55 |
P a g e
Heating Fan Optimization (Blower Off Delay)
NOTE
: For non-heat pump applications this setting is found in the Heating
Configuration menu.
Once a heating cycle ends the fan will continue to run for this time period. This is
also known as the blower off delay, for heating. The longer the time, the more heat
is pulled out of the heat exchanger but the cooler the temperature is at the end of the
cycle. The actual blower off delay will always be the longest of the equipment
setting or the thermostat setting.
Default:
0 seconds
Options:
Between 0 and 900 seconds
On Thermostat:
Select Menu > (hold) Service > Installation Settings > Thresholds >
Compressor Configurations > Heating Fan Optimization
Summary of Contents for TP-WEM01
Page 38: ...38 P a g e ...
Page 50: ...50 P a g e ...