Figure 19

Conversion Kit Rating Plate Label

A13071

Table 5

Orifice Size* and Manifold Pressure (in. w.c.)  for Gas Input Rate
(Tabulated data based on 22,000 Btuh per burner, derated 4 percent for each 1000 ft. (305 M) above sea level)

ALTITUDE RANGE

FT. (M)

AVG. GAS

HEAT VALUE

AT ALTITUDE

(BTU/CU FT.)

SPECIFIC GRAVITY OF NATURAL GAS

0.58

0.60

0.62

0.64

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

Orifice

No.

Manifold

Pressure

U.S.A.

0 to 2000

(0 to 610)

900

42

3.5

42

3.6

42

3.7

41

3.5

925

42

3.3

42

3.4

42

3.5

42

3.7

950

43

3.8

42

3.3

42

3.4

42

3.5

975

43

3.6

43

3.8

42

3.2

42

3.3

1000

43

3.5

43

3.6

43

3.7

43

3.8

1025

43

3.3

43

3.4

43

3.5

43

3.6

1050

44

3.6

43

3.2

43

3.4

43

3.5

1075

44

3.4

44

3.5

43

3.2

43

3.3

1100

44

3.3

44

3.4

44

3.5

43

3.2

U.S.A.

 2001 to

3000 (610

to 914)

 

800

42

3.4

42

3.5

42

3.6

42

3.7

825

42

3.2

42

3.3

42

3.4

42

3.5

850

43

3.7

43

3.8

42

3.2

42

3.3

875

43

3.5

43

3.6

43

3.7

43

3.8

900

43

3.3

43

3.4

43

3.5

43

3.6

925

43

3.1

43

3.2

43

3.3

43

3.4

950

43

2.9

43

3.0

43

3.1

43

3.2

975

43

2.8

43

2.9

43

3.0

43

3.1

1000

43

2.6

43

2.7

43

2.8

43

2.9

U.S.A.

3001 to

4000

(914 to

1219)

775

42

3.2

42

3.3

42

3.4

42

3.5

800

43

3.6

43

3.8

42

3.2

42

3.3

825

43

3.4

43

3.5

43

3.7

43

3.8

850

43

3.2

43

3.3

43

3.4

43

3.6

875

43

3.0

43

3.1

43

3.3

43

3.4

900

43

2.9

43

3.0

43

3.1

43

3.2

925

43

2.7

43

2.8

43

2.9

43

3.0

950

43

2.6

43

2.7

43

2.8

43

2.8

U.S.A.

4001 to

5000

(1219 to

1524)

750

43

3.6

43

3.8

42

3.2

42

3.3

775

43

3.4

43

3.5

43

3.6

43

3.8

800

43

3.2

43

3.3

43

3.4

43

3.5

825

43

3.0

43

3.1

43

3.2

43

3.3

850

43

2.8

43

2.9

43

3.0

43

3.1

875

43

2.7

43

2.8

43

2.9

43

2.9

900

43

2.5

43

2.6

43

2.7

43

2.8

925

43

2.4

43

2.5

43

2.6

43

2.6

* Orifice number 43 is factory installed.

Summary of Contents for KGBPN42011SP

Page 1: ...n perform basic maintenance functions such as cleaning and replacing air filters Trained service personnel must perform all other operations When working on heating equipment observe precautions in th...

Page 2: ...ZW037 1 VALVE CVRSN KIT W R SPRING 92 0935 323267 701 1 PARTS ASSY 42 323267 702 1 PARTS ASSY 43 323267 703 1 PARTS ASSY 44 323267 704 1 PARTS ASSY 45 339851 701 1 LABEL KIT 339851 702 1 LABEL KIT 319...

Page 3: ...in yearly specific gravity average for local gas supply 3 Find installation altitude in Table 3 For Canada altitudes of 2000 to 4500 ft use U S A Altitudes of 2001 to 3000 ft in Table 3 4 Find closest...

Page 4: ...43 3 7 43 3 8 42 3 2 850 44 3 8 43 3 5 43 3 6 43 3 7 875 44 3 6 44 3 7 43 3 4 43 3 5 4000 900 44 3 4 44 3 5 44 3 7 44 3 8 1219 925 44 3 2 44 3 4 44 3 5 44 3 6 950 44 3 1 44 3 2 44 3 3 44 3 4 750 42 3...

Page 5: ...625 43 3 7 42 3 2 42 3 3 42 3 4 650 43 3 5 43 3 6 43 3 7 43 3 8 675 44 3 7 44 3 8 43 3 4 43 3 5 10000 700 44 3 4 44 3 5 44 3 7 44 3 8 3048 725 44 3 2 44 3 3 44 3 4 44 3 5 Orifice numbers shown in BOLD...

Page 6: ...stment screw 5 Remove the Propane regulator spring white 6 Install the natural gas regulator spring silver 7 Install the regulator adjustment screw 8 Turn the adjusting screw clockwise in 8 5 full tur...

Page 7: ...its splice connection with the yellow wire of the furnace wire harness Disconnect and discard this orange wire and the splice connection c Connect the yellow wire of the furnace wire harness see b abo...

Page 8: ...3 For Canada altitudes of 2000 to 4500 ft use U S A Altitudes of 2001 to 3000 ft in Table 3 4 Find closest natural gas heat value and specific gravity in Table 3 5 Follow heat value line and specific...

Page 9: ...tion instructions Figure 12 Conversion Rating Plate Label A13070 LABEL APPLICATION 1 Fill in Conversion Responsibility Label 339851 205 and apply over Propane Conversion Responsibility Label Date name...

Page 10: ...amage Improper installation adjustment alteration service maintenance or use can cause carbon monoxide poisoning explosion fire electrical shock or other conditions which could result in personal inju...

Page 11: ...fore installing modifying or servicing system main electrical disconnect switch must be in the OFF position and install a lockout tag There may be more than one disconnect switch Lock out and tag swit...

Page 12: ...er burner Low NOx models in downflow or horizontal positions must use Table 6 21 000 Btuh per burner See input listed on rating plate Use Table 5 22 000 Btuh per burner for models 58DLA 58PHA 58PHB 58...

Page 13: ...44 3 4 44 3 5 43 3 2 U S A 2001 to 3000 610 to 914 800 42 3 4 42 3 5 42 3 6 42 3 7 825 42 3 2 42 3 3 42 3 4 42 3 5 850 43 3 7 43 3 8 42 3 2 42 3 3 875 43 3 5 43 3 6 43 3 7 43 3 8 900 43 3 3 43 3 4 43...

Page 14: ...25 43 2 9 43 3 0 43 3 1 43 3 2 750 43 2 7 43 2 8 43 2 9 43 3 0 775 43 2 6 43 2 7 43 2 7 43 2 8 800 43 2 4 43 2 5 43 2 6 43 2 7 825 43 2 3 43 2 3 43 2 4 43 2 5 850 43 2 1 43 2 2 43 2 3 43 2 4 U S A 700...

Page 15: ...4 43 3 5 900 43 3 0 43 3 1 43 3 2 43 3 3 925 43 2 8 43 2 9 43 3 0 43 3 1 950 43 2 7 43 2 8 43 2 9 43 2 9 975 43 2 5 43 2 6 43 2 7 43 2 8 1000 43 2 4 43 2 5 43 2 6 43 2 7 U S A 3001 to 4000 914 to 1219...

Page 16: ...8 43 2 9 650 43 2 5 43 2 5 43 2 6 43 2 7 675 43 2 3 43 2 4 43 2 4 43 2 5 700 43 2 1 43 2 2 43 2 3 43 2 3 725 48 3 7 43 2 0 43 2 1 43 2 2 750 48 3 5 48 3 6 48 3 7 43 2 0 U S A 9001 to 10 000 2743 to 3...

Page 17: ...itch Lock out and tag switch with a suitable warning label Verify proper operation after servicing For J and G valves See Figure 24 1 Be sure gas and electrical supplies to furnace are off 2 Remove ca...

Page 18: ...re than one disconnect switch Lock out and tag switch with a suitable warning label Verify proper operation after servicing 1 Be sure main gas and electric supplies to furnace are off 2 Remove Low Gas...

Page 19: ...ressure tap on gas valve 2 Turn on furnace power supply 3 Turn gas supply manual shutoff valve to ON position 4 Turn furnace gas valve switch to ON position 5 Jumper R W thermostat connections on cont...

Page 20: ...ition 7 Jumper R and W thermostat connections to call for heat See Figure 13 8 Check manifold orifices for gas leaks when main burners ignite 9 Adjust gas manifold pressure Refer to Table 5 or Table 6...

Reviews: