TRUE ON LINE UPS

TRUE ON LINE UPS

2. Safety Instructions

PLEASE READ THE FOLLOWING USER MANUAL AND THE SAFETY INSTRUCTIONS

BEFORE INSTALLING THE UNIT AND STARTING IT UP!

2-1 Transport

Please transport the UPS system  only in the original packaging  (to protect against

shock and impact).

2-2 Set-up

Condensation may occur if the UPS system is moved directly from a cold to a 

warm environment. The UPS system must be absolutely dry before being installed. 

Please allow an acclimatization time  of at least two hours.  

Do not install the UPS  system near water or in  damp environments. 

Do not install the UPS system where it would be exposed to direct sunlight or near heat. 

Do not block off ventilation openings in the UPS system's  housing.

2-3 Installation

Do not connect appliances or  items of equipment which would  overload the UPS 

system (e.g. laser printers) to  the UPS outlet socket 

Place cables in such a way that no one can step on or trip over them. 

Do not connect domestic appliances  such as hair dryers to  UPS output sockets. 

The UPS can be operated by any individuals with no previous experience 

Installation for 1K / 2K / 3K

Connect the UPS system only  to an earthed shockproof socket  outlet. 

The building wiring socket outlet (shockproof socket outlet) must be easily accessible

and close to the UPS system.

This is operator installable 

When installing the equipment, it should ensure that the sum of the leakage current

of the UPS and the  connected consumer does not exceed  3.5mA.

Installation for 6K / 10K

Warning: This is a product for restricted sales distribution  to informed partners. 

Installation restrictions or additional measures may be needed to prevent disturbances. 

A readily accessible disconnect device shall be incorporated in the building installation

wiring and must be close  to the UPS system.

This is permanently connected equipment and only qualified maintenance personnel

may carry out installations.

2-4 Operation

Do not disconnect the mains  cable on the UPS system  or the building wiring 

socket outlet (shockproof socket outlet) during operations since this would cancel

the protective earthing of the  UPS system and of all  connected loads. 

The UPS system features its  own, internal current sou rce (ba tteries).  The UPS  

output sockets or output terminals block may be electrically live even if the  UPS 

system is not connected to the building wiring socket outlet. 

In order to fully disconnect the UPS system, first press the  Standby switch then 

disconnect the mains lead 

Ensure that no fluids or other foreign objects can enter the UPS system. 

The UPS operates with hazardous voltages. Only qualified maintenance personnel

may carry out repairs

2-5 Maintenance, servicing and faults

The UPS system operates with  hazardous voltages. Repairs Should  be  carried out 

only by qualified maintenance personnel. 

Caution - risk of electric  shock. Even after the unit is disconnected from the mains 

power supply (building wiring socket  outlet), components inside the UPS  system

are still connected to the  battery and are still electrically  live and dangerous. 

Before carrying out any  kind of servicing and/or  maintenance, disconnect the 

batteries and verify that no  current is present and no  hazardous voltage exist in the 

terminals of high capability capacitor  such as BUS-capacitors. 

Summary of Contents for EA 900RT 10KVAH

Page 1: ...www cbcinter co th online UPS 1KVA 3KVA 1KVA 3KVA R Uninterruptible Power Supply R ...

Page 2: ...es the batteries and powers the inverter On the basis of this DC voltage the inverter generates a sinusoidal AC voltage which permanently supplies the loads Computers and periphery are thus powered entirely by the mains voltage In the event of power failure the maintenance free batteries power the inverter This manual covers the UPS listed as follows Please confirm whether it is the model you inte...

Page 3: ...d sales distribution to informed partners Installation restrictions or additional measures may be needed to prevent disturbances A readily accessible disconnect device shall be incorporated in the building installation wiring and must be close to the UPS system This is permanently connected equipment and only qualified maintenance personnel may carry out installations 2 4 Operation Do not disconne...

Page 4: ...es remove wristwatches rings and other metal objects use only tools with insulated grips and handles When changing batteries install the same number and same type of batteries Do not attempt to dispose of batteries by burning them This could cause battery explosion Do not open or destroy batteries Escaping electrolyte can cause injury to the skin and eyes It may be toxic Please replace the fuse on...

Page 5: ...e inverter The red FAULT LED lights up and an acoustic warning signal is issued continuously when the UPS system is in fault condition Press the Standby switch in order to turn off the warning tone BYPASS LED INVERTER LED FAULT LED BYPASS AC INPUT AC OUTPUT BATTERY ON OFF Function Display LOAD BATTERY CAPACITY LEDs 1 These LEDs show the load of the UPS system if the mains power is available normal...

Page 6: ...ay as follows Here display the input main power voltage parameter this numerical value can inspect main power voltage variety from 0V 290V INPUT VOLTAGE 220 0V INPUT VOLTAGE 220 0V Main power in or first time UPS ON LCD display LCD display content and relative work model LCD Display Screen Line LED Bypass LED Inverter LED Fault LED Battery LED Display Cycle Button LCD Display Screen Bypass LED Lin...

Page 7: ... 50 0HZ BATTERY CAPACITY 100 BATTERY CAPACITY 100 Press the Display cycle button on front panel once more LCD will display as follows 10 11 TRUE ON LINE UPS TRUE ON LINE UPS Here display the UPS output load capacity parameter this numerical value can inspect UPS take load capacity variety from 0 200 LOAD CAPACITY 100 LOAD CAPACITY 100 If no main power with main power but no bypass output battery v...

Page 8: ...tion Interface Fan 6KR Rear Panel Communication Interface Fan Communication Interface Fan Fan Input Switch 6K Rear Panel 10K Rear Panel Intelligent Slot Intelligent Slot Input Switch Battery Connector H Model Battery Connector H Model Communication Interface Network Fax Modem Surge Protection Intelligent Slot 2KR 3KR Rear Panel Battery Connector H Model Intelligent Slot Input Switch Terminal Block...

Page 9: ...L AMPERAGE OF YOUR INCOMING FEEDER 1 Inspection Inspect the packaging carton and its contents for damage Please inform the transport agency immediately should you find signs of damage Please keep the packaging in a safe place for future use Note Please ensure that the incoming feeder is isolated and secured to prevent it from being switched back on again 1 2 3KVA UPS Input connection 1KVAH Externa...

Page 10: ...ng the On Switch I or disconnecting the input of the UPS system from the power supply 6 Turn Off the UPS 2 Connection 2 1 UPS Input Connection If the UPS is connected via the power cord please use a proper socket with protection against electric current and pay attention to the capacity of the socket over 10A for 1KS H 2K over 16A for 2KH 3KS H 2 2 UPS Output Connection The output of 1KS H 2KS H a...

Page 11: ... Connection and operation for 6K 10K WHEN INSTALLING THE ELECTRICAL WIRING PLEASE NOTE THE NOMINAL AMPERAGE OF YOUR INCOMING FEEDER THIS SERIES IS NOT SUITABLE FOR 16 A SUB DISTRIBUTION BOARDS 6 Plug the external battery cord to the external battery socket on the rear panel of the UPS to complete the connection procedure and the UPS will start to charge the battery pack 2 One end of the external b...

Page 12: ...necting the input of the UPS system from the power supply CAUTION THE OUTPUT SOCKETS OF THE UPS SYSTEM MAYSTILL BE ELECTRICALLY LIVE EVEN IF THE POWER SUPPLYSYSTEM HAS BEEN DISCONNECTED OR THE UPS IS ON OFF POSITION 8 Turn Off the UPS 8 1 In Inverter Mode Press button continuously for more than 1 second to turn off the UPS Then the UPS will get into self test status first After having finished the...

Page 13: ...he problem persists please inform your dealer FAULT LED lights warning tone once a second Overload Remove loads of UPS output FAULT LED lights up permanent warning tone UPS fault Notify dealer Emergency supply period shorter than nominal value Batteries not fully charged batteries defect Charge the batteries for at least 1 2 hours and then check capacity If the problem still persists consult your ...

Page 14: ... 0Ah 20 12V 9 0Ah 8 2 Operating Environment Ambient Temperature Operating humidity Altitude Storage temperature 0 to 40 95 1000m 0 40 8 3 Typical stored energy time Typical values at 25 in minutes Model No 100 Load 50 Load 1K 5 14 2K 9 21 3K 5 15 6K 8 23 5 12 8 4 Dimensions and weights Model No Model No Model No Net Weight kg 145 400 220 14 145 400 220 7 192 460 340 34 5 192 460 340 15 192 460 340...

Page 15: ...Radiated Emission EN50091 2 Limits for UPS which have a rated output current exceeding 25A 25 100A EMS EN61000 4 2 ESD Level 4 EN61000 4 3 RS Level 3 EN61000 4 4 EFT Level 4 EN61000 4 5 lighting surge Level 4 EN61000 2 2 Immunity to low frequency signals 9 Communication port 9 1 RS232 Interface The following is the pin assignment and description of DB 9 connector Pin Description I O 2 TXD Output 3...

Page 16: ...n Lasting Beep Twice 1s Twice 1s Lasting Beep Lasting Beep Lasting Beep Lasting Beep Lasting Beep Once 2min Once 1s Lasting Beep Once 1s 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 No Work Model LED No Alarm Beep 0 35 Load Capacity 36 55 Load Capacity 56 75 Load Capacity 76 95 Load Capacity 96 105 Load Capacity 0 20 Battery Capacity 21 40 Battery Capacity 41 60 Battery Cap...

Page 17: ...the input wiring of each UPS 3 Connect the output wires of each UPS to an output breaker panel disconnect the jumper on JP1 and JP2 of the terminal block first and connect each output breaker to a main output breaker and then to the loads The requirement of the output wiring is as follows 2 Parallel installation When the distance between the UPS in parallel and the breaker panel is less than 20 me...

Page 18: ...32 TRUE ON LINE UPS Parallel Installation Diagram UPS1 O P Wiring Breaker I P L I P N I P CHD UPS1 O P Wiring Breaker UPS2 O P Wiring Breaker UPS2 O P Wiring Breaker I P L I P N I P CHD ...