Wiring inputs and outputs 

 

 

 

 
 

TruVu™ UC683T

 

 

CARRIER CORPORATION ©2021   

Installation and Start-up Guide 

 

All rights reserved 

 

26 

 

 If you are using the UO, set the universal output's DIP switch to Binary or Analog for the type of device wired 

to the output.  

  

 

WARNINGS

  

 

The universal output is set to Binary in the factory. To avoid damage to the controller, use a voltmeter to 
verify there is no voltage on the UO-01 (+) and Common  (

) terminals before setting the DIP switch to 

Analog.   

 

 Do not apply voltage to the universal output if the DIP switch is set to Analog. 

Connect binary and analog output wiring to the screw terminals on the TV-UC683T and to the controlled 

device. 

Connect the ground wire to the AO outputs' terminals. 

 

 

 

 

 

Summary of Contents for TruVu UC683T

Page 1: ...T Tr ru uV Vu u U UC C6 68 83 3T T I In ns st ta al ll la at ti io on n a an nd d S St ta ar rt t u up p G Gu ui id de e Carrier 2021 Catalog No 11 808 852 01 12 3 2021...

Page 2: ...version of this document from www hvacpartners com the Carrier Partner Community website or your local Carrier office Important changes are listed in Document revision history at the end of this docu...

Page 3: ...vice 17 Wiring devices to the TV UC683T s Rnet port 18 Wiring devices to the TV UC683T s Act Net port 19 Wiring inputs and outputs 21 Inputs 21 Outputs 22 Wiring specifications 23 To wire inputs and o...

Page 4: ...ubleshooting 56 LEDs 56 To configure custom Prog LED 59 To get a Module Status report 59 Troubleshooting inputs and outputs 60 To get a Device Log 61 To get the TV UC683T s serial number 62 To replace...

Page 5: ...troubleshooting Has network statistics that can be viewed numerically or as trend graphs Supports BACnet MS TP Supports Rnet devices Supports Act Net devices Works with the i Vu v7 0 or later system...

Page 6: ...sensors an Equipment Touch an TruVu ET Display and Wireless Adapter for wireless sensors Service USB port for connecting locally to controller setup pages the TruVu ET Display or the Carrier wireless...

Page 7: ...ce the power supplied by the Rnet port NOTE If the total power required by the sensors on the Rnet exceeds the power supplied by the Rnet port use an external power source The Wireless Adapter Equipme...

Page 8: ...er off in order for the change to be saved Real time clock Real time clock keeps track of time in the event of a power failure for up to 3 days Protection A single fast acting 5mm x 20mm glass fuse fo...

Page 9: ...BBMD Standard Device Profiles as defined in ANSI ASHRAE Standard 135 2012 BACnet Annex L Protocol Revision 14 Compliance United States of America FCC CFR Part 15 Class B Canada Industry Canada Complia...

Page 10: ...ment Touch or TruVu ET Display to the TV UC683T s Rnet port to view or change the controller s property values schedule equipment view trends and alarms and more without having to access the system s...

Page 11: ...ler toward the DIN rail until you hear it click and the spring loaded latch secures the controller to the DIN rail Screw Mount Leave about 2 in 5 cm on each side of the controller for wiring Pull the...

Page 12: ...w terminal connector from the controller s power terminals labeled 24V 3 Connect the power supply s wires to the red screw terminal connector 4 Connect an 18 AWG or larger wire from the power supply s...

Page 13: ...h1 To connect the TV UC683T to a computer using the Carrier wireless service adapter 1 Insert the Carrier wireless service adapter part USB W into the controller s USB Service Port to communicate with...

Page 14: ...low 2 A new Ethernet connection will appear on your computer 3 If your computer uses a static IP address use the following settings for the new connection Address 169 254 1 x where x is 2 to 7 Subnet...

Page 15: ...ated on the other side of an IP router Be connected to any third party IP devices NOTE Carefully plan your addressing scheme to avoid duplicating addresses If third party devices are integrated into t...

Page 16: ...intact during power cycles MS TP For MS TP on Port S1 set up autobaud or the baud rate On the controller setup pages BACnet tab Port S1 In the i Vu interface on the navigation tree right click your TV...

Page 17: ...All button to erase the Local Devices table if there is information in it 6 Click Discover The table finds and lists the first 256 unconfigured devices on the same subnet The table is sorted by serial...

Page 18: ...fied controller enter the Address and Location optional 7 Repeat steps 3 and 4 for each controller that you want to address 8 For more details about discovering and configuring your devices see Local...

Page 19: ...TCP IP Ethernet 10 or 100 Mbps Port S1 1 BACnet MSTP Modbus Serial RS485 9 6 to 115 2 kbps Service Port 2 USB 2 0 USB Comm Port future use USB 2 0 USB Rnet Port See Wiring devices to the TV UC683T s...

Page 20: ...o the Ethernet Connect an Ethernet cable from the building BAS system or another TV UC683T controller to the Eth0 Ethernet port If necessary connect another Ethernet cable from the Eth1 port to the ne...

Page 21: ...a network segment set the port s End of Net switch to Yes NOTE The controller s End of Net switch applies network termination and bias If the controller is at the end of a network segment that includ...

Page 22: ...t port in a daisy chain configuration ZS sensors Wireless Adapter that communicates with wireless sensors Equipment Touch TruVu ET Display See the device s Installation and Start up Guide for complete...

Page 23: ...available for Act Net devices AC supply 25 VA 1 A DC supply 15W 0 625A Use an external transformer if your devices exceed the maximum power CAUTIONS If the power source for the Act Net devices require...

Page 24: ...the Act Net port terminals on the controller to the matching terminal on the supported device They may not be in the same order See example below The TV UC683T supports Act Net communication to the A...

Page 25: ...is open Maximum closed contact resistance is 1kOhms 0 5 Vdc 0 10 Vdc The input impedance of the TV UC683T is approximately 120 kOhm when configured as a voltage input Pulse counter 2 Pulse counting up...

Page 26: ...y can switch up to 3 75 A 30 Vac Vdc The total power and current that can be switched by a bank of 3 relays cannot exceed the Class 2 limits of 100 VA or 4 2 A Universal output The TV UC683T s univers...

Page 27: ...5 meters 26 AWG Shielded Pulse counter TLO 1000 feet 305 meters 22 AWG Shielded Output wiring To size output wiring consider the following Total loop distance from the controller to the controlled dev...

Page 28: ...tart up Guide All rights reserved 24 To wire inputs and outputs WARNING Do not apply line voltage mains voltage to the controller s ports and terminals The Gnd terminal is shared by the inputs outputs...

Page 29: ...the TV UC683T s power and communications connections work properly 2 Turn off the TV UC683T s power 3 Connect the input wiring to the screw terminals on the TV UC683T NOTE Connect the shield wire to t...

Page 30: ...S The universal output is set to Binary in the factory To avoid damage to the controller use a voltmeter to verify there is no voltage on the UO 01 and Common terminals before setting the DIP switch t...

Page 31: ...and Start up Guide All rights reserved 27 7 Turn on the TV UC683T s power See Troubleshooting inputs and outputs page 60 NOTE You can install connector covers sold separately part PLM KIT by snapping...

Page 32: ...pe 1 in the Num field for Pump S S NOTES Exp expander number is 00 for the inputs and outputs located on the TV UC683T Do not assign the same output number to more than one point 4 Enter the appropria...

Page 33: ...0 10 Volt Linear w Offset 2 10 Volts Engineering values associated with 2 Vdc Min and 10 Vdc Max 1 Thermistor Thermistor Select your Thermistor type or set up and select a Non Linear Custom Table 2 N...

Page 34: ...dc Max No Translation N A The Analog Output microblock will output the same value that comes in to the microblock 2 10 Vdc Electrical 0 10 Volt Linear w Offset 2 10 Volts Engineering values associated...

Page 35: ...outputs differently To set these values appropriately you should understand how the driver uses them Offset Polarity Notes Analog Input BAI Offset value positive or negative adds a fine adjustment to...

Page 36: ...outers are found select one or more routers in the list on the Manage tab and click Upload All Content to upload to the i Vu application Use Ctrl click Shift click or both to select multiple items 4 C...

Page 37: ...ime Synch Sensitivity seconds When the controller receives a time sync request if the difference between the controller s time and the time sync s time is greater than this field s value the controlle...

Page 38: ...o if the object s value updates excessively for 30 seconds an alarm is sent to the i Vu application listing all objects that are updating excessively A Return to normal alarm is sent only after all ob...

Page 39: ...sponse is received APDU Segment Timeout How many milliseconds the device will wait before resending a message segment if no response is received Number of APDU Retries The number of times the device w...

Page 40: ...Name that appears in the Recipients table Recipient Type Use Address static binding for either of the following Third party BACnet device recipients that do not support dynamic binding When you want...

Page 41: ...r Generated Alarm Description Short message shown on the i Vu Alarms page or in an alarm action when this type of alarm is generated Events Alarm Category and Alarm Template See Setting up an alarm so...

Page 42: ...ory and Alarm Template See Alarms in i Vu Help Enable Clear these checkboxes to disable Alarm or Return to normal messages of this type from this controller Notification Class Do not change this field...

Page 43: ...ys the state of the End of Net termination switch for Port S1 IP Configuration Allow setup of IP addressing through an external tool When this field is enabled you can set up IP addressing through a t...

Page 44: ...in the Network Activity tab Eth0 Eth1 Port Statistics BACnet IP Statistics BACnet IP Rx Unicast Packets BACnet IP packets received from a single BACnet device BACnet IP Tx Unicast Packets BACnet IP pa...

Page 45: ...e file The capture will automatically resume Click on the Start Stop option to end the Continuous capture If the port is set up for MS TP select an option in the Capture section To download the captur...

Page 46: ...Net device This number is printed on a label on the device Device Status Displays the current status of the device Possible statuses Description Normal Operation Successful communication No Communica...

Page 47: ...ble click Accept after every change Unknown Error Firmware or bus error Auto addressed device When a device that does not have an address is found on the bus an unused address in automatically assigne...

Page 48: ...mains OFF as long as write requests are received but switches to ON if the controller does not receive a request within the specified time The binary input must have the Expander number and Input numb...

Page 49: ...delete all samples currently stored in the controller Stop When Full Check this field to stop trend sampling when the maximum number of samples is reached Enable trend log at specific times only Coll...

Page 50: ...To communicate through a BACnet Service port network page 46 To access the controller setup pages and use the Local Network tab you must first connect to and manually address one TV UC683T For instruc...

Page 51: ...n for the device in the i Vu interface Device Description You can enter an intuitive description for the device in the i Vu interface Configuration APDU Timeout How many milliseconds the device will w...

Page 52: ...Configuration BACnet tab NOTE The TV UC683T can be configured for only one BACnet communication type On the BACnet tab you can choose to run BACnet Over IP or BACnet Over Ethernet on the Eth0 and Eth...

Page 53: ...UC683T controller or by using the i Vu application In the i Vu navigation tree right click the TV UC683T select Driver Properties and go to Driver Settings tab Local Network Configuration Check Allow...

Page 54: ...To change the Mode 1 Select the devices you want to change 2 Select one of the following IP addressing modes Default IP Devices with rotary switches that are used when autogenerating the address if a...

Page 55: ...g the DSC button immediately adds it to the table and displays a blue dot TIP You can build a table of devices in the order that you ve pressed the DSC buttons Clear the table and then press each DSC...

Page 56: ...lable you will have to assign a network number and enter it 5 Click Apply 6 On the right of the page in the Networks using selected connection table click the checkbox next to the network you want to...

Page 57: ...ected connection table click the checkbox next to the network you want to connect to 15 Click Apply 16 Select the BACnet IP Service Port Connection and click Start The status changes to Connected 17 C...

Page 58: ...nce between the controller s ground and the computer s AC power ground could damage the USB Link and the controller If you are not sure of the wiring polarity use a USB isolator between the computer a...

Page 59: ...rt Control Panel System Device Manager Ports Com LPT The COM port number is beside Silicon Labs CP210x USB to UART Bridge 6 Set the Baud rate to 115200 7 Click Apply 8 On the right of the page in the...

Page 60: ...ruVu UC683T CARRIER CORPORATION 2021 Installation and Start up Guide All rights reserved 56 If you have problems mounting wiring or addressing the TV UC683T contact Carrier Control Systems Support LED...

Page 61: ...TP Change MAC address to unique address using USB Service Port Blue 2 blink Controller has same MAC address as another connected device Duplicate address on MSTP Change MAC address to a unique value u...

Page 62: ...red Green 2 blink Download of driver is in progress Download in progress No action required Green 3 blink BACnet Device ID is not set Download required Download the controller Green Fast blink Install...

Page 63: ...e Present Value The pulse pattern repeats after a 2 second delay LED will blink the number of times given in the BAO with ON pulse 0 5 seconds and OFF pulse 0 5 seconds To get a Module Status report A...

Page 64: ...igured microblock A misconfiguration on the expander A missing or disconnected expander To check for errors 1 In the i Vu navigation tree select the equipment controlled by the 2 On the Properties pag...

Page 65: ...in Max limits No Output Output s Hand Auto Off switch is in Hand or Off position The expander s Hand Auto Off switch is in the Auto position No Sensor No device is attached to the output The device is...

Page 66: ...inside circuit board See To get a Module Status report page 59 To replace the TV UC683T s fuse The TV UC683T has one fuse If the TV UC683T s power LED is not lit this could be due to a blown power fu...

Page 67: ...ace the power connector 8 Verify the LEDs on the TV UC683T are lit To revert to default settings WARNING This erases all archived information and user configuration settings When recovery is complete...

Page 68: ...ubleshooting or start up you can prevent the i Vu application from communicating with the TV UC683T by shutting down communication from the TV UC683T to the i Vu application When Out of Service i Vu n...

Page 69: ...dio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which...

Page 70: ...nd versions Reset Counters The number of times each of the following events have occurred since the last time the controller was commanded to clear the reset counters See NOTE below this table Power f...

Page 71: ...n 6 MB maximum contains data that does not need to be preserved through a power cycle such as status values that are calculated during runtime IP Networks BBMDs Shows the following information for eac...

Page 72: ...ough the BACnet Service Port network Wiring specifications Changed warning for minimum bend radius X TS BB O BM Wiring devices to the TV UC683T Rnet Port Changed Rnet rate of communication from 115 kb...

Page 73: ......

Page 74: ...Carrier 2021 Catalog No 11 808 852 01 12 3 2021...

Reviews: