4.10 Controller Function Codes
CnF45
Low Humidity Enabled
Out
In
CnF46
Quench/liquid Injection Valve Type
nO=0=no
nC=1=nc
CnF47
Vent Position
OFF
UP, LOW, CUStOM
CnF49
OEM Reset Option
OFF
0-off,1-std, 2-spec, 3-cust
CnF50
Enhanced Bulb Mode Interface
0
0-out, 1-in
CnF51
Timed Defrost Disable
0
0-out, 1-in
CnF52
Oil Return Algorithm
0
0-out, 1-in
CnF53
Water Cool Oil Return Logic
0
0-out, 1-in
CnF55
TXV Boost Relay
0
0-out, 1-in
CnF56
TXV Boost Circuit
0
0-out, 1-in
CnF57
PWM Compressor Control
0
0-out, 1-in
CnF59
Electronic Evaporator Expansion Valve
0
0-out, 1-EC, 2-KE, 3-NA
CnF61
ACT ASC Control Enable
0
0-out, 1-in
CnF62
Extended Temperature Control Enable
0
0-out, 1-in
CnF63
CCPC Pre-trip/Tripstart Default State
0
0-on, 1-off
CnF64
Enable Fan Pulsing Logic
0
0-in, 1-out
CnF66
High Speed Evaporator Fan Option
0
0-off, 1-on
CnF67
Air Heaters
0
0-out, 1-in
Table 4–5 Controller Function Codes
Code
Title
Description
Note: If the function is not applicable, the display will read “-----”
Display Only Functions
- Cd01 through Cd26 are display only functions.
Cd01
Digital Unloader
Valve Closed (%)
Displays the DUV percent closed. The right display reads 100% when the valve
is fully closed. The valve will usually be at 10% on start up of the unit except in
very high ambient temperatures.
Cd03
Compressor Motor
Current
The current sensor measures current draw in lines L1 & L2 by all of the high volt
-
age components. It also measures current draw in compressor motor leg T3. The
compressor leg T3 current is displayed.
Cd04
Cd05
Cd06
Line Current,
Phase A
Line Current,
Phase B
Line Current,
Phase C
The current sensor measures current on two legs. The third unmeasured leg is
calculated based on a current algorithm. The current measured is used for con
-
trol and diagnostic purposes. For control processing, the highest of the Phase A
and B current values is used for current limiting purposes. For diagnostic pro
-
cessing, the current draws are used to monitor component energization.When
-
ever a heater or a motor is turned ON or OFF, the current draw increase/
reduction for that activity is measured. The current draw is then tested to deter
-
mine if it falls within the expected range of values for the component. Failure of
this test will result in a Pre-trip failure or a control alarm indication.
Cd07
Main Power Voltage
The main supply voltage is displayed.
Table 4–4 Controller Configuration Variables
Config
Title
Default
Option