To adjust input and output properties
TruVu™ UC683T
CARRIER CORPORATION ©2021
Installation and Start-up Guide
All rights reserved
30
Output values
Output
I/O Type
Sensor/Actuator Type
Min/Max
Analog (BAO)
0-10 Vdc
Electrical
0
–
10 Volt
Linear Full Range
Engineering values associated with 0
Vdc (Min) and 10 Vdc (Max)
1
No Translation
N/A. The Analog Output microblock will
output the same value that comes in to
the microblock.
2-10 Vdc
Electrical
0
–
10 Volt
Linear w/Offset,
2
–
10 Volts
Engineering values associated with 2
Vdc (Min) and 10 Vdc (Max)
1
Binary (BBO)
Relay
Relay/Triac
Output
N/A
N/A
Universal (BBO or BAO)
0-10 Vdc
Electrical
0
–
10 Volt
Linear Full Range
Engineering values associated with 0
Vdc (Min) and 10 Vdc (Max)
No Translation
N/A. The Analog Output microblock will
output the same value that comes in to
the microblock.
2-10 Vdc
Electrical
0
–
10 Volt
Linear w/Offset,
2
–
10 Volts
Engineering values associated with 2
Vdc (Min) and 10 Vdc (Max)
Relay
Relay/Triac
Output
N/A
N/A
12 Vdc PWM
PWM 80 Hz
No Translation
0% (Min) and 100% (Max). The Analog
Output microblock will vary the width of
the pulse based on the value that
comes into the microblock.
1
The Analog Output microblock uses the Min and Max values to linearly translate its incoming value into a
physical output signal (Volts) sent from the TV-UC683T to a device. For example, set Min to 0 and Max to 100
for an Analog Output microblock that receives a 0 to 100% open signal from a PID microblock and that controls
a 0
–
10 Vdc actuator so that when the PID signal is 100%, the TV-UC683T output is 10 Vdc. Similarly, when the
PID signal is 50%, the TV-UC683T output is 5 Vdc.