69 |
P a g e
Heat Configuration (Furnace)
The settings in this menu set will manage the thresholds for your heating terminals
W1 and W2 on a heating system that has a furnace.
Heat Differential Temperature (Furnace)
The minimum difference between the indoor temperature and the heating
setpoint before the system will turn on in an occupied comfort profile (e.g. Home,
Wake, Sleep). A setpoint of 70
o
F with a heating differential temperature setting of
0.5
o
F degrees, will energize heating at 69.5
o
F. As part of the energy savings
algorithms, this differential temperature setting is relaxed by 1
o
F for unoccupied
comfort profiles (Away). In the example above, if the thermostat is in the away
mode, then the system will delay energizing heating until the indoor temperature
reaches 69
o
F.
Default:
0.5
o
F
Options:
Between 0.5
o
F and 3.0
o
F
On Thermostat:
Select Menu > (hold) Service > Installation Settings > Operating
Thresholds > Heat Configuration > Heating Differential Temperature
Summary of Contents for TP-WEM01
Page 38: ...38 P a g e ...
Page 50: ...50 P a g e ...