background image

All alarms that need to be connected in the 

house should be put into ‘Learn Mode’ by sliding 

the switch on the back of the alarm to the ‘Learn 

Mode’ position. 

The red LED will light up to indicate that ‘Learn 

Mode’ has been selected. 

Please note that when the alarms are placed 

in ‘Learn Mode’ they can’t be inserted into the 

mounting base. 

Do not take out the battery during ‘Learn Mode’ as 

this will interrupt the learn process. 
Press and hold the test button at one alarm only, 

until it beeps and the LED flashes. This alarm will 

become the master and will start sending out a 

specific house code to the other alarms. 

As  the  other  alarms  receive  the  specific  house 

code, they will also flash the LED light.

When  the red LED light flashes on all alarms, 

they are connected and MUST BE SWITCHED 

OUT OF ‘LEARN MODE’ and installed. 
Label the original “Learn” alarm in order to easily 

add new CAVIUS Wireless Family alarms to the 

system.
2. THE BEST AREAS TO INSTALL THE SMOKE 

ALARM:

• Install an alarm between possible fire sources 

and bedrooms as a minimum.

• Install alarms on each floor of the house, in hall-

ways and stairways. 

• Alarms in each room such as bed rooms and 

living rooms.

Additional alarms increase the security.

Optical smoke alarm device

Commercial reference: 2103

Developed by CAVIUS
The smoke alarm is designed for private homes.

PLEASE READ THE USER GUIDE 

CAREFULLY BEFORE INSTALLATION AND 

RETAIN FOR FUTURE USE.

SAFETY INSTRUCTIONS:

The device comes with a 3V lithium battery. Bat-

teries are to be handled with care and battery pow-

ered devices should be kept out of reach of chil-

dren. Do not try to recharge or burn the batteries.
TECHNICAL INFORMATION:

The maximum number of alarms that can be inter-

linked within a house group are 32. 
Please note: These must be alarms from the CAVIUS 

The distance between interlinked alarms depends 

on the house layout and they should always be 

tested after installation. It is not advised to get 

more than 10m distance between two smoke 

alarms.
Diameter: 65mm. Height: 44mm
The alarm is powered by a replaceable 3v CR123A 

lithium battery.
In normal situations, minimum battery life is 5 

years, but severe RF interferences may affect battery 

life of your device.

1. HOW TO SET UP AND CONNECT ALARMS: 

Start by pulling out the battery isolation strip as 

shown.

Please note: The product label must not be 

removed as it contains important information 

regarding the product. 

3. AREAS WHERE NOT TO INSTALL SMOKE-

ALARMS:

• In dusty rooms.

• At the top of a high pointed ceiling, in ceiling 

corners, and within 50cm of a wall.

• In rooms where the temperature goes out side 

+4

o

 to 38

o

C or above 90% relative humidity not 

condensing.

• In kitchens, garages, laundries, or too close to 

fireplaces; areas where either dampness, gases 

or smoke could occur.

Place the alarm where it is reachable in order to 

test the battery and for maintenance. 
4. PLACEMENT:
The smoke alarm is design to be installed on a 

ceiling or wall.
For ceiling installation:

The smoke alarm should be a minimum of 50cm 

from the wall. 

For catheral or peak ceiling or wall installation:

With a minimum of one smoke alarm per floor and 

a maximum distance between smoke alarms of 

10 meters. 
5. INSTALLING THE SMOKE ALARM:
Detach the alarm from the mounting base by 

twisting counter clockwise.

Use the mounting base ring to mark the screw 

holes on the ceiling or the wall. 

UK

MOUNTING

BASE

CHAMBER

FILTER

TEST BUTTON

RED LED

DO NOT 

REMOVE THE 

PRODUCT LABEL

ISOLATION 

STRIP

LEARN MODE

NORMAL MODE

MARK UP 

SCREW HOLES 

WITH A PEN

USE THE 

ENCLOSED 

SCREWS AND 

PLUGS

Peak ceiling

Minimum 50cm 

from peak

Minimum 30cm and 

maximum 50cm from 

ceiling

Wall

Ceiling

Minimum 50cm 

from wall

Wall

Ceiling

Reviews: