Communications Manual Rev 3.21
Software Versions 3.xx
003R-618-321
Page
29
8.1.1. Span
Span calibration is performed using REG_CALIBRATE_SPAN as shown in the table
below.
Type of Calibration
Parameter
Other Registers
Span Calibration using
test weights
none REG_WEIGHT_CALIBRATI
ON
Direct mV/V Span
Calibration
(mV/V * 10,000) as
hexadecimal value
REG_FULLSCALE
eg. Execute a Span calibration using a scale base of 2500 g. Assume that the
indicator has Units = g, Decimal Places = “000000”.
Command =
10
H
CMD_EXECUTE
Register Id
= 0103
H
REG_CALIBRATE_SPAN
Set span weight
20120100:9C4
REG_WEIGHT_CALIBRATION
Add test weights
Execute
20100103:
REG_CALIBRATE_SPAN
Sample Response
81100103:0000
Indicator shows “S. in P”
Check Status by reading
20040021:
Sample Response while
calibrating
81040021:00002000
Indicator is Calibrating
Sample Response when complete
81040021:00000000
Calibration finished, no errors
InternalErrorCode field = 0 showing that the calibration was successful.
eg. Execute a Direct Span calibration at 3.0 mV/V. Assume that REG_FULLSCALE
already contains 3000 decimal.
Command =
10
H
CMD_EXECUTE
Register Id
= 0103
H
REG_CALIBRATE_SPAN
Parameter Field
= 7530
H
(3.0 * 10000 = 30000 decimal)
Execute with direct mV/V
20100103:7530
REG_CALIBRATE_SPAN
Sample Response
81100103:0000
Check Status
20040021:
REG_SYSTEM_STATUS
Sample Response
81040021:00000C00
InternalErrorCode field = 0 showing that the calibration was successful.
Summary of Contents for X320
Page 1: ...IP69K Washdown Indicator Communications Manual 800 223 4227 www cas usa com U51024290 ...
Page 47: ...Communications Manual Rev 3 21 Software Versions 3 xx Page 46 003R 618 321 Notes ...
Page 48: ...Communications Manual Rev 3 21 Software Versions 3 xx 003R 618 321 Page 47 Notes ...
Page 49: ...Communications Manual Rev 3 21 Software Versions 3 xx Page 48 003R 618 321 Notes ...
Page 50: ...Notes ...