4–41
T-340
AL25
Condenser IP
Condenser fan motor
internal protector (IP) is
open.
Insufficient Air
Flow
Shut down unit and
check condenser fan for
obstructions.
Remove obstructions.
Condenser Fan
Motor
Shut down unit, discon
-
nect power, & check
Condenser Fan Motor IP
at plug connection pins 1
& 2.
Replace defective con
-
denser fan motor, refer
to Condenser Fan Motor
.
AL26
All Sensors Fail
-
ure:
Supply/Return
Probes
Sensors out of range. All sensors de
-
tected as out of
range
Perform Pre-trip P5:
If P5 passes, no further
action is required.
If P5 fails, replace the
defective sensor as de
-
termined by P5, refer to
TEMPERATURE SEN
-
SOR Service
AL27
Analog to Digital
Accuracy Fail
-
ure
Controller AD convert
-
er faulty.
Controller
Power cycle the unit. If
the alarm persists, it indi
-
cates a defective micro
-
processor.
Replace defective micro
-
processor, refer to Con
-
troller Service
AL28
Low Suction
Pressure
Suction pressure too
low for normal opera
-
tion.
N/A
Power cycle the unit.
Resetting the unit may
correct problem, monitor
the unit.
Suction Pressure
Transducer (SPT)
Confirm accurate SPT
pressure readings, refer
to MANIFOLD GAUGE
.
Replace SPT if defec
-
tive.
Discharge Pres
-
sure Transducer
(DPT)
Confirm accurate DPT
pressure readings, refer
to MANIFOLD GAUGE
.
Replace DPT if defec
-
tive.
AL29
AutoFresh
Failure
Alarm 29 is triggered if
CO
2
or O
2
level is out
-
side of the limit range
and the vent position is
at 100% for longer than
90 minutes.
Alarm LED will be
activated and user
intervention is re
-
quired.
Refer to eAutoFresh
manual.
The alarm is triggered off
when atmospheric con
-
ditions are within limit
settings.
AL50
Air Vent Position
Sensor (VPS)
VPS Sensor out of
range.
Vent Position
Sensor (VPS)
Make sure VPS is se
-
cure.
Manually tighten panel.
If the alarm persists, re
-
place the sensor or the
assembly.
Replace VPS.
AL51
EEPROM Fail
-
ure
Controller Memory
Failure
Controller
Pressing the ENTER key
when “CLEAr” is dis
-
played will result in an at
-
tempt to clear the alarm.
If action is successful (all
alarms are inactive),
alarm 51 will be reset.
Power cycle the unit. If
the alarm persists, it indi
-
cates defective controller
memory.
Replace defective con
-
troller, refer to Controller
Service
.
Table 4–6 Controller Alarm Indications
Alarm Code
Cause
Components
Troubleshooting
Corrective Actions