard/display module to access functions and sub-
functions. (These procedures are also explained in the

 Installation, 

 Service Instructions

along with examples and details on using the control
features. A copy of the installation instructions should be
kept handy while troubleshooting.)

Checking Display Codes 

 To determine how the

machine has been programmed to operate, check the

diagnostic information (

and operating

mode displays 

If no display appears,

follow the procedures in Troubleshooting, Modules,
page 23. If the display is working, continue as follows:

1. Note all the alarm codes displayed 

2 .   N o t e   a l l   t h e   o p e r a t i n g   m o d e   c o d e s   d i s p l a y e d

3. Note the leaving chilled water temperature set point

in effect and the current leaving water temperature

If the machine is running, compare the “in effect”

leaving water temperature set point with the current
water temperature. Remember that if reset is in effect,
they may be different because the machine is operating
to the modified chilled water set point. If the current
temperature is equal to the set point but the set point
is not the one desired, recall that if dual set point has
been selected in the schedule function, there are 2 set
points to which the machine can be operating. Check

the programming of the schedule function to see if the

occupied or unoccupied set point should be in effect.

OPERATING MODE CODES 

 Following is an

explanation of the operating mode codes:

Temperature Reset (21) 

 In this mode, the unit is using

temperature reset to adjust the set point, and the unit is
controlling to the modified set point. This means that the
leaving water temperature may not equal the chilled water
set point. The set point can be modified based on return
water, outside air temperature or space temperature.
Demand Limit (22) 

 This indicates that the capacity of

the unit is being limited by the demand limit control

option. The unit may not be able to produce the desired

leaving water temperature because the unit may not load
to full capacity.

 Control (24) -- If this option is in effect and

the cooler water temperature is warm, extra stages will
not be added if the water temperature leaving the cooler is
decreasing faster than   F (0.6 C) per minute.
Standby (26) 

 The unit is being held in the standby

mode either because the RUN /STANDBY switch is 
or a set of relay contacts in series with the 
STANDBY switch is open (contacts wired between
terminals 

 and 

Unoccupied Mode (27) 

 In dual set point schedule, this

mode means the machine is operating to the unoccupied
set point. In single set point schedule, this mode shuts
down the unit in the same manner as “Unit Standby.”

If the schedule is holding the machine off when it is

needed, set the schedule for inactive mode until the
schedule can be properly reprogrammed. (See the Sched-
ule Function section of the Installation, Start-Up and
Service Instructions.) The override feature can also 
used to temporarily place the unit in occupied mode.

Enter

c

l

  , then the number of hours to override

(1 to 

 then press 

  . If the unit is in override and

you wish to cancel it, enter zero hours in the same manner.
Run Mode (28)

To enter the MODES subfunction, depress

 

and use the

key to determine if more than one

mode applies.

Do not attempt to bypass, short or modify the

control circuit or electronic boards in any way to
correct a problem. This could result in component
failures or a hazardous operating condition.

ALARM CODES 

 The following is a detailed descrip-

tion of each alarm code error and the possible cause.

Manual reset of an alarm is accomplished by moving the
RUN/STANDBY switch to STANDBY, then back

to RUN.
Codes 5 l-54, Compressor Failure 

 If the DSIO relay

module relay 

or 

control relay feedback switch opens

during operation of a compressor, the microprocessor

will detect this and will stop the compressor, energize
the alarm light, and display a code of 5 1 to 54, depending
on the compressor. The compressor will be locked off;
to reset, use the manual reset method.

 the lead compressor in a circuit is shut down, all the

other compressors in the circuit will be stopped and
locked off. Only the alarm code for the lead compressor
will be displayed,

The microprocessor has also been programmed to

indicate a compressor failure if the feedback terminal on
the 

 terminal strip receives voltage when the com-

pressor is not supposed to be on.
Following are possible causes for this failure:

 

Switch Open 

 The high-pressure switch

for each compressor is wired in series with the 24-volt
power that energizes the compressor control relay. If the
high-pressure switch opens during operation the com-

pressor will stop and this will be detected by the micro-
processor through the feedback terminals.

 Gas Thermostat 

 The discharge gas thermo-

stat switch in each compressor is also wired in series with
the 24-volt power that energizes the control relay (CR).

If the switch opens during operation of the compressor,

the compressor will be stopped and the failure will be
detected through the feedback terminals.

 Module Failure 

 If a DSIO relay module relay

fails open or closed, the microprocessor will detect this
and lock the compressor off and indicate an error.

Wiring Errors 

 If a wiring error exists causing the CR

or feedback switch not to function properly, the 

 will indicate an error.

 

 

 

 

  I f   t h e   h a r d w a r e   t h a t

monitors the feedback switch fails or the processor fails
to energize the relay module relay to ON, an error may
be indicated.

12

Summary of Contents for HS070-160

Page 1: ...ervice mechanics should install start up and service this equipment When working on the equipment observe precautions in the literature tags stickers and labels attached to the equipment and any other safety precautions that apply l Follow all safety codes 0 Wear safety glasses and work gloves l Use care in handling rigging and setting bulky equipment l Use care in handling elcetronic components E...

Page 2: ...0 second time period the EXV driver module senses this and the processor module immediately shuts down all compressors in the affected refrigeration circuit If a shutdown occurs due to loss of cftarse or low oil pressure the EXV driver module communicates this to the processor module and the processor module locks the compressors off in the affected refrigeration circuit The proper fault code s wi...

Page 3: ...or the other control functions The control monitors the superheat and the rate of change of superheat to control the position of the valve The valve stroke is very large this results in very accurate control of the superheat The electronic expansion valve is also used to limit the maximum saturated suction temperature to 55 F 12 8 C to keep from overloading the compressor during high cooler water ...

Page 4: ...B The liquid line solenoid valve remains closed for 10 seconds after the initial compressor on that refrigeration circuit starts This permits a pump out cycle at start up to minimize refrigerant floodback to the compressor If the compressor in that refrigeration circuit has run in the 15 minutes before the call for cooling the pumpout cycle is bypassed After pumpout the liquid line solenoid valve ...

Page 5: ... FAILURE Unit will restart automatically when power is restored BLOWN FUSE IN POWER FEED DISCONNECT Replace fuse Restart is automatic LOW WATER TEMPERATURE CUTOUT Move RUN STANDBY switch to STANDBY then back to RUN Restart is automatic AUXILIARY INTERLOCK Automatic restart after condition is corrected OPEN CONTROL CIRCUIT FUSE Replace fuse Unit will restart automatically FREEZE PROTECTION Unit wil...

Page 6: ...ing the function name key will advance the display through all subfunctions within a function and then back to the first To move to another function either depress the function name key for the desired function display will show the first subfunction or Access a particular subfunction by using the subfunction number and the function name key KEYBOARD ENTRY DISPLAY R E S E T R S T R R S P DEMAND Tt...

Page 7: ... LCSA X LCSB X OILA X OILB X OUTPUTS SLDA X SLDB X UNLA X UNLB X EXVAO X EXVAC X EXVBO X EXVBC X COMP CA1 X CA2 X CBI X CB2 X X ALARMS ALARM X ALARM X ALARM X MODE MODE X STAG ES X STAGE q 4 El r c 0 c 0 0 c cl 4 ill c SET POlNT If unit is in dual set point mode the set point currently in effect is displayed 0 t El 4 Leaving water temperature System temperatures Cooler leaving water temp Cooler en...

Page 8: ...mber or for zero Field configuration entry codes Number of unloaders enter number Reset type none 1 return water 2 space or outside air Load shed enable disable 1 enable Ftuid type water 1 brine Pulldown enable disable 1 enable FACT CFG COMP X F F D C F G UNLS X RSTP X LDSH X FLD X PLDN X Sunday flag LL rTime periods 2 8 same elements as period I q 4 SET POINT COMMENT DISPLAY SET POINT c w s o x c...

