Troubleshooting
125
If a hardware problem exists, the terminal switches off automatically.
The LED of the ON/OFF button transmits a series of blue flashes.
The LED flashes once per second and, dependent on the error, 1 to 27
times in succession. There is a two second pause at the end of the se-
quence. The sequence then starts again from the beginning. This makes
counting easier for you.
Restart the terminal. If the terminal switches off again, and the LED of
the ON/OFF button flashes blue again, the problem still exists.
You can rectify the problems listed in the following table locally.
Flashes
Cause/remedy
7
The temperature measured in the terminal exceeds 95°C. Possibly the temper-
ature sensor is defective.
/
Allow the terminal to cool before restarting. If the error reoccurs, the terminal
must be sent in.
25
The internal 12V power supply is unstable.
/
There may be a problem with the applied voltage at the terminal. Check the
power supply.
26
The internal 5V power supply is unstable.
/
There may be a problem with the applied voltage at the terminal. Check the
power supply.
27
The internal 3.3V power supply is unstable.
/
There may be a problem with the applied voltage at the terminal. Check the
power supply.
For all other hardware problems, the terminal must be sent in. Tell the
service partner how many flashes there are.
Blue flashing
signals of the
ON/OFF button