ZP3 Fire Panel User Guide
25
3. Record the action taken in the logbook.
4. Press the Reset button after the fault has been rectified.
The system restores to normal.
Disabling system elements
Zones, sensors, call points, sounders, control outputs, outputs, and remote
manned centre alarms can be manually disabled for maintenance or other
purposes. When disabled, the condition reports on the ZP3 panel as described in
Table 11 below. Disablement is normally carried out by maintenance personnel,
and can only be done by personnel with a level 2 access (or higher). In certain
cases, where a specific part of a system is regularly disabled at certain times (for
example, a meeting room which allows smoking), the system is sometimes set
up to allow the operator to carry out the disablement, usually with a key switch.
Table 11: Disablement - annunciation and alarm
Description
Remarks
Common Disabled LED
Illuminated.
Text display
Zone screen showing details of the affected zone.
Status indicators
Illuminated to indicate the system element that is disabled.
Types of disablement
Disablements of the system can be categorized as shown in Table 12 below.
Table 12: Disabling system elements — types of disablement
Category
Description
Devices
Disabling input devices such as zones, sensors, manual breakglass call
points, etc. Provided that the number of devices disabled is sufficiently small,
and that the relevant staff are aware of the situation and are in control, this
type of disablement is usually considered acceptable.
Sounders and
RMC
Disabling sounders or the remote manned centre alarms, This type of
disablement is considered very serious, and some authorities do not approve
of this practice. If sounders are disabled for any reason, they must be
enabled again as soon as possible.
Operator action
1. Press the Disabled button to view disabled zones.
The screen shows disabled or partly disabled zones.
2. Scroll with the Up and Down buttons to view all the disablement messages.
Status LED indicators indicate which system elements are disabled.
3. If a fire alarm occurs while sounders are disabled, press the Restore Disabled
Alarms button. This restores any disabled sounders. Continue to press this
button to toggle between Enable All Sounders and Disable All Sounders.