background image

9

„

EVAPORATOR COMPARTMENT

 (Interior top area) 

— All serviceable parts are directly accessible from the 

top of the cartridge compartment. 

„

COMPRESSOR COMPARTMENT

 (Bottom rear 

area) — Access to compressor compartment requires 

removal of the side panel of the cartridge. Condenser 

fan access also requires removal of a side panel. Side 

panels are secured with 5 Phillips screws. After tubing 

and electrical connections are removed, compressor 

replacement requires removal of four clips securing 

compressor to the base.

„

EVACUATION

 — Moisture in a refrigeration system 

may affect performance.
When large amounts of moisture are present, system 

freeze ups will occur. Even in minute amounts, mois-

ture will combine with refrigerants to form an acid.  

The corrosive action of this acid forms sludge, which 

will plug the lines and drier.
Since most field type vacuum pumps cannot pull a low 

enough vacuum to remove all moisture from the sys-

tem, it is recommended that the system be triple evac-

uated, breaking each time with dry refrigerant 

nitrogen. Use care to purge air from the charging hose 

when breaking the vacuum.

„

CHARGING REFRIGERATION SYSTEM

 — Refer to 

Table 2 for refrigerant type and amount of charge.   

Since capillary tube systems have small critical refrig-

erant charges, it is recommended that a field charge 

either be weighed in or transferred from a portable 

charging cylinder. After maximum vacuum has been 

obtained as detailed above, attach charging cylinder to 

the system line making sure to purge air from hose 

with refrigerant. With the unit running, allow refrig-

erant to run slowly into the system until the desired 

charge is reached. When using refrigerant blends it is 

recommended to charge into the high side of the sys-

tem with the initial charge and then add any remain-

ing charge into the suction side; however, care must

be taken to meter the remaining amount into the

low side so that excess liquid does not enter the

compressor.

„

TROUBLESHOOTING

 — Refer to Table 3 and

Figures 10-12.

Before servicing unit, disconnect electrical service. 

On sizes 1100L and 1300L, turn disconnect switch 

(located on power cord) to the OFF position. Failure 

to disconnect electrical service could result in elec-

trical shock and cause personal injury or death.

Summary of Contents for Miracool 1300L

Page 1: ...hout notice and without incurring obligations Printed in Mexico 6 06 79BC560002 01_C OWNER S MANUAL MIRACOOL GLASS DOOR MERCHANDISER 260L 1300L 300L 750L 1300L a79 13 a79 14 a79 15 Sales Office P O Bo...

Page 2: ...ll accessories and components including legs casters and shelves File a claim immediately with the shipping company if shipment is damaged or incomplete INSTALLATION LOCATE UNIT Refer to Figure 1 for...

Page 3: ...PER LEFT CORNER FLUORESCENT LAMP SIGNBOARD SIZES 750L 1100L AND 1300L ONLY WOOD SKID RETAINING SCREW IF USED HEX HEAD BOLT SCREW POWER CORD LEFT CONNECTOR LIGHTING CORD RIGHT CONNECTOR CARTRIDGE COMPA...

Page 4: ...ree Use caution to ensure that power and electrical cords do not get pinched between the cartridge and cabinet while removing cartridge TO LEVEL UNIT The door is equipped with gravity assisted cams an...

Page 5: ...retaining tab on the shelf clip captures the shelf as shown in Figure 6 7 Before loading the shelf ensure that the shelf is resting on each of 4 clips and that the clips are installed as shown in Figu...

Page 6: ...he lamp holder Refer to Figure 7 On units with safety shields the identification mark cannot be seen See Figure 8 Verify manually that the lamp has been rotated and locked into place Improperly instal...

Page 7: ...igher setting Adjust tempera ture control in small increments one position at a time NOTE For operation above 3 000 ft altitude ther mostat should be adjusted by a qualified service technician Before...

Page 8: ...r disconnecting the unit from the power supply remove the grille retaining screw located in the upper most part of the grille See Figure 1 2 Lift the grille up and away from the unit 3 Unplug the powe...

Page 9: ...itrogen Use care to purge air from the charging hose when breaking the vacuum CHARGING REFRIGERATION SYSTEM Refer to Table 2 for refrigerant type and amount of charge Since capillary tube systems have...

Page 10: ...lace 5 Excessive discharge pressure 5 Check ventilation restrictions in cooling medium restrictions in refrigeration system 6 Compressor too hot return gas hot 6 Check refrigerant charge fix leak if n...

Page 11: ...11 FIGURE 10 WIRING DIAGRAM SIZES 260L 300L a79 10...

Page 12: ...12 a79 12 FIGURE 11 WIRING DIAGRAM SIZE 750L...

Page 13: ...13 FIGURE 12 WIRING DIAGRAM SIZES 1100L 1300L a79 11...

Page 14: ...can be used to remove debris CABINET EXTERIOR Cabinets should be cleaned with a solution of mild soap and water or mild household cleaner Do not use caustic soap or abrasive cleaners since these might...

Page 15: ...Sponge with cloth then rinse with clear water and wipe dry Satisfactory for use on all finishes Stubborn Spots and Stains Caked on Splatter and other Light Discolorations Revere Ware Goddard s Twinkl...

Page 16: ...2006 Carrier Corporation Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Printed in Mexico 6 06 79BC560...

Reviews: