Technical Manual

GAMK (& GAM20K)

v2.0EN

1. Technical characteristics

Dimensions

Ø 172mm / breadth 91mm (without trim)

Installation

On 1.5" vacuum point

Power supply

Voltage: 12 V~ AC / Frequency: 50Hz/60Hz

Consumed power

25W

Weight

950g (projector only) / 1,2kg (with packaging)

LED type

27 monochrome MidPower LEDs / Cool White (~ 6000°K)/

Warm White (~ 3000°K)

PK10R100 (GAM20)

Cool White (~6000°K)

PK10R104 (GAM20K)

Warm White (~3000°K)

Risk group 1 (low risk) according to IEC62471:2006

IP Rating

IP-68

Max light stream

1400 lm max.

Floodlights must never be turned on outside of water.

1.1. Packaging Contents

1 BRIO GAM light with

• 2x0.75mm² cable: 3m (pre-assembled)

• Technical manual (this document)

2. Description

BRIO GAM LED light are designed to replace swimming pool projectors, traditionally equipped
with 300W PAR56 incandescent bulbs. They are installed exclusively in 1,5" vacuum outlet and
allow you to reduce your energy consumption and to light your swimming pool.

2.1. Trims

The GAM are supplied without trim, allowing the use of the trim of your choice;

www.c-

cei.fr

2

Summary of Contents for GAMK

Page 1: ...2 3 Installation 4 3 1 Placement of trim 4 3 2 Installing In wall through 1 5 threaded 1 5 vacuum point 5 4 Electrical Connections 6 5 Transformer Power 6 6 Projector Protection 6 7 Cable Cross Sectio...

Page 2: ...risk according to IEC62471 2006 IP Rating IP 68 Max light stream 1400 lm max Floodlights must never be turned on outside of water 1 1 Packaging Contents 1 BRIO GAM light with 2x0 75mm cable 3m pre ass...

Page 3: ...Technical Manual GAMK GAM20K v2 0EN Gaia PF10R14L W White RAL9003 PF10R14L G Grey RAL7040 PF10R14L S Sand RAL1015 PF10R14L A Anthracite RAL7016 www c cei fr 3...

Page 4: ...Installation 3 1 Placement of trim The trim of your choice not supplied with the GAM should clipped around the former as shown in the following illustration Put a clip then a second opposite of the fi...

Page 5: ...hreaded 1 5 vacuum point BRIO LED GAM GAM20K lights should be installed in a threaded 1 5 duct vacuum point for example We recommend that installation is per formed by a professional Please refer to t...

Page 6: ...tened in order to avoid any water in filtration Once startup and the operation tests are complete it is recommended to drown the connection with a reusable soft hydrophobic insulating gel ref CCEI PNS...

Page 7: ...5 4 6 The voltage drop in the supply cable of the GAM cable should be limited in order to comply with the applicable stan dards and ensure optimal illumination Follow the table opposite one projector...

Page 8: ...ue SAS FR47403521693 declares that product GAM GAM20K is compliant with the safety and electromagnetic compatibil ity requirements of European directives 2006 95 CE and 2004 108 CE Emmanuel Baret Mars...