2
ZP3 Fire Panel User Guide
Basic system features
The ZP3 system incorporates a wide range of features and capabilities, including
these:
• The ZP3 incorporates the proven ZP system of automatic contamination
adjustment for each sensor. This recalibrates each sensor as it becomes
contaminated, and provides a constant sensitivity even when sensors are
dirty.
• Each sensor is individually adjustable for sensitivity, including different
sensitivities for day and night operation.
• Selectable alarm verification allows the time integration of each sensor to be
set. Analogue sensors provide prealarm, alarm, service, and diagnostic
alarms.
• The panel continuously checks every sensor for contamination, with
automatic alarm.
• The system supports both fire and non-fire monitoring functions, e.g. door
open, fault alarms, etc.
• The ZP-loop provides for addressable loop-powered sounders, reducing
wiring.
• Each panel supports up to 50 zones, optionally 128. Built-in zone LEDs
display up to 50 zones, and extender panels provide LED display for up to
128 zones.
• Each panel has the capacity for 896 programmable inputs and outputs, which
can be located with the panel, or remotely via serial connection.
• Flash memory retains all programming and data, even if the panel is powered
down.