background image

9

TROUBLESHOOTING

SYSTEMS COMMUNICATION FAILURE

If communication between outdoor unit, control board, and indoor
user interface control has failed, the control will flash the

appropriate fault code. (See table 3) Check the wiring to the UI,

indoor and outdoor units.

PRESSURE SWITCH PROTECTION

The outdoor unit is equipped with high-- and low--pressure
switch es. If th e co n tro l sen ses th e o p en in g o f a h ig h o r

low--pressure switch, it will de--energize the compressor contactor,

keep the outdoor fan operating for 15 minutes and display the
appropriate fault code. (See table 3)
After a 15 minute delay, if there is still a call for cooling, and the

LPS or HPS is reset, the compressor contactor is energized. If the
LPS or HPS has not closed after a 15 minute delay, the outdoor fan

is turned off. If the open switch closes anytime after the 15--minute

delay, then the unit will resume operation with a call for cooling.
If the LPS or HPS trips for five consecutive cycles, then unit
operation is locked out for 4 hours and the appropriate fault code

(See table 3) is displayed.
In the event of a high--pressure switch trip or high--pressure

lockout, check the refrigerant charge, outdoor fan operation and
outdoor coil for airflow restrictions.
In the event of a low--pressure switch trip or low--pressure lockout,

check the refrigerant charge and indoor airflow.

CONTROL FAULT

If the outdoor unit control board has failed, the control will flash

the appropriate fault code. (See table 3) The control board should
be replaced.

24V BROWN OUT PROTECTION

If the control voltage is less than 15.5volts for at least 4 seconds,
the compressor contactor and fan relay are de-- energized.

Compressor and fan operation are not allowed until control voltage
is a minimum of 17.5volts. The control will flash the appropriate

fault code. (See table 3) Verify the control voltage is in the
allowable range of 18--30volts.

COMPRESSOR VOLTAGE SENSING

The input terminals labeled VR and VS on the control board (see
Fig. 11) are used to detect compressor voltage status, and alert the

user of potential problems. The control continuously monitors the

high voltage on the run capacitor of the compressor motor. Voltage
should be present any time the compressor contactor is energized,

and voltage should not be present when the contactor is
de--energized.

COMPRESSOR THERMAL CUTOUT OR LOSS

OF 230V POWER

If the control senses the compressor voltage after start--up, and is
then absent for 10 consecutive seconds while cooling demand

exists, it will de--energize the compressor contactor, keep the

outdoor fan operating for 15 minutes (if 230v power present) and
display the appropriate fault code. (See table 3) Possible causes are

compressor internal overload trip or loss of high voltage (230V) to
compressor without loss of control voltage.
After a 15 minute delay, if there is still a call for cooling, the

compressor contactor is energized. If the thermal protector has not

re--set, the outdoor fan is turned off. If the call for cooling
continues, the control will energize the compressor contactor every

15 minutes. If the thermal protector closes, (at the next 15 minute
interval check), the unit will resume operation.
If the thermal cutout trips for three consecutive cycles, then unit

operation is locked out for 4 hours and the appropriate fault code

(See Table 3) is displayed.

CONTACTOR SHORTED DETECTION

If there is compressor voltage sensed when there is no demand for
compressor operation, the contactor may be stuck closed. The

control will flash the appropriate fault code. Check the contactor
and control box wiring.

NO 230V AT COMPRESSOR

If the compressor voltage is not sensed when the compressor
should be starting, the contactor may be stuck open or the unit

disconnect or circuit breaker may be open. The control will flash
the appropriate fault code. Check the contactor, unit disconnect or

circuit breaker and control box wiring.

TEMPERATURE THERMISTORS

Thermistors are electronic devices which sense temperature. As the

temperature increases, the resistance decreases. Thermistors are
used to sense outdoor air (OAT) and coil temperature (OCT).
If the outdoor air or coil thermistor should fail, the control will

flash the appropriate fault code. (See table 3)

IMPORTANT

: The outdoor air thermistor and coil thermistor are

factory mounted in the correct locations.

Do not re--locate

thermistor sensors.

THERMISTOR SENSOR COMPARISON

The control continuously monitors and compares the outdoor air

temperature sensor and outdoor coil temperature sensor to ensure
proper operating conditions. The comparison is, if the outdoor air

sensor indicates

10

_

F (

--12.22

_

C) warmer than the coil sensor

(or) the outdoor air sensor indicates

20

_

F (

--6.67

_

C) cooler than

the coil sensor, the sensors are out of range.
If the sensors are out of range, the control will flash the appropriate

fault code. (See Table 3)
The thermistor comparison is not performed during low ambient

cooling.

FAILED THERMISTOR DEFAULT OPERA-

TION

Factory defaults have been provided in the event of failure of

outdoor air thermistor and/or coil thermistor.
If the OAT sensor should fail, low ambient cooling will not be
allowed, and the one minute outdoor fan off delay will not occur.
If the OCT sensor should fail, low ambient cooling will not be

allowed.
Thermistor Curve: The resistance vs. temperature chart shown in

Figure 12 enables the technician to check the outdoor air and
outdoor coil thermistors for proper resistance. Unplug the

thermistor assembly from the circuit board and measure resistance
across each thermistor. For example, if the outdoor temperature is

60

_

F (15.56

_

C), the resistance reading across the outdoor air

thermistor should be around 16,000 Ohms.

STATUS CODES

Table 3 shows the status codes flashed by the amber status light.
Most system problems can be diagnosed by reading the status code

as flashed by the amber status light on the control board.
The codes are flashed by a series of short and long flashes of the

status light. The short flashes indicate the first digit in the status
code, followed by long flashes indicating the second digit of the

error code. The short flash is 0.25 second ON and the long flash is

1.0 second ON. Time between flashes is 0.25 second. Time
between short flash and first long flash is 1.0 second. Time

between code repeating is 2.5 seconds with LED OFF.
Count the number of short and long flashes to determine the
appropriate flash code. Table 3 gives possible causes and actions

related to each error.
Example: 3 short flashes followed by 2 long flashes indicates a 32

code. Table 3 shows this to be low pressure switch open.

24AN

B

6

Summary of Contents for Infinity 24ANB6

Page 1: ...ult in enhanced installation reliability or operation WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death Before installing modifying or servicing system main electrical disconnect switch must be in the OFF position There may be more than 1 disconnect switch Lock out and tag switch with a suitable warning label CUT HAZARD Failure to follow this c...

Page 2: ...t must be reinstalled before unit is placed into operation A11380 Fig 2 Louver Spacer Location Install on a Solid Level Mounting Pad If conditions or local codes require the unit be attached to pad tie down bolts should be used and fastened through knockouts provided in unit base pan Refer to unit mounting pattern in Fig 3 to determine base pan size and knockout hole location For hurricane tie dow...

Page 3: ...LINE APPLICATIONS Over 80 ft 24 38 m Crankcase Heater Yes Yes Compressor Start Assist Capacitor and Relay Yes Yes Evaporator Freeze Thermostat Yes For non Infinity systems only No Liquid Line Solenoid Valve No See Long Line Application Guideline Low ambient Pressure Switch Yes For non Infinity system only No Support Feet Recommended No Thermal Expansion Valve TXV Hard Shutoff Yes Yes Winter Start ...

Page 4: ...hould be evacuated using the recommended deep vacuum method of 500 microns An alternate triple evacuation method may be used See triple evacuation method in Service Manual IMPORTANT Always break a vacuum with dry nitrogen Deep Vacuum Method The deep vacuum method requires a vacuum pump capable of pulling a vacuum of 500 microns and a vacuum gage capable of accurately measuring this vacuum depth Th...

Page 5: ...sory transformer as required Final Wiring Check IMPORTANT Check factory wiring and field wire connections to ensure terminations are secured properly Check wire routing to ensure wires are not in contact with tubing sheet metal etc Compressor Crankcase Heater When equipped with a crankcase heater furnish power to heater a minimum of 24 hr before starting unit To furnish power to heater only set th...

Page 6: ...by subcooling method If any adjustment is necessary adjust charge slowly and allow system to operate for 15 minutes to stabilize before declaring a properly charged system If the indoor temperature is above 80_F 26 67_C and the outdoor temperature is in the favorable range adjust system charge by weight based on line length and allow the indoor temperature to drop to 80_F 26 67_C before attempting...

Page 7: ... the LED will be turned OFF until the next valid communication Amber Status Light An amber colored STATUS light is used to display the operation mode and fault codes as specified in the troubleshooting section See Table 3 for codes and definitions NOTE Only one fault code will be displayed on the outdoor unit control board the most recent with the highest priority Crankcase Heater Operation The cr...

Page 8: ... is ON when outdoor coil temp outdoor air temperature 25_F 3 89_C or outdoor coil temp 80_F 26 67_C or if outdoor fan has been OFF for 30 minutes Fan is turned on to allow refrigerant system to stabilize S Low pressure switch is ignored for first 3 minutes during low ambient start up After 3 minutes if LPS trips then outdoor fan motor is turned off for 10 minutes with the compressor running If LPS...

Page 9: ...three consecutive cycles then unit operation is locked out for 4 hours and the appropriate fault code See Table 3 is displayed CONTACTOR SHORTED DETECTION If there is compressor voltage sensed when there is no demand for compressor operation the contactor may be stuck closed The control will flash the appropriate fault code Check the contactor and control box wiring NO 230V AT COMPRESSOR If the co...

Page 10: ...not reading or out of range Ohm out sensor and check wiring Thermistors out of range 56 Improper relationship between coil sensor and outdoor air sensor Ohm out sen sors and check wiring Thermal Cutout 72 Compressor voltage sensed after start up then absent for 10 consecutive sec onds while cooling demand exists Possible causes are internal compressor over load trip or loss of high voltage to comp...

Page 11: ... Fig 10 Resistance vs Temperature Chart Outdoor Coil Temp OCT Outdoor Air Temp OAT COMM STATUS A06314 Fig 11 Single Stage Control Board LEGEND 24 V FACTORY WIRING 24 V FIELD WIRING FIELD SPLICE CONNECTION A10089 Fig 12 Infinity Control Four Wire Connection Wiring Diagrams See Thermostat Installation Instructions for specific unit combinations 24ANB6 ...

Page 12: ... operate CAUTION R R C W W1 Y Y2 G W Y C G R Y C 24VAC HOT 24VAC COM HEAT STAGE 1 HEAT STAGE 2 INDOOR FAN A C THERMOSTAT TYPICAL FURNACE or FAN COIL AIR CONDITIONER FIELD INSTALLED JUMPER WIRE R R C W W1 Y Y2 G W Y C G R Y C 24VAC HOT 24VAC COM HEAT STAGE 1 HEAT STAGE 2 INDOOR FAN A C THERMOSTAT TYPICAL FURNACE or FAN COIL AIR CONDITIONER A10091 LEGEND 24 V FACTORY WIRING 24 V FIELD WIRING FIELD S...

Page 13: ...manifold hose when charging into suction line with compressor operating S Manifold sets should be 700 psig high side and 180 psig low side with 550 psig low side retard S Use hoses with 700 psig service pressure rating S Leak detectors should be designed to detect HFC refrigerant S Puron refrigerant as with other HFCs is only compatible with POE oils S Vacuum pumps will not remove moisture from oi...

Page 14: ...W Morris St D Indianapolis IN 46231 Printed in U S A Edition Date 08 11 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 24ANB6 2SI Replaces 24ANB6 1SI 24ANB6 ...

Reviews: