5
Orifice Size and Manifold Pressure (in.w.c.) for Gas Input Rate (cont.)
S
A
G
L
A
R
U
T
A
N
F
O
Y
T
I
V
A
R
G
C
I
F
I
C
E
P
S
S
A
G
.
G
V
A
HEAT VALUE
0.58
0.60
0.62
0.64
AT ALTITUDE
Orifice
Manifold
Orifice
Manifold
Orifice
Manifold
Orifice
Manifold
(Btu/cu ft)
No.
Pressure
No.
Pressure
No.
Pressure
No.
Pressure
ALTITUDE
RANGE
ft (m)
SINGLE-STAGE FURNACE
(TABULATED DATA BASED ON 20,000 BTUH PER BURNER, DERATED 2%/1000 FT (305M) ABOVE SEA LEVEL)
650
42
3.4
42
3.5
42
3.6
42
3.7
7001
675
43
3.8
42
3.2
42
3.3
42
3.4
(2134)
700
43
3.5
43
3.7
43
3.8
42
3.2
725
44
3.8
43
3.4
43
3.5
43
3.6
750
44
3.5
44
3.7
44
3.8
43
3.4
8000
775
44
3.3
44
3.4
44
3.5
44
3.7
(2438)
800
44
3.1
44
3.2
44
3.3
44
3.4
825
44
2.9
44
3.0
44
3.1
44
3.2
625
42
3.4
42
3.5
42
3.6
42
3.7
8001
650
43
3.8
42
3.2
42
3.3
42
3.4
(2439)
675
43
3.5
43
3.6
43
3.7
42
3.2
700
44
3.7
43
3.4
43
3.5
43
3.6
725
44
3.5
44
3.6
44
3.7
44
3.8
9000
750
44
3.3
44
3.4
44
3.5
44
3.6
(2743)
775
44
3.0
44
3.2
44
3.3
44
3.4
9001
600
42
3.3
42
3.4
42
3.6
42
3.7
(2744)
625
43
3.7
42
3.2
42
3.3
42
3.4
650
43
3.5
43
3.6
43
3.7
43
3.8
675
44
3.7
44
3.8
43
3.4
43
3.5
10000
700
44
3.4
44
3.5
44
3.7
44
3.8
(3048)
725
44
3.2
44
3.3
44
3.4
44
3.5
* Orifice numbers shown in
BOLD
are factory-installed.
to
to
to
U.
S
.A.
On
ly
U.
S
.A.
On
ly
U.
S
.A.
On
ly
A11253B
Figure 6
Igniter Position
−
Back View
A11405
2-1/2-in.
(64.4)
1-1/4-in.
(31.8)
Figure 7
Igniter Position
−
Side View
A12392
2
−
in.
(2.5 mm
3/8
−
in.
3/16
−
in.
, +0.8 -1.5)
(50 mm)
(9.6 mm)
(4.6 mm)
3/32
−
in., +1/32 -3/64-in.
CONVERT GAS VALVE
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in unit damage
The gas valve must be converted and pre
−
adjusted before
operating on propane gas. If not converted and pre
−
adjusted,
sooting and corrosion will occur leading to early heat
exchanger failure.
!
WARNING
FIRE, EXPLOSION, ELECTRICAL SHOCK
HAZARD
Failure to follow this warning could result in personal injury,
death or property damage.
Gas supply MUST be shut off before disconnecting electrical
power and proceeding with conversion.
Do not use this kit if the gas valve in
has a green label
on top of the valve. The green label on the gas valve is a special
low capacity gas valve. Refer to Specification Sheet for the
correct conversion kit.