Free Cooling Temperature Delta
NOTE
: This menu is not available for heat recovery (HRV) or energy recovery
ventilator (ERV) types.
When Free Cooling is enabled, the minimum temperature delta will put a lower
limit on engaging Free Cooling based on the difference between the indoor
temperature and the cool to setpoint. If the different between the indoor
temperature and setpoint is less than this setting then Free Cooling will not be
engaged.
Default:
2°F
Options:
1, 2, 3, 4, …, 9, 10°F