background image

2

Outdoor unit contains system refrigerant charge for operation with
AHRI rated indoor unit when connected by 15 ft. (4.57 m) of

field--supplied or factory accessory tubing. For proper unit
operation, check refrigerant charge using charging information

located on control box cover and/or in the Check Charge section of

this instruction.

IMPORTANT

: Maximum liquid--line size is 3/8--in. OD for all

residential applications including long line.

IMPORTANT

: Always install the factory--supplied liquid--line

filter drier. Obtain replacement filter driers from your distributor or
branch.

INSTALLATION

!

WARNING

UNIT OPERATION AND SAFETY HAZARD

Failure to follow this warning could result in personal injury

or equipment damage.
Puron

R

refrigerant systems operate at higher pressures than

standard R--22 systems.

Do not use R--22 service

equipment or components on Puron refrigerant equipment.

Specifications for this unit in residential new construction market
require the outdoor unit, indoor unit, refrigerant tubing sets,

metering device, and filter drier listed in presale literature. There

can be no deviation. Consult the Application Guideline and
Service Manual – Air Conditioners and Heat Pumps Using Puron

r

Refrigerant to obtain required unit changes for specific applications
and for R--22 retrofit.

Check Equipment and Job Site

Unpack Unit

Move to final location. Remove carton taking care not to damage
unit.

Inspect Equipment

File claim with shipping company prior to installation if shipment
is damaged or incomplete. Locate unit rating plate on unit corner

panel. It contains information needed to properly install unit.
Check rating plate to be sure unit matches job specifications.
This unit employs one louver spacer on each of the four sides to

prevent louver movement during operation. The louver spacers are

trapped between the coil surface and louver at the approximate
center of each side (See Fig. 2). This louver spacer should be

present and, if dislodged during shipment, must be reinstalled
before unit is placed into operation.

A11380

Fig. 2 -- Louver Spacer Location

Install on a Solid, Level Mounting Pad

If conditions or local codes require the unit be attached to pad, tie
down bolts should be used and fastened through knockouts

provided in unit base pan. Refer to unit mounting pattern in Fig. 3

to determine base pan size and knockout hole location.
For hurricane tie downs -- contact your local distributor for details
and PE (Professional Certification), if required by local authorities.
On rooftop applications, mount on level platform or frame. Place

unit above a load--bearing wall and isolate unit and tubing set from
structure. Arrange supporting members to adequately support unit

and minimize transmission of vibration to building. Consult local

codes governing rooftop applications.
Roof mounted units exposed to winds may require wind baffles.
Consult the Application Guideline and Service Manual --

Residential Split System Air Conditioners and Heat Pumps Using
Puron

r

Refrigerant for wind baffle construction.

NOTE

: Unit must be level to within

±

2

_

(

±

3/8 in./ft..) per

compressor manufacturer specifications.

Clearance Requirements

When installing, allow sufficient space for airflow clearance,

wiring, refrigerant piping, and service. Allow 30 in. (762 mm)
clearance to service end of unit and 48 in. (1219.2 mm) above unit.

For proper airflow, a 6 in. (152.4 mm) clearance on one side of

unit and 12 in. (304.8 mm) on all remaining sides must be
maintained. Maintain a distance of 24 in. (609.6 mm) between

units. Position so water, snow, or ice from roof or eaves cannot fall
directly on unit.

3/8---in. (9.53 mm) Dia.

Tiedown Knockouts in

Basepan(2) Places

View From Top

UNIT BASE PAN

Dimension

TIEDOWN KNOCKOUT LOCATIONS in. (mm)

A

B

C

31–1/2 X 31–1/2

9–1/8 (231.8)

6–9/16 (166.7) 24–11/16 (627.1)

35 X 35

9–1/8 (231.8)

6–9/16 (166.7)

28–7/16 (722.3)

A05177

Fig. 3 -- Tiedown Knockout Locations

On rooftop applications, locate unit at least 6 in. (152.4 mm) above

roof surface.

Operating Ambient

The minimum outdoor operating ambient in cooling mode is 55

°

F

(12.78

_

C) without low ambient cooling enabled, and the

maximum outdoor operating ambient in cooling mode is 125

°

F

(51.67

_

C).

24AN

B

6

Summary of Contents for Infinity 24ANB6

Page 1: ...ult in enhanced installation reliability or operation WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death Before installing modifying or servicing system main electrical disconnect switch must be in the OFF position There may be more than 1 disconnect switch Lock out and tag switch with a suitable warning label CUT HAZARD Failure to follow this c...

Page 2: ...t must be reinstalled before unit is placed into operation A11380 Fig 2 Louver Spacer Location Install on a Solid Level Mounting Pad If conditions or local codes require the unit be attached to pad tie down bolts should be used and fastened through knockouts provided in unit base pan Refer to unit mounting pattern in Fig 3 to determine base pan size and knockout hole location For hurricane tie dow...

