background image

Connect the 4 wires to the power supply: Live feed 

(L1), neutral (N), Ground (   ), lamp feed wire (L2).

Install the wires as shown.

Install the cableholder and replace the cover.

NOTE: After putting the wires through the alarm, 

check if the test button can move free. If the hole 

is too small the test button cannot move.

can be added to the system

Minimum 10cm

6.

 TEST FUNCTION:

After installation, and at least once per quarter, 

test all of your alarms to ensure they are operating 

correctly and are within range of each other.
It is recommended to check visually every week if 

the LED flashes correctly (every 48sec.).

Press the test button on any alarm for at least 10 

seconds.This will send out a test signal from the 

alarm; all other connected alarms should receive 

the signal within a short time. The alarms will emit 

a short beep and the LED will flash every 8 sec-

onds for 2 minutes. 

NOTE: Test function also transmits a weaker RF 

signal to ensure an optimal operation in normal 

conditions.
When the test signal is sent out, the alarms will 

respond in two ways:
1. A single beep every 8 seconds indicates that 

the alarms are connected and functioning.

2. Three short beeps every 8 seconds indicates a 

smoke sensor fault. The alarm should be cleaned 

by running the vacuum (on a low setting) around 

the smoke alarm chamber and tested again.
If required this indication can be stopped early on 

each alarm by a short press of the test button. 
TIP: It is safe to cover the sound output holes with 

your finger or a cloth during the testing to minimize 

the sound level emitted. 
If the problem continues, please visit www.cavius.com 

for any trouble shooting.

7. 

NORMAL MODE:

In normal mode the LED will flash every 48 seconds 

to show correct operation.

The green LED is on when the alarm is connected 

to mains power. It may take up to 1 minute to 

indicate that mains power has been connected.

8. 

 ALARM MODE:

When the smoke is detected, the smoke alarm will 

go into ‘Alarm Mode’. It will sound the alarm signal 

and the red LED will flash. 

The smoke alarm will also transmit the alarm signal 

to the other connected alarms, which will also 

sound the alarm signal after a short delay.

The CAVIUS Wireless Family have two different 

alarm signals: 

Alarm signal 1 (--- --- ---) is life threatening 

alarms, like a smoke alarm. 
Alarm signal 2 (-    -   -) is a non life threatening 

alarm, like a flooding alarm:
Smoke alarm signal:            --- --- ---
Heat alarm signal:                --- --- ---
Flood alarm signal:               -    -   -
CO alarm low level signal:    -    -   -
CO alarm high level signal:  --- --- ---

Please note that only the originating alarm’s red 

LED will flash, so it can be identified.

9.

 

PAUSE/HUSH FUNCTION:

If the smoke alarms are to set into a false alarm by 

cooking, fireplace, etc. they can be paused for 10 

minutes by pressing the test button on the origi-

nating smoke alarm only (indicated by the flashing 

LED).

The reason for this is that it is necessary to locate 

the source of the alarm before using the hush 

function.  This is to make sure that it is not a life 

threatening situation. 

10. 

 ADD EXTRA DEVICE:

The mains powered smoke alarm can be used 

together with the alarms in the CAVIUS wireless 

family: Smoke, Heat, Flood, CO & mains power 

alarms. All CAVIUS interconnected alarms within the 

   

as they run on the same frequency and use the 

same data protocol.This means that the wireless 

system can consist of a combination of smoke, 

heat, flood etc.
Place all alarms into ‘Learn Mode’ and repeat 

section 1.
Always test connection to all devices by repeating 

test function section 6 after adding devices. 

11. 

LOW BATTERY SIGNAL:

Your product has a battery back-up with a 1 year 

life in battery mode without mains power, and up 

to 10 years normal life with mains. However, we 

recommend to replace the battery every 5 years.

When the battery is starting its end of life, a short 

beep will sound out every 48 seconds for 30 days.

Light bulb: maximum 75W

Lamp: maximum 2 kgs weight

3

L2

N

L2

N

L1

N

N

L1 L2

HEAT ALARM

SMART REMOTE

FLOOD ALARM

SMOKE ALARM

MAINS POWERED

SMOKE ALARM

Summary of Contents for 2201-003

Page 1: ...garages laundries or too close to fireplaces areas where either dampness gases or smoke could occur Place the alarm where it is reachable in order to test the alarm and for maintenance 4 PLACEMENT The smoke alarm is designed to be installed on a ceiling With a minimum of one smoke alarm per floor and a maximum distance between smoke alarms of 10 meters For ceiling installation The smoke alarm shou...

Page 2: ...d OFF Remove the plastic cover to access to the power supply connector Pass the lamp wire through the smoke alarm 5 INSTALLING THE SMOKE ALARM NOTE THIS ALARM NEEDS TO BE INSTALLED BY A PROFESSIONAL MAKE SURE ELECTRICITY IS SWITCHED OFF BEFORE STARTING THE INSTALLATION CAUTION LIVE NEUTRAL AND EARTH MUST BE CORRECTLY INSTALLEDAND NOT MIXED UP NOTE The alarm is delivered in the packaging with a dus...

Page 3: ...d 8 ALARM MODE When the smoke is detected the smoke alarm will go into Alarm Mode It will sound the alarm signal and the red LED will flash The smoke alarm will also transmit the alarm signal to the other connected alarms which will also sound the alarm signal after a short delay The CAVIUS Wireless Family have two different alarm signals Alarm signal 1 is life threatening alarms like a smoke alar...

Page 4: ...the battery respecting the polarities Attach the alarm on power supply by twisting clockwise until it clicks and test the alarm 14 OTHER INFORMATION Do not paint the alarm Disposal For battery and product please dispose properly at the end of life This is electronic waste which should be recycled WARNING Please remove dust cover after installation Smoke will not be able to reach the chamber while ...

Reviews: