6
Figure 6: Thermostat wiring, heating and air conditioning
with ECM variable speed motor
Figure 7: Thermostat wiring, heating and air
conditioning/heat pump with ECM variable speed motor
Note: On units with 2 stage cooling or heat pump, terminal Y1
must be used. When Y1 on the electronic control receives a 24
VAC signal, the air flow is reduced by 20%. Do not use
terminal Y1 with a single stage cooling or heat pump.
2.5 INSTALLATION
OF
THE
BURNER
Refer to the burner manufacturer’s instructions. Also, the
burner must be installed always in the same way
independently of the furnace orientation.
1. Position the mounting gasket between the mounting
flange and the burner mounting plate. Align the holes in
the burner mounting plate with the studs on the mounting
flange and bolt securely in place.
2. Remove the burner drawer assembly or the air tube
assembly;
3. Install the nozzle (refer to Technical Specifications,
(Table 6);
4. Check the electrode settings;
5. Make the electrical connections;
6. Complete oil line connections.
2.5.1 Nozzles
The burner comes equipped with an appropriate nozzle.
However, if another size or a replacement nozzle is
required, use the manufacturer’s recommended spray
angle and type a shown in Table 1 and based on a pump
pressure of 100 psi.
Always select nozzle sizes by working back from the
desired flow rate at operating pressure and not the nozzle
marking.
2.5.2 Air and Turbulator Settings
Before starting the burner for the first time, adjust the air
and turbulator settings to those listed in this manual, Table
6. Once the burner becomes operational, final
adjustments will be required. Refer to section 3 of this
manual.
2.5.3 Post purge delay adjustment
The post purge delay on the oil-fired burners is factory set
to zero second. This delay is applicable for all installations
with chimney venting. For heating units installed with side
wall venting and a burner equipped with this feature, the
post purge delay must be set to 15 seconds. No delay is
required for Riello burners. Refer to the burner control
instruction manual and markings for proper adjustment of
the post purge delay.
2.6 VENTING
WARNING
Poisonous carbon monoxide gas, fire and explosion
hazard.
Read and follow all instructions in this section.
Failure to properly vent this furnace can result in in
death, bodily injury and/or property damage.
To ensure the safe and proper functioning of an oil
furnace, it must always be connected to a flue with
sufficient draft or to an approved side-wall venting system.
In addition, it is strongly recommended to perform a
complete inspection of all the existing venting systems.
WARNING
Poisonous carbon monoxide gas hazard.
Never install a hand operated damper in the vent pipe.
However, any Underwriters Laboratories listed,
electrically operated automatic type vent damper may
be installed if desired. Be sure to follow the
instructions provided with vent damper. Also, read
and follow all instructions in this section of the
manual.
Failure to properly vent this furnace or other
appliances can result in death, bodily injury and/or
property damage.
Summary of Contents for OBM112 Series
Page 17: ...17 Figure 9 Furnace Dimensions ...
Page 18: ...18 Figure 10 Wiring Diagram 4 Speed Motor PSC ...
Page 19: ...19 Figure 11 Wiring Diagram Variable Speed Motor ECM ...
Page 20: ...Figure 12 Parts list with 4 speed motor PSC 20 B50091C ...
Page 22: ...22 Figure 13 Parts list with variable speed motor ECM B50092C ...
Page 24: ......
Page 42: ...Figure 9 Dimensions de la fournaise 18 ...
Page 43: ...19 Figure 10 Diagramme électrique avec moteur 4 vitesses PSC ...
Page 44: ...20 Figure 11 Diagramme électrique avec moteur vitesse variable ECM ...
Page 45: ...Figure 12 Liste de pièces avec moteur 4 vitesses PSC 21 B50091C 21 B50091C ...
Page 47: ...23 B50092C 23 B50092C Figure 13 Liste de pièces avec moteur vitesse variable ECM B50092C ...