Page 3: ...LINE APPLICATIONS Over 80 ft 24 38 m Crankcase Heater Yes Yes Compressor Start Assist Capacitor and Relay Yes Yes Evaporator Freeze Thermostat Yes For non Infinity systems only No Liquid Line Solenoid Valve No See Long Line Application Guideline Low ambient Pressure Switch Yes For non Infinity system only No Support Feet Recommended No Thermal Expansion Valve TXV Hard Shutoff Yes Yes Winter Start ...

Page 4: ...hould be evacuated using the recommended deep vacuum method of 500 microns An alternate triple evacuation method may be used See triple evacuation method in Service Manual IMPORTANT Always break a vacuum with dry nitrogen Deep Vacuum Method The deep vacuum method requires a vacuum pump capable of pulling a vacuum of 500 microns and a vacuum gage capable of accurately measuring this vacuum depth Th...

Page 5: ...sory transformer as required Final Wiring Check IMPORTANT Check factory wiring and field wire connections to ensure terminations are secured properly Check wire routing to ensure wires are not in contact with tubing sheet metal etc Compressor Crankcase Heater When equipped with a crankcase heater furnish power to heater a minimum of 24 hr before starting unit To furnish power to heater only set th...

Page 6: ...by subcooling method If any adjustment is necessary adjust charge slowly and allow system to operate for 15 minutes to stabilize before declaring a properly charged system If the indoor temperature is above 80_F 26 67_C and the outdoor temperature is in the favorable range adjust system charge by weight based on line length and allow the indoor temperature to drop to 80_F 26 67_C before attempting...

Page 7: ... the LED will be turned OFF until the next valid communication Amber Status Light An amber colored STATUS light is used to display the operation mode and fault codes as specified in the troubleshooting section See Table 3 for codes and definitions NOTE Only one fault code will be displayed on the outdoor unit control board the most recent with the highest priority Crankcase Heater Operation The cr...

Page 8: ... is ON when outdoor coil temp outdoor air temperature 25_F 3 89_C or outdoor coil temp 80_F 26 67_C or if outdoor fan has been OFF for 30 minutes Fan is turned on to allow refrigerant system to stabilize S Low pressure switch is ignored for first 3 minutes during low ambient start up After 3 minutes if LPS trips then outdoor fan motor is turned off for 10 minutes with the compressor running If LPS...

Page 9: ...three consecutive cycles then unit operation is locked out for 4 hours and the appropriate fault code See Table 3 is displayed CONTACTOR SHORTED DETECTION If there is compressor voltage sensed when there is no demand for compressor operation the contactor may be stuck closed The control will flash the appropriate fault code Check the contactor and control box wiring NO 230V AT COMPRESSOR If the co...

Page 10: ...not reading or out of range Ohm out sensor and check wiring Thermistors out of range 56 Improper relationship between coil sensor and outdoor air sensor Ohm out sen sors and check wiring Thermal Cutout 72 Compressor voltage sensed after start up then absent for 10 consecutive sec onds while cooling demand exists Possible causes are internal compressor over load trip or loss of high voltage to comp...

Page 11: ... Fig 10 Resistance vs Temperature Chart Outdoor Coil Temp OCT Outdoor Air Temp OAT COMM STATUS A06314 Fig 11 Single Stage Control Board LEGEND 24 V FACTORY WIRING 24 V FIELD WIRING FIELD SPLICE CONNECTION A10089 Fig 12 Infinity Control Four Wire Connection Wiring Diagrams See Thermostat Installation Instructions for specific unit combinations 24ANB6 ...

Page 12: ... operate CAUTION R R C W W1 Y Y2 G W Y C G R Y C 24VAC HOT 24VAC COM HEAT STAGE 1 HEAT STAGE 2 INDOOR FAN A C THERMOSTAT TYPICAL FURNACE or FAN COIL AIR CONDITIONER FIELD INSTALLED JUMPER WIRE R R C W W1 Y Y2 G W Y C G R Y C 24VAC HOT 24VAC COM HEAT STAGE 1 HEAT STAGE 2 INDOOR FAN A C THERMOSTAT TYPICAL FURNACE or FAN COIL AIR CONDITIONER A10091 LEGEND 24 V FACTORY WIRING 24 V FIELD WIRING FIELD S...

Page 13: ...manifold hose when charging into suction line with compressor operating S Manifold sets should be 700 psig high side and 180 psig low side with 550 psig low side retard S Use hoses with 700 psig service pressure rating S Leak detectors should be designed to detect HFC refrigerant S Puron refrigerant as with other HFCs is only compatible with POE oils S Vacuum pumps will not remove moisture from oi...

Page 14: ...W Morris St D Indianapolis IN 46231 Printed in U S A Edition Date 08 11 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 24ANB6 2SI Replaces 24ANB6 1SI 24ANB6 ...

Reviews: