Figure 24 Evaporator Fan Rotation
c. Check the VFD fan by placing a piece of paper over the fan
grille to verify it pulls in. Refer to
.
Figure 25 VFD Fan Rotation
36. Enter a DataCORDER Trip Start. Refer to
a. By entering a trip start first, all test data will be included as
part of the maintenance record.
b. Press the ALT MODE key. When the left display shows "dC",
press the ENTER key.
c. Use the Arrow keys to scroll to Code dC30.
d. Press and hold the ENTER key for five seconds.
e. The "Trip Start" event will be entered in the DataCORDER.
Figure 26 Trip Start