Page 9: ...hut off Circuit B shut off Stop reset Reset Method M a n u a l M a n u a l M a n u a l M a n u a l M a n u a l M a n u a l M a n u a l M a n u a l m a n u a l Auto M a n u a l M a n u a l M a n u a l M a n u a l Auto Auto Auto Auto Auto Auto Auto Probable Cause High pressure switch trip or high discharge gas temp switch trip on when it is not supposed to be on Wiring error between electronic contr...

Page 10: ... Table 6 shows the order of the readouts TEST FLJNCTlOh The test operates the Quick Test diagnostic program When the unit is in STANDBY mode the test subfunctions will energize the solenoid valves unloaders electronic expansion valves and com pressors The solenoids and unloaders will energize for 3 minutes The expansion valve will travel to fully open in one test and to fully closed in the next Th...

Page 11: ...d water pump is turned on The schedule function can be programmed ngle set point or dual set pntnt operation for inactive si SET POINT FUNCTION Set points are entered through the keyboard Set points can be changed within the upper and lower limits which are fixed The ranges are listed below Chilled Water Set Point Water 40 to 70 F 4 4 to 21 C Brine Special Order Units 15 to 70 F 9 4 to 21 C Rc set...

Page 12: ...le this mode shuts down the unit in the same manner as Unit Standby If the schedule is holding the machine off when it is needed set the schedule for inactive mode until the schedule can be properly reprogrammed See the Sched ule Function section of the Installation Start Up and Service Instructions The override feature can also be used to temporarily place the unit in occupied mode Enter c l SCHD...

Page 13: ...e compressors are operating the leaving water temperature thermistor will indicate no temperature change But the temperature of the entering water will drop rapidly and the entering water thermistor will detect this When the entering water temperature drops to 5 F 2 8 C below the leaving water temperature alf the compressors will stop and code no 61 will be displayed To correct use manual reset me...

Page 14: ...does not necessarily mean that a thermistor is accurate To determine accuracy the reading must be compared with a measure ment of the actual temperature to which the thermistor probe is exposed Quick Test The Quick Test feature allows the service technician to individually test all the inputs and outputs of the control system The test function operates the Quick Test diagnostic program When the un...

Page 15: ...ponds to that resistance this temperature should appear in the Quick Test display Loss of charge and oil pressure switch tests show LOW if the switch is open and NRM or SAFE if the switch is closed The input channel can be tested by disconnecting the switch and using a jumper to simulate a closed or open circuit See Fig 5 Note that the switch is read by the processor period ically not continuously...

Page 16: ...24V NEUTRAL 2 4 v F E E D 1 DSlO TERM I STRIP 24v N E U T R A L LC R F CIRCUIT B LOSS OF C H A R G E CiRCUtT A Fig 6 Pressure Feedback Circuit Wiring Simplified U N L O A D E R C K T A UNLOADER CKT B LIQUID LINE SOLENOID CKT A LIQUID LINE SOLENOID CKT B Fig 7 Auxiliary Components 24 V Control Circuit Wiring Simplified 16 ...

Page 17: ... 14213 6 13825 5 13449 2 13084 2 12730 1 12386 6 120533 11730 0 11416 l 11111 5 10815 8 10528 7 10250 0 9979 3 9716 5 9461 3 9213 4 8972 6 8738 6 8511 4 8290 6 59 0 661 0 61 0 620 63 0 644 0 65 0 66 0 67 0 68 0 69 0 70 0 71 0 T2 0 73 13 74 0 75 0 76 0 77 0 76 0 79 0 80 0 87 0 82 0 83 0 84 0 85 0 E6 0 87 0 88 O 89 0 90 0 91 0 92 0 93 0 94 0 95 0 96 0 97 0 98 0 99 0 100 0 101 0 102 0 103 0 104 0 105...

Page 18: ...63 20 079 19 058 I a 094 17 184 16 325 15 515 14 749 14 026 13 342 12 696 12 085 11 506 10 959 10 441 9 9495 9 485 9 0445 8 627 a 237 7 8555 T E M P E R A T U R E C 16 17 la 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 57 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 V O L T A G E 3 38739 3 3366 3 2853 3 23369 3 18154 3 12913 3 07641 3 ...

Page 19: ... recheck Press to reach the EXV A Close Quick Test If a problem still exists replace the EXV driv er If the voltage reading is correct the expansion valve should be checked Next text EXVB Connect the positive test lead to pin 7 and the negative to pin 8 9 IO 1 l in succes sion during the EXVB Quick Test Step 2 Check EXV Wiring Check wiring to elec tronic expansion valves from terminal strip on EXV...

Page 20: ...If EXV plug was disconnected during this process reconnect it after the cover is removed 4 Enter appropriate EXV Quick Test step for EVXA or EXVB in the outputs subfunction of the test function p p j q Press ENTR to initiate test With cover lifted off the EXV valve body observe operation of valve motor and lead screw The motor should turn in the clockwise direction and the lead screw should move d...

Page 21: ...rete steps of n otjc rn arc obtained The large number of steps and long st cdkt r csults in very itccurate control of refrigerant flow B e c a u s e tht EXVs art wntmEItd hy rtw processor module it is possible to track vaIvc pr sition During initial start up EXV is fully cloxcd After start up v rIkc position is tracked by processor by constantly thsct ving amount of valve movement The processor ke...

Page 22: ...8 are located in lead compressor in each circuit in a suction passage between motor and cylinders above oil pump SENSOR REPLACEMENT TI T2 T5 T6 T7 T8 Compressor and Cooler Sensors are installed directly in refrigerant or water circuit Relieve all refrigerant pressure or drain water before removing Proceed as follows refer to Fig I I I Remove and discard original sensor and coupling I IMPORTANT Do ...

Page 23: ... See Fig 9 The proper addresses are PSI0 Processor Module 00 DSIC Relay Module 32 I 610 IiXV Driver Module 50 If a modules indicate a communication failure check the COM hq l tg on the PSI0 module for proper seating lf r good connection is assured and the condition per sists replacr the PSI0 module Xf only a ITS 10 module indicates a communication failure check the COhlM plug on that module for pr...

Page 24: ...re powered up and powered off by a signal from the microprocessor The relays switch the circuit to which they are connected No power is supplied to these connections by the DSIO module S E N S O R B U S C O N N E C T O R INPUTS 24 VAC CHANNEL I J3 PINS I 2 3 I 18 2 3 8 4 586 4 788 2 4 6 88 ARE GROUND C1 PSI0 DSIO DSIO HSIO RELAY EXV DRIVER Fig 13 Sensor Bus Wiring COMMON Is CHANNEL fMoN MON MON 1 ...

Page 25: ...lve to neutral in a repeating sequence to drive the valves in incremental steps S E N S O R B U S C O N N E C T O R RED STATUS LIGHT iREEN C O M M U N I C A T I O N LtGHT STEPPER MOTOR 2 J4 STEPPER MOTOR I I 2 4 6EiBARE GROUND C Keyboard Display Module HSIO Fig 17 he onlv function of the HSIO is to allow the operator I cr municate with the processor It is used to enter confiyt ra tions and set poi...

Page 26: ...or short Replace compressor if necessary Compressor loses oil Seized compressor Reolace comPressor Loss of charge control 1 Repair leak Compressor cycles off on toss of charge Compressor shuts down on high pressure control erratic in action I Low refrigerant charge Add refrigerant High pressure control Replace control erratic in action Expansion valve relay contacts Check cooler and Frosted suctio...

Page 27: ......

Page 28: ...s the right to discontinue or change at any time specifications or designs without notice and without incurring obligations I Book 2 PC111 Catalog No 533 030 Printed in U S A Form30HR HS 1T Pg 28 l 89 Replaces New T a b 5c ...

Reviews: