Adjusting the i-Vu® Open Router driver properties
i-Vu® Open Router
CARRIER CORPORATION ©2020
Installation and Start-up Guide
All rights reserved
19
After you find and upload the i-Vu® Open Router in the i-Vu® interface, you may want to customize the i-Vu® Open
Router's settings for your applications. You can change settings on the
Driver Properties
page.
1
In the i-Vu® interface, right-click the i-Vu® Open Router in the navigation tree and select
Driver Properties
.
2
Adjust the driver as desired.
Driver
On the
Driver
page, you can change the following properties:
•
Backup battery conservation settings. See table below.
•
BAC
view
® inactivity timeout and user password. See table below.
•
Module clock synchronization and failure. See table below.
Backup Battery
Turn off internal backup
battery after ___ days to
conserve battery life (shutoff
date/time)
How long backup battery should run after power loss.
TIP
Downloading memory activates the battery backup. This conserves battery
life when you know the i-Vu® Open Router will be without power for an extended
period after downloading (for example, during shipment):
Verify the
Archive Valid
LED is lit, then set this field to 0.
After you install the i-Vu® Open Router and apply power, enter a number greater
than 0.
BACview Device Control
Overwrite Daylight Saving
parameters set in a BACview
device?
Yes
—
Every memory download includes
Daylight Saving Time
properties from the
System Options
tab and overwrites changes to these properties made from the
BAC
view
®
device.
No
—
Download
Daylight Saving Time
properties during first download. You must
make subsequent changes from the BAC
view
® device.
Keypad inactivity timeout
(minutes)
Log out the user (if a user-level password is required), turn off the backlight, and
display the standby screen after this period of inactivity.
Keypad user-level password
Numeric password user must enter to access system through a BAC
view
®
device.
Module Clock
Clock Fail Date and Time
Date and time the control program uses when controller's real-time clock is
invalid.
TIP
Use an occupied date and time (such as a Tuesday at 10 a.m.) so the
equipment does not operate in unoccupied mode if the controller loses power
during occupancy.
Time Synch Sensitivity
(seconds)
When the controller receives a time sync request, if the difference between the
controller's time and the time sync's time is greater than this field's value, the
controller's time is immediately changed. If the difference is less than this field's
value, the controller's time is slowly adjusted until the time is correct.