background image

12

NOx DEVICE INSTALLATION (when

required)

The following models must have NOx baffles installed (58PHX,

58PHY, 58DLX, 58STX, 313JAV, 313JBV, 311JAV, 310JAV,

PG8JEA, PG8JEB, and PG8JAA). NOx baffles are not included

in this kit and must be ordered separately or reused if retained

from original conversion to Propane.
For NOx device installation, follow these additional steps:

Figure 16

Representative Furnace Drawing

A03069

Representative drawing only, some models may vary in appearance.

9. Use a pair of needle nose pliers to install the NOx device.

10. Squeeze the sides of the device, if necessary, to install in

the heat exchanger.

11. Re-install screw in hole underneath heat exchanger inlet.

It is very IMPORTANT to reinstall the NOx bracket mounting
screw. (See 

Figure 17

)

12. Repeat steps for each heat exchanger.

Figure 17

NOx Device Installation

A02195

ORIFICE SELECTION/DERATE

!

CAUTION

UNIT DAMAGE HAZARD

Failure to follow this caution may result in unit damage.
DO NOT re

drill burner orifices. Improper drilling may result in

burrs, out

of

round holes, etc. Obtain new orifices if orifice size

must be changed. (See 

Figure 18

)

Figure 18

Burner Orifice

BURNER 
ORIFICE

BURNER 
ORIFICE

A96249

Determine natural gas orifice size and manifold pressure for

correct input at installed altitude by using  

Table 5

 or 

Table 6

.

All models in all positions except Low NOx models in downflow
and horizontal positions use 

Table 5

 (22,000 Btuh per burner).

Low NOx models in downflow or horizontal positions must use

Table 6

 (21,000 Btuh per burner). See input listed on rating plate.

Use Table 5 (22,000 Btuh per burner) for models 58DLA, 58PHA,

58PHB, 58STA, 310AAV, 311AAV, 313AAV, 313ABV, PG8MAA,

and PG8MEA.
Use Table 6 (21,000 Btuh per burner) for Low NOx models

58DLX, 58PHX, 58PHY, 58STX, 310JAV, 311JAV, 313JAV,

313JBV,  PG8JAA, PG8JEA, and PG8JEB.

1. Obtain yearly heat

value average (at installed altitude) for

local gas supply.

2. Obtain yearly specific

gravity average for local gas supply.

3. Find installation altitude in 

Table 5

 or 

Table 6

.

For Canada altitudes of 2000 to 4500 ft., use U.S.A. Altitudes of

2001 to 3000 ft. in 

Table 5

 or 

Table 6

.

4. Find closest natural gas heat value and specific gravity in

Table 5

 or 

Table 6

.

5. Follow heat

value line and specific

gravity line to point of

intersection to find orifice size and manifold pressure

setting.

Furnace gas input rate on furnace rating plate is for installations

at altitudes up to 2000 ft. (610 M).

In the U.S.A

.; the input rating for altitudes above 2000 ft. (610 M)

must be reduced by 4 percent for each 1000 ft. (305 M) above

sea level.

In Canada

, the input rating must be derated by 5 percent for

altitudes of 2000 ft. to 4500 ft. (610 M to 1372 M) above sea

level.
The Conversion Kit Rating Plate accounts for high altitude

derate.

INSTALL ORIFICES

1. Install main burner orifices. DO NOT use Teflon tape.

Finger-tighten orifices at least one full turn to prevent

cross-threading, then tighten with wrench.

2. There are enough orifices in each kit for largest furnace.

Discard extra orifices.

DO NOT reinstall the manifold at this time.

Summary of Contents for KGBPN42011SP

Page 1: ...n perform basic maintenance functions such as cleaning and replacing air filters Trained service personnel must perform all other operations When working on heating equipment observe precautions in th...

Page 2: ...ZW037 1 VALVE CVRSN KIT W R SPRING 92 0935 323267 701 1 PARTS ASSY 42 323267 702 1 PARTS ASSY 43 323267 703 1 PARTS ASSY 44 323267 704 1 PARTS ASSY 45 339851 701 1 LABEL KIT 339851 702 1 LABEL KIT 319...

Page 3: ...in yearly specific gravity average for local gas supply 3 Find installation altitude in Table 3 For Canada altitudes of 2000 to 4500 ft use U S A Altitudes of 2001 to 3000 ft in Table 3 4 Find closest...

Page 4: ...43 3 7 43 3 8 42 3 2 850 44 3 8 43 3 5 43 3 6 43 3 7 875 44 3 6 44 3 7 43 3 4 43 3 5 4000 900 44 3 4 44 3 5 44 3 7 44 3 8 1219 925 44 3 2 44 3 4 44 3 5 44 3 6 950 44 3 1 44 3 2 44 3 3 44 3 4 750 42 3...

Page 5: ...625 43 3 7 42 3 2 42 3 3 42 3 4 650 43 3 5 43 3 6 43 3 7 43 3 8 675 44 3 7 44 3 8 43 3 4 43 3 5 10000 700 44 3 4 44 3 5 44 3 7 44 3 8 3048 725 44 3 2 44 3 3 44 3 4 44 3 5 Orifice numbers shown in BOLD...

Page 6: ...stment screw 5 Remove the Propane regulator spring white 6 Install the natural gas regulator spring silver 7 Install the regulator adjustment screw 8 Turn the adjusting screw clockwise in 8 5 full tur...

Page 7: ...its splice connection with the yellow wire of the furnace wire harness Disconnect and discard this orange wire and the splice connection c Connect the yellow wire of the furnace wire harness see b abo...

Page 8: ...3 For Canada altitudes of 2000 to 4500 ft use U S A Altitudes of 2001 to 3000 ft in Table 3 4 Find closest natural gas heat value and specific gravity in Table 3 5 Follow heat value line and specific...

Page 9: ...tion instructions Figure 12 Conversion Rating Plate Label A13070 LABEL APPLICATION 1 Fill in Conversion Responsibility Label 339851 205 and apply over Propane Conversion Responsibility Label Date name...

Page 10: ...amage Improper installation adjustment alteration service maintenance or use can cause carbon monoxide poisoning explosion fire electrical shock or other conditions which could result in personal inju...

Page 11: ...fore installing modifying or servicing system main electrical disconnect switch must be in the OFF position and install a lockout tag There may be more than one disconnect switch Lock out and tag swit...

Page 12: ...er burner Low NOx models in downflow or horizontal positions must use Table 6 21 000 Btuh per burner See input listed on rating plate Use Table 5 22 000 Btuh per burner for models 58DLA 58PHA 58PHB 58...

Page 13: ...44 3 4 44 3 5 43 3 2 U S A 2001 to 3000 610 to 914 800 42 3 4 42 3 5 42 3 6 42 3 7 825 42 3 2 42 3 3 42 3 4 42 3 5 850 43 3 7 43 3 8 42 3 2 42 3 3 875 43 3 5 43 3 6 43 3 7 43 3 8 900 43 3 3 43 3 4 43...

Page 14: ...25 43 2 9 43 3 0 43 3 1 43 3 2 750 43 2 7 43 2 8 43 2 9 43 3 0 775 43 2 6 43 2 7 43 2 7 43 2 8 800 43 2 4 43 2 5 43 2 6 43 2 7 825 43 2 3 43 2 3 43 2 4 43 2 5 850 43 2 1 43 2 2 43 2 3 43 2 4 U S A 700...

Page 15: ...4 43 3 5 900 43 3 0 43 3 1 43 3 2 43 3 3 925 43 2 8 43 2 9 43 3 0 43 3 1 950 43 2 7 43 2 8 43 2 9 43 2 9 975 43 2 5 43 2 6 43 2 7 43 2 8 1000 43 2 4 43 2 5 43 2 6 43 2 7 U S A 3001 to 4000 914 to 1219...

Page 16: ...8 43 2 9 650 43 2 5 43 2 5 43 2 6 43 2 7 675 43 2 3 43 2 4 43 2 4 43 2 5 700 43 2 1 43 2 2 43 2 3 43 2 3 725 48 3 7 43 2 0 43 2 1 43 2 2 750 48 3 5 48 3 6 48 3 7 43 2 0 U S A 9001 to 10 000 2743 to 3...

Page 17: ...itch Lock out and tag switch with a suitable warning label Verify proper operation after servicing For J and G valves See Figure 24 1 Be sure gas and electrical supplies to furnace are off 2 Remove ca...

Page 18: ...re than one disconnect switch Lock out and tag switch with a suitable warning label Verify proper operation after servicing 1 Be sure main gas and electric supplies to furnace are off 2 Remove Low Gas...

Page 19: ...ressure tap on gas valve 2 Turn on furnace power supply 3 Turn gas supply manual shutoff valve to ON position 4 Turn furnace gas valve switch to ON position 5 Jumper R W thermostat connections on cont...

Page 20: ...ition 7 Jumper R and W thermostat connections to call for heat See Figure 13 8 Check manifold orifices for gas leaks when main burners ignite 9 Adjust gas manifold pressure Refer to Table 5 or Table 6...

Reviews: