background image

This appliance must only be installed in Great Britain or Ireland.

1. This fire is a natural gas appliance and has been designed for use with the following applications:

a) 

Class I

- Conventional brick or stone chimney as used for a solid fuel fire with a cross sectional dimension of

225mm x 225mm (9” x 9”) or a lined flue with a minimum diameter of 175mm (7”), with the fireplace components
conforming to BS1251, or a builders opening a minimum of 560mm high and 406mm wide with a minimum depth
of 230mm to allow sufficient volume for debris collection. To obtain this depth it would not normally be necessary
to remove the chair brick. Any permanent flue restrictions or variable dampers are to be removed or locked in the
fully open position. The chimney should also be swept prior to installation.

b) 

Class II

- A double walled or insulated metal flue box built to the requirements of BS715 with an insulated flue

having a minimum diameter of 125mm (5”) and a minimum effective overall height of 3 metres (10’).

NOTE

: If the flue box is to be used with an existing brick or stone chimney, a 125mm (5”) minimum diameter

flue liner conforming to BS715 may be used.

2. A non-combustible hearth must be provided to comply with current building regulations. Care should be taken
to prevent any damage being caused to surrounding soft furnishings or decoration, e.g. many embossed vinyl
wall coverings may become discoloured if placed too close to the appliance.

3. A suitable proprietary fire surround with 100

0

c rating may be used with a minimum clearance from hearth to

underside of shelf of 830mm, providing that the depth of shelf is 150mm or less.

4. Where the shelf depth is greater than 150mm, the minimum height clearance should be increased by 25mm
increments for each additional 12.5mm of shelf depth.

5. Minimum width between vertical sides of combustible surround should not be less than 800mm provided the
appliance is central to the surround and the surround legs do not exceed a 150mm profile.

6. If the 150mm profile is exceeded, the width of the surround (and the back panel) should be increased by 
25mm for each additional 12.5mm of profile depth.

FLUE FLOW TEST

A flue flow test (smoke test) is carried out to check the effectiveness of the flue and to ensure that there is no
leakage into another part of the premises (including any loft), or as appropriate other adjoining premises (this is
particularly important where a number of chimneys combine into a multiple stack).
The flue flow test should be carried out using a suitable smoke pellet which the pellet manufacturer claims to
generate 5m

3

of smoke in 30 seconds burn time.

These gas fires should have the flue flow test carried out with the appliance in position but not connected to the
gas supply so that the smoke test can be carried out with representative flue flow conditions.
A warm flue will be more effective than a cold flue. If the flue is reluctant to draw, which can be initially assessed
by lighting a smoke match at the intended position of the appliance flue connection, introduce some heat into the
flue for a minimum of 10 minutes using a blow torch or other means.
Other factors, such as weather conditions and a combination of materials used to construct the flue can all
influence the flue draught. The pre-heating process may require as much as half an hour before the flue behaves
satisfactory as a blow torch does not represent the volume of heat consistent with the normal appliance
operation.

A Flue Flow Test should be checked as follows:
1. Carry out those visual checks as indicated previously, and continue only if satisfactory.
2. Establish that an adequate air supply is available for the combustion of the appliance
3. Close all doors and windows in the room that the appliance is to be installed.
4. Light a smoke pellet at the intended position for the appliance. Place the inset fire case into position.
5. The test is satisfactory if

- there is no significant escape of smoke from the appliance position.
- there is no seepage of smoke over the length of the flue.
- smoke is discharged only from the correct terminal.

VENTILATION

No special ventilation bricks or vents are required in the room containing the appliance, providing that normal
adventitious room ventilation exists. The installer must determine this by carrying out a spillage test.

SPILLAGE TEST

To check for satisfactory clearance of products of combustion, close all doors and windows and leave the fire
burning for five minutes. Insert a lit smoke match on a vertical plane 50mm down, 50mm inside the canopy
opening. All the smoke must be drawn into the flue. If spillage occurs, allow a further ten minutes and repeat the
test. 

Should the Installer detect signs of spillage after a further 10 minutes (the odd wisp may be ignored)

it may be necessary to remove the fire outlet baffles - see page 8. 

Should spillage still occur turn the

appliance off and seek expert advice.
To continue the test: If an extractor fan is situated in the room the test should be repeated with the fan running. 
If there is a connecting room with an extractor fan the test should be repeated with all the doors to that room
open and the extractor fan running.

INSTALLATION REQUIREMENTS

5

Summary of Contents for Integra Convector Plus

Page 1: ...ld be handed to the end user when the installation is complete This is an official requirement and is the responsibility of the fitter of this appliance Having installed the appliance the installer sh...

Page 2: ......

Page 3: ...6 6 Installation Procedure Decorative Cast 8 Commissioning 8 Removing the Baffles 9 Technical Data 9 Replacement Parts 9 Trouble Shooting GAS SAFE Engineer Only 10 User Instructions 11 Cleaning and Ma...

Page 4: ...ht to ensure safe operation The installer must then establish that all the products of combustion are entering the flue within five minutes of lighting from cold This can be verified by traversing the...

Page 5: ...out using a suitable smoke pellet which the pellet manufacturer claims to generate 5m3 of smoke in 30 seconds burn time These gas fires should have the flue flow test carried out with the appliance in...

Page 6: ...n the front leg and two at the rear of the tray Remove the burner tray and place to one side Fig 3 6 When the burner tray has been removed decide which side of the appliance the gas supply will be ent...

Page 7: ...2 Before making the final connection thoroughly purge the supply pipe to clear any foreign matter i e masonry dust etc as this could lead to blockages in the control valve and or pilot assemblies 3 Fi...

Page 8: ...rative frame on to the studs and secure with the two nuts provided 6 Insert the two screws into the lower holes in the decorative frame and carefully tighten ensuring the fire box is securely clamped...

Page 9: ...f VFC02 VFM03 VCSC04 VCR05 3 Oxygen Depletion Sensing Pilot In the unlikely event of a pilot failure the pilot assembly should only be replaced by a GAS SAFE Registered Engineer The user must not carr...

Page 10: ...he coal set as per Ceramic Component Layout Instructions pages 13 14 5 The fire makes a roaring noise when lit Check That the front coal is seated correctly and the pilot hole is positioned correctly...

Page 11: ...and when ignited this can take two or three clicks it can be seen through the front coal set Keep the knob depressed for 10 15 seconds to allow the thermocouple to establish the pilot flame The knob c...

Page 12: ...only a soft brush to remove any soot deposits from the ceramic liners during cleaning as this is the only method that can be used to remove deposits The ceramic liners are very delicate and should be...

Page 13: ...ic liner Ensure that the lower part of the side cheeks sit on the front coal and are in front of the rear coal Fig 17 It is very important that all the coals are used and arranged as shown in order to...

Page 14: ...peaks of the fuel bed and are not placed in between This helps the flow of burnt gases and should give an even glowing fuel bed Fig 19 7 Lay another row of four coals on the next row up again making s...

Page 15: ...ht Remove the brass fret and check the pilot area for soot If soot is present remove all the loose coals and the front coal and thoroughly clean any debris in and around the pilot area If the fire wil...

Page 16: ...Unit 200 Glenfield Park Site 1 Philips Road Blackburn Lancashire BB1 5PF Tel 01254 695244 Fax 01254 695255 Web www legend fires com Email info legend fires com Issue B 13 9 11...

Reviews: