Introduction
i-Vu® Open Router
CARRIER CORPORATION ©2020
Installation and Start-up Guide
All rights reserved
2
Specifications
Driver
drv_ivuopenrouter
Maximum number of Open
controllers supported
60
Power
24 Vac ±10%, 50
–
60 Hz
24 VA power consumption
26 Vdc (25 V min, 30 V max)
Single Class 2 source only, 100 VA or less
Port E1
(10/100 BaseT
Ethernet)
For Ethernet LAN, BACnet IP, and Modbus TCP/IP communication at 10 or 100 Mbps,
half duplex
Both
Assigned
(default) and
DHCP
IP addressing are supported and DIP switch
selectable
Port S1 (BACnet MS/TP)
For communication with the controller network using BACnet MS/TP at 9600 bps, 19.2
kbps, 38.4 kbps, or 76.8 kbps (DIP switch selectable). Default is 76.8k bps.
BACnet
For communication with the controller network using ARC156 (156 kbps)
Port S2
EIA-232 port (115.2 kbps) for i-Vu® Open Router configuration using PuTTY or
Hyperterminal.
Local Access
(Router Config) For system start-up and troubleshooting using Field Assistant
Real time clock
Battery-backed real-time clock keeps track of time in event of power failure
Battery
10-year Lithium CR123A battery ensures the following data is retained for a maximum
of 720 hours during power outages:
•
Time
•
Graphics
•
Control programs
•
Editable properties
•
Schedules
•
Trends
To conserve battery life, you can set the driver to turn off battery backup after a
specified number of days and depend on the archive function to restore data when the
power returns.
A low battery is indicated by the
Battery Low
LED or a low battery alarm in the i-Vu®
application, a touchscreen device, and Field Assistant.
Protection
Built-in surge and transient protection for power and communications in compliance
with EN61000-6-1.
Incoming power and network connections are protected by non-replaceable internal
solid-state polyswitches that reset themselves when the condition that causes a fault
returns to normal.
The power and network connections are also protected against transient excess
voltage/surge events lasting no more than 10 msec.
CAUTION
To protect against large electrical surges on serial EIA-485 networks,
place a PROT485 at each place wire enters or exits the building.
Summary of Contents for i-Vu CIV-OR
Page 4: ......
Page 35: ......
Page 36: ...CARRIER CORPORATION 2020 Catalog No 11 808 412 01 12 24 2020 ...