background image

6

Start--Up

CAUTION

!

UNIT OPERATION AND SAFETY HAZARD

Failure to follow this caution may result in minor personal

injury, equipment damage or improper operation.
To prevent compressor damage or personal injury, observe the

following:

S

Do not overcharge system with refrigerant.

S

Do not operate unit in a vacuum or at negative pressure.

S

Do not disable low pressure switch in scroll compressor

applications.

S

Dome temperatures may be hot.

CAUTION

!

PERSONAL INJURY HAZARD

Failure to follow this caution may result in personal

injury.
Wear safety glasses, protective clothing, and gloves when

handling refrigerant and observe the following:

S

Front seating service valves are equipped with Schrader

valves.

CAUTION

!

ENVIRONMENTAL HAZARD

Failure to follow this caution may result in environmental

damage.
Federal regulations require that you do not vent refrigerant

to the atmosphere. Recover during system repair or final

unit disposal.

Follow these steps to properly start up the system:

1. After system is evacuated, fully open liquid and vapor ser-

vice valves.

2. Unit is shipped with valve stem(s) front seated (closed) and

caps installed.

Replace stem caps after system is opened to refrigerant flow.
Replace caps finger--tight and tighten with wrench an addi-
tional 1/12 turn

3. Close electrical disconnects to energize system.
4. Set room thermostat at desired temperature. Be sure set

point is below indoor ambient temperature.

5. Set room thermostat to COOL and fan control to ON or

AUTO mode, as desired. Operate unit for 15 minutes.
Check system refrigerant charge.

Check Charge

Factory charge amount and desired subcooling are shown on unit
rating plate. Charging method is shown on information plate inside

unit. To properly check or adjust charge, conditions must be

favorable for subcooling charging. Favorable conditions exist
when the outdoor temperature is between 70

_

F and 100

_

F

(21.11

_

C and 37.78

_

C), and the indoor temperature is between

70

_

F and 80

_

F (21.11

_

C and 26.67

_

C). Follow the procedure

below:
Unit is factory charged for 15ft (4.57 m) of lineset. Adjust charge

by adding or removing 0.6 oz/ft of 3/8 liquid line above or below

15ft (4.57 m) respectively.
For standard refrigerant line lengths (80 ft/24.38 m or less), allow

system to operate in cooling mode at least 15 minutes. If conditions
are favorable, check system charge by subcooling method. If any

adjustment is necessary, adjust charge slowly and allow system to

operate for 15 minutes to stabilize before declaring a properly
charged system.
If the indoor temperature is above 80

_

F (26.67

_

C), and the

outdoor temperature is in the favorable range, adjust system charge

by weight based on line length and allow the indoor temperature to

drop to 80

_

F (26.67

_

C) before attempting to check system charge

by subcooling method as described above.
If the indoor temperature is below 70

_

F (21.11

_

C), or the outdoor

temperature is not in the favorable range, adjust charge for line set

length above or below 15ft (4.57 m) only. Charge level should then
be appropriate for the system to achieve rated capacity. The charge

level could then be checked at another time when the both indoor

and outdoor temperatures are in a more favorable range.

NOTE

: If line length is beyond 80 ft (24.38 m) or greater than

20 ft (6.10 m) vertical separation, See Long Line Guideline for
special charging requirements.

Major Components

Control Board

The AC control board controls the following functions:

S

Compressor contactor operation

S

Outdoor fan motor operation

S

Compressor external protection

S

Pressure switch monitoring

S

Time Delays

Field Connections

When using Infinity communicating control, 4 field wires are

required to be connected to the factory wires already wired to the

ABCD terminal (see Fig. 12). Unit as provided by manufacturer is
set up for Infinity communicating control.
When used with a standard non--communicating thermostat, it is
recommended to use 3 thermostat control wires to be connected to

R, Y and C. When using 3 wires, all diagnostic and time delay
features are enabled (See Fig. 13). Disconnect factory provided

wires from A, B, C, and D terminals. Using factory provided

wires, connect to R, C, and Y on the control board for 3 wire
thermostat control. Connect field 24V wires to factory provided

wires now connected to R, C, and Y and cap both sides or remove
unused factory provided wires.
When only 2 thermostat control wires are available, units will

function, but some control features are lost. (See Fig. 14). With
only 2 wires connected, the circuit board will be powered down

whenever there is no call for cooling, and the following will result:

S

Compressor time delay is reduced from 5 minutes to 10 seconds

S

When the thermostat is not calling for cooling, the amber status
light will be off, and no diagnostics codes will be available

S

All system counters will be reset on each new call for cooling

24AN

B

6

Summary of Contents for Infinity 24ANB6

Page 1: ...ult in enhanced installation reliability or operation WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death Before installing modifying or servicing system main electrical disconnect switch must be in the OFF position There may be more than 1 disconnect switch Lock out and tag switch with a suitable warning label CUT HAZARD Failure to follow this c...

Page 2: ...t must be reinstalled before unit is placed into operation A11380 Fig 2 Louver Spacer Location Install on a Solid Level Mounting Pad If conditions or local codes require the unit be attached to pad tie down bolts should be used and fastened through knockouts provided in unit base pan Refer to unit mounting pattern in Fig 3 to determine base pan size and knockout hole location For hurricane tie dow...

Page 3: ...LINE APPLICATIONS Over 80 ft 24 38 m Crankcase Heater Yes Yes Compressor Start Assist Capacitor and Relay Yes Yes Evaporator Freeze Thermostat Yes For non Infinity systems only No Liquid Line Solenoid Valve No See Long Line Application Guideline Low ambient Pressure Switch Yes For non Infinity system only No Support Feet Recommended No Thermal Expansion Valve TXV Hard Shutoff Yes Yes Winter Start ...

Page 4: ...hould be evacuated using the recommended deep vacuum method of 500 microns An alternate triple evacuation method may be used See triple evacuation method in Service Manual IMPORTANT Always break a vacuum with dry nitrogen Deep Vacuum Method The deep vacuum method requires a vacuum pump capable of pulling a vacuum of 500 microns and a vacuum gage capable of accurately measuring this vacuum depth Th...

Page 5: ...sory transformer as required Final Wiring Check IMPORTANT Check factory wiring and field wire connections to ensure terminations are secured properly Check wire routing to ensure wires are not in contact with tubing sheet metal etc Compressor Crankcase Heater When equipped with a crankcase heater furnish power to heater a minimum of 24 hr before starting unit To furnish power to heater only set th...

Page 6: ...by subcooling method If any adjustment is necessary adjust charge slowly and allow system to operate for 15 minutes to stabilize before declaring a properly charged system If the indoor temperature is above 80_F 26 67_C and the outdoor temperature is in the favorable range adjust system charge by weight based on line length and allow the indoor temperature to drop to 80_F 26 67_C before attempting...

Page 7: ... the LED will be turned OFF until the next valid communication Amber Status Light An amber colored STATUS light is used to display the operation mode and fault codes as specified in the troubleshooting section See Table 3 for codes and definitions NOTE Only one fault code will be displayed on the outdoor unit control board the most recent with the highest priority Crankcase Heater Operation The cr...

Page 8: ... is ON when outdoor coil temp outdoor air temperature 25_F 3 89_C or outdoor coil temp 80_F 26 67_C or if outdoor fan has been OFF for 30 minutes Fan is turned on to allow refrigerant system to stabilize S Low pressure switch is ignored for first 3 minutes during low ambient start up After 3 minutes if LPS trips then outdoor fan motor is turned off for 10 minutes with the compressor running If LPS...

Page 9: ...three consecutive cycles then unit operation is locked out for 4 hours and the appropriate fault code See Table 3 is displayed CONTACTOR SHORTED DETECTION If there is compressor voltage sensed when there is no demand for compressor operation the contactor may be stuck closed The control will flash the appropriate fault code Check the contactor and control box wiring NO 230V AT COMPRESSOR If the co...

Page 10: ...not reading or out of range Ohm out sensor and check wiring Thermistors out of range 56 Improper relationship between coil sensor and outdoor air sensor Ohm out sen sors and check wiring Thermal Cutout 72 Compressor voltage sensed after start up then absent for 10 consecutive sec onds while cooling demand exists Possible causes are internal compressor over load trip or loss of high voltage to comp...

Page 11: ... Fig 10 Resistance vs Temperature Chart Outdoor Coil Temp OCT Outdoor Air Temp OAT COMM STATUS A06314 Fig 11 Single Stage Control Board LEGEND 24 V FACTORY WIRING 24 V FIELD WIRING FIELD SPLICE CONNECTION A10089 Fig 12 Infinity Control Four Wire Connection Wiring Diagrams See Thermostat Installation Instructions for specific unit combinations 24ANB6 ...

Page 12: ... operate CAUTION R R C W W1 Y Y2 G W Y C G R Y C 24VAC HOT 24VAC COM HEAT STAGE 1 HEAT STAGE 2 INDOOR FAN A C THERMOSTAT TYPICAL FURNACE or FAN COIL AIR CONDITIONER FIELD INSTALLED JUMPER WIRE R R C W W1 Y Y2 G W Y C G R Y C 24VAC HOT 24VAC COM HEAT STAGE 1 HEAT STAGE 2 INDOOR FAN A C THERMOSTAT TYPICAL FURNACE or FAN COIL AIR CONDITIONER A10091 LEGEND 24 V FACTORY WIRING 24 V FIELD WIRING FIELD S...

Page 13: ...manifold hose when charging into suction line with compressor operating S Manifold sets should be 700 psig high side and 180 psig low side with 550 psig low side retard S Use hoses with 700 psig service pressure rating S Leak detectors should be designed to detect HFC refrigerant S Puron refrigerant as with other HFCs is only compatible with POE oils S Vacuum pumps will not remove moisture from oi...

Page 14: ...W Morris St D Indianapolis IN 46231 Printed in U S A Edition Date 08 11 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 24ANB6 2SI Replaces 24ANB6 1SI 24ANB6 ...