Wiring devices to the TV-UC683T's Act Net port
TruVu™ UC683T
CARRIER CORPORATION ©2021
Installation and Start-up Guide
All rights reserved
19
Supports a combination of up to 5 Act Net addresses, as follows:
•
Address
1
is reserved for the Carrier actuator
•
Address
2
and
3
are reserved for the VAV Zone II Secondary Duct
•
Address
4
and
5
for i-Vu® Smart Valves
Maximum power available for Act Net devices:
•
AC supply - 25 VA (1 A)
•
DC supply - 15W (0.625A)
•
Use an external transformer if your devices exceed the maximum power.
CAUTIONS
○
If the power source for the Act Net devices require a connection to earth ground, you must place it in the
same control panel as the TV-UC683T controller, so that it shares a common earth ground reference,
thereby reducing the potential for ground loops.
○
A remote Act Net power source, installed near the Act Net devices, should be floating (no local
connection to earth ground).
Wiring devices to the TV-UC683T's Act Net port
Summary of Contents for TruVu UC683T
Page 73: ......
Page 74: ...Carrier 2021 Catalog No 11 808 852 01 12 3 2